HomeEnginesHercules G3400

Hercules G3400 Engine

The Hercules G3400 is a 5.56 L 6-cylinder engine. It powers generator sets from Kohler, including the ES799.

Also known as: Hercules G3400, G-3400

5.557 L
Displacement
6
Cylinders

Engine specifications

Displacement5.557 L
Cylinders6

Generator sets powered by this engine

1

Common problems

15
  • Starter not engaging
    Fix: Drive pinion may be spinning. Automotive crank plants only
  • S1 to terminal t3 on regulator open.
    Fix: *Correct connections.
  • No outflow (no exciter voltage-into AC volts)
    Cause: Regulator relay RR could be causing overcharged or undercharged battery--check this after resistor check
    Fix: Check contacts of relay CC may not be closing to complete battery charging circuit. Check brushes, AC leads, and AC armature for open circuits
  • No build-up.
    Cause: L Open circuit between battery and field. l Battery discharged.
    Fix: *Make correct connections. *l Charge battery.
  • Load relay L dirty or open contacts
    Fix: Check for dirty or open contacts--replace relay if needed
  • Insufficient load
    Fix: A load of 60 watts or more is needed to start automatic plant. A remote switch can be added to test run these plants--check diagrams
  • Generator output erratic.
    Cause: L Regulator sensing terminals not connected properly.
    Fix: *Check terminals 5 and 6 (120 V. connection) or terminals 5 and 7 (240 V. connection). *l Correct connections.
  • Generator faulty on plants with automotive cranking
    Fix: Check for faulty DC generator--excessive resistance in R2 resistor. If overcharging occurs, R2 resistance may be too little
  • Dirty commutator.
    Fix: *Clean commutator.
  • Cranking reset trips during cranking
    Fix: Reset the reset button--if plant still does not crank, check for open circuit
  • Cranking contactor C contacts do not close when switch is moved to on position
    Fix: Replace relay C
  • Choke heater circuit failure
    Cause: The choke valve could ‘stick’ the air cleaner
    Fix: Check the Ohm value of the resistor with a Volt-Ohmmeter. If faulty and allows higher voltage, it could cause the choke for starting
  • Check field circuit for open shunt
    Cause: Open field resistor connection
  • Center tap missing on three wire automatic plants
    Fix: Check for loose leads or missing center tap
  • Battery not being charged properly
    Cause: Check condition of battery--may be sulfated or have cracked cell. Replace as needed
    Fix: Check charge switch if left in HAND CRANK position, battery will not be charged

Compiled from service & troubleshooting documentation across every generator set that uses the Hercules G3400.

Maintenance schedule

ItemSpecCapacityPart #Interval
Fuel filterFuel Filter801112 Amazon eBay
Oil filterOil Filter801111 Amazon $69.06 eBay $107.90

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Also used in

2
  • Chicago Pneumatic 250RG-2 — Compressor
  • Quincy Compressor QS250 — Compressor

Other equipment known to use this engine, via filter-application cross-reference — useful for sourcing parts even when your exact machine isn't listed elsewhere on this page.

Common questions

What is the displacement of the Hercules G3400?

The Hercules G3400 has a displacement of 5.557 liters with 6 cylinders.

Which generators use the Hercules G3400 engine?

The Hercules G3400 powers 1 generator set(s), including Kohler ES799.

What is a common problem with the Hercules G3400 engine?

A commonly reported issue on generators using the Hercules G3400 is: Starter not engaging. Fix: Drive pinion may be spinning. Automotive crank plants only.