The HGM560 is an engine. It powers generator sets from Kohler, including the 1300REZCK.
Also known as: HGM560
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 0 | No faults present | Decision-Maker 3+ Shutdown Fault Code | Info | |
| 0/0/0/0 | No error | Decision-Maker 8000 Error List | ||
| 0/0/1/6 | Illegal access | Read (write) of the communication object. Object intended only for write (read). | ||
| 0/0/2/6 | Comm. Object nonexistent | Decision-Maker 8000 Error List | ||
| 1 | Master switch not in auto (warning) | Decision-Maker 3+ Shutdown Fault Code | Warning | |
| 2 | Master switch error | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 3 | Overcrank | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 4 | Locked rotor | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 5 | Overspeed | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 6 | Low oil pressure prealarm (warning) | Decision-Maker 3+ Shutdown Fault Code | Warning | |
| 7 | Low oil pressure shutdown | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 8 | High coolant temperature prealarm (warning) | Decision-Maker 3+ Shutdown Fault Code | Warning | |
| 9 | High coolant temperature shutdown | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 10 | Low coolant temperature (warning) | Decision-Maker 3+ Shutdown Fault Code | Warning | |
| 11 | Aux. delay | Decision-Maker 3+ Shutdown Fault Code | ||
| 12 | Aux. immediate | Decision-Maker 3+ Shutdown Fault Code | ||
| 13 | MDEC/ADEC yellow alarm (warning) | Decision-Maker 3+ Shutdown Fault Code | Warning | |
| 14 | MDEC/ADEC red alarm | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 15 | Loss of ECM comms | Decision-Maker 3+ Shutdown Fault Code | Shutdown | |
| 16 | kW Overload | Decision-Maker 340 Alert Code | ||
| 17 | Under Frequency Warning | Decision-Maker 340 Alert Code | Warning | |
| 18 | High Battery Voltage | Decision-Maker 340 Alert Code | ||
| 19 | Coolant Temperature Signal Loss | Decision-Maker 340 Alert Code | ||
| 20 | Oil Pressure Signal Loss | Decision-Maker 340 Alert Code | ||
| 21 | Ground Fault Detected | Decision-Maker 340 Alert Code | ||
| 22 | Over Current | Decision-Maker 340 Alert Code | ||
| 23 | Engine Cooldown | Decision-Maker 340 Alert Code | ||
| 24 | Time Delay Engine Start | Decision-Maker 340 Alert Code | ||
| 25 | Generator Running | Decision-Maker 340 Alert Code | ||
| 26 | NFPA 110 Common Alarm | Decision-Maker 340 Alert Code | ||
| 27 | Starting Aid | Decision-Maker 340 Alert Code | ||
| 28 | Low Oil Pressure | Decision-Maker 340 Alert Code | ||
| 29 | High Coolant Temperature | Decision-Maker 340 Alert Code | ||
| 30 | Overcrank | Decision-Maker 340 Alert Code | ||
| 31 | Overspeed | Decision-Maker 340 Alert Code | ||
| 32 | Emergency Stop | Decision-Maker 340 Alert Code | ||
| 33 | Not In Auto | Decision-Maker 340 Alert Code | ||
| 34 | System Ready | Decision-Maker 340 Alert Code | ||
| 35 | Low Battery Voltage | Decision-Maker 340 Alert Code | ||
| 36 | Battery Charger Fault | Decision-Maker 340 Alert Code | ||
| 37 | Low Fuel | Decision-Maker 340 Alert Code | ||
| 38 | High Coolant Temperature Warning | Decision-Maker 340 Alert Code | Warning | |
| 39 | Low Oil Pressure Warning | Decision-Maker 340 Alert Code | Warning | |
| 40 | Low Coolant Temperature | Decision-Maker 340 Alert Code | ||
| 41 | Weak Battery | Decision-Maker 340 Alert Code | ||
| 42 | Load Shed Underfrequency | Decision-Maker 340 Alert Code | ||
| 43 | Load Shed Excess kW | Decision-Maker 340 Alert Code | ||
| 44 | Low AC Output | Decision-Maker 340 Alert Code | ||
| 45 | Overvoltage L1-L2 | Decision-Maker 340 Alert Code | ||
| 46 | Overvoltage L2-L3 | Decision-Maker 340 Alert Code | ||
| 46-66 | Digital Input 01-21 | Decision-Maker 550/6000 System Event Code | ||
| 47 | Overvoltage L3-L1 | Decision-Maker 340 Alert Code | ||
