| 120 | 1 | 120 VAC loads only - line to neutral | T1 (Red) and T3 (Black) hot; T2 (White) grounded neutral; green ground wire | One load with a maximum total wattage requirement equal to the generator's rated power output, with 120V across the generator output terminals |
| 120 | 1 | Line T1 (Red) to T2 (White) via circuit breaker CB1 | T1 (Red), T2 (White) | 120V single-phase 60 Hz loads |
| 120 | 1 | Line T3 (Black) to T2 (White) via circuit breaker CB2 | T3 (Black), T2 (White) | 120V single-phase 60 Hz loads; total unit load must not exceed maximum generator rating |
| 120 | Single | 120 volts only - dual circuits | Re-route stator lead 44 to ground stud previously occupied by 33; re-route lead 33 to line side of CB1; renumber ground wire 33 as 44; renumber 44A as 33A | Requires 12 AWG jumper between CB1 and CB1A; remove tie bar between breaker handles |
| 120 | Single | 120 volts only - dual circuits (conversion) | Stator lead 33 rerouted to line side of CB1A; stator lead 44 moved to ground stud; wire #44 renumbered #11; ground wire 33 renumbered 44; wire 44A renumbered 33A | Two stator windings, each protected by line breakers CB1 and CB1A (trip rating 35 amps); neutral (T2 white) is grounded |
| 120 | single phase | 120 VAC loads only - one load with maximum total wattage equal to the generator's rated power output; 120V across the generator output terminals | T1 (red), T2 (white), T3 (black), green ground; grounded neutral | Figure 1.1/5.1 - Connection for 120 Volts Only |
| 120 VAC only | 1-Phase | Single load, 120V across output terminals | 11P/22P, 33/44 | Max wattage equal to rated output |
| 120/240 | 1 | 120/240 VAC loads - dual voltage output | T1 (Red), T2 (White), T3 (Black) plus green ground wire | One 240V load at rated output, OR two separate 120V loads each at half rated output. Loads across T1-T2 and T3-T2 must not exceed ratings. Unit is reconnectable to 120 and/or 240 volts; not RVIA/ANSI listed when reconnected for dual voltage. |
| 120/240 | Single | Dual voltage - stator power windings connected in series (factory shipped) | Lead 11/11A to T1 (Red); lead 44/44A to T3 (Black); leads 22 and 33 grounded to T2 NEUTRAL (White); green ground lead | Tie bar connects the two switch handles on line breaker CB1 |
| 120/240 | Single | Series (dual voltage), factory default | 11/11A to T1 (red); 44/44A to T3 (black); 22 and 33 grounded to T2 neutral (white) | Four-position terminal block; tie bar connects CB1 and CB1A handles; CB1 and CB1A trip rating 35 A |
| 120/240 | single phase | 120/240 VAC loads - one load with maximum total wattage equal to rated output at 240V; or two separate loads each up to half rated output at 120V | T1 (red), T3 (black) are 'hot'; T2 (white) is the grounded neutral; green lead connects to ground | Figure 1.2/5.3 - Connection for 120/240 Volts; units not listed per RVIA/ANSI when reconnected for dual voltage output |
| 120/240 VAC | 1-Phase | Dual voltage output, two hot leads T1(11P/44 red) T3(33 black), neutral T2 (22P/33 white) | 11P, 22P, 33, 44 | No longer RVIA listed if reconnected for dual voltage |