| 48 | Overvoltage L1-L0 | Decision-Maker 340 Alert Code | ||
| 49 | Overvoltage L2-L0 | Decision-Maker 340 Alert Code | ||
| 50 | Overvoltage L3-L0 | Decision-Maker 340 Alert Code | ||
| 51 | Undervoltage L1-L2 | Decision-Maker 340 Alert Code | ||
| 52 | Undervoltage L2-L3 | Decision-Maker 340 Alert Code | ||
| 53 | Undervoltage L3-L1 | Decision-Maker 340 Alert Code | ||
| 54 | Undervoltage L1-L0 | Decision-Maker 340 Alert Code | ||
| 55 | Undervoltage L2-L0 | Decision-Maker 340 Alert Code | ||
| 56 | Undervoltage L3-L0 | Decision-Maker 340 Alert Code | ||
| 57 | Master Switch Open (OFF/RESET) | Decision-Maker 340 Alert Code | ||
| 58 | Power-Down Error | Decision-Maker 340 Alert Code | ||
| 59 | Overfrequency Shutdown | Decision-Maker 340 Alert Code | Shutdown | |
| 74-81 | Reserved for additional input | Decision-Maker 550/6000 System Event Code | ||
| 75 | ECMCommunicationLoss | Decision-Maker 3000 Event Code 75; ECM Fault | Shutdown | |
| 82 | Defined Common Fault | Decision-Maker 550/6000 System Event Code | ||
| 99 | Genset Parameter Warning | Decision-Maker 550/6000 System Event Code | Warning | |
| 100 | Genset S/N Mismatch Warning | Decision-Maker 550/6000 System Event Code | Warning | |
| 101 | Genset S/N Mismatch Shutdown | Decision-Maker 550/6000 System Event Code | Shutdown | |
| 103 | Protective Relay Overvoltage | Decision-Maker 550/6000 System Event Code | ||
| 104 | Protective Relay Under Voltage | Decision-Maker 550/6000 System Event Code | ||
| 105 | Protective Relay Overfrequency | Decision-Maker 550/6000 System Event Code | ||
| 106 | Protective Relay Underfrequency | Decision-Maker 550/6000 System Event Code | ||
| 107 | Protective Relay Reverse Power | Decision-Maker 550/6000 System Event Code | ||
| 108 | Protective Relay Over Power | Decision-Maker 550/6000 System Event Code | ||
| 109 | Protective Relay Loss of Field | Decision-Maker 550/6000 System Event Code | ||
| 110 | Protective Relay Overcurrent Vr | Decision-Maker 550/6000 System Event Code | ||
| 111 | Reverse Power Shutdown | Decision-Maker 550/6000 System Event Code | Shutdown | |
| 112 | Over Power Shutdown | Decision-Maker 550/6000 System Event Code | Shutdown |
Showing the first 80 of 247 codes.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.
Tools: Belden #9841 or equivalent shielded twisted-pair cable
⚠ Accidental starting can cause severe injury or death.
⚠ Accidental starting can cause severe injury or death.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| APM802 RS-485 connections on TB10 | Connector 7 (--) Blue; Connector 8 (+) Green. Shield: do not connect at TB10 or base module; tape to insulate unused end. | 120 ohm resistor located on the base module. | ||
| Decision-Maker 3+ RS-485 connection (TB5) | Connect A to --, B to +, and GND to shield. | Use Belden #9841 or equivalent cable. Termination resistor X-6058-27 (121 ohms) connect + to -- on last device in network. | ||
| Decision-Maker 3500 TB12 RS-485 connection | COM (+) White; COM (--) Black. Shield: do not connect at TB12 or DEC 3500; connect shield at RSA III P27 connection only. | Use Belden #9844 or equivalent cable. | ||
| Decision-Maker 550 / 6000 RS-485 connector | Connect + to +, -- to --, GND to shield between devices. Use Belden #9841 or equivalent cable. | Termination resistor X-6058-27 (121 ohms) connect + to -- on last device in network. | ||
| Decision-Maker 8000 RS-485 connections (customer connection area, bottom panel) | Blue, high (H) or positive (+), wire connects to the A terminal; Green, low (L) or negative (--), wire connects to the B terminal. COM terminal also present. | Pull up jumper, pull down jumper, and 120 ohm resistor for RS-485 are located on the controller base box. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The HGM560 powers 1 generator set(s), including Kohler 1300REZCK.