Home›Engines›General Motors Vortec (V-6)

General Motors Vortec (V-6) Engine

The General Motors Vortec (V-6) is a 4.3 L engine rated at 1800 rpm. It powers generator sets from Kohler, including the 38RCL. It holds 4.5 L (1.2 gal) of oil and 4.5 L (1.2 gal) of coolant.

Also known as: General Motors Vortec (V-6)

Part of the General Motors Vortec engine family — 4 variants share parts & fitment.

4.3 L
Displacement
1800 rpm
Rated speed
4.5 L
Oil capacity

Engine specifications

Oil capacity4.5 L
Coolant capacity4.5 L
Displacement4.3 L
Rated speed1800 rpm

Generator sets powered by this engine

1

Common problems

15
  • The generator set cranks but does not start, starts hard, lacks power, or operates erratically
    Cause: Air cleaner clogged
    Fix: Clean and/or replace the air cleaner.
  • Generator set stops suddenly
    Cause: Low oil pressure shutdown
    Fix: Check for oil leaks. Check the oil level and add oil if necessary.
  • The generator set does not crank
    Cause: Battery weak or dead
    Fix: Recharge or replace the battery.
  • No AC output
    Cause: AC circuit breaker in the OFF position
    Fix: Place the circuit breaker in the ON position.
  • Loss of communication to accessory modules
    Cause: Bad connections
    Fix: Check wiring and connections. Verify that cable size and length of run comply with the instructions in the Installation manual.
  • LCM relays do not operate
    Cause: Bad connections
    Fix: Check wiring and connections. Verify that cable size and length of run comply with the instructions in the Installation manual.
  • Low output or excessive drop in voltage
    Cause: Generator set overloaded
    Fix: Reduce the load.
  • Fuse M3, battery charging alternator, 70 amps M3
  • Fuse F6, starter, 20 amps F6
  • Fuse F4, ignition, 15 amps F4
  • Fuse F2, ECM 10 amps F2
  • Fuse F1, 5 amps F1
  • Fans run after engine shuts down
    Cause: The fans continue to run for 2 minutes after the engine shuts down to evacuate the engine compartment.
  • Date is flashing
    Cause: Controller power was disconnected and then reconnected
    Fix: Check battery connections. See Figure 5-1. Check utility power connection for the built-in battery charger. Reset the time, date, and exercise schedule. See Section 2.5.7, Setting the Exerciser at Power-Up.
  • Controller LCD display is off
    Cause: Low or no battery voltage
    Fix: Check connections. Check generator set battery. See Figure 5-1.

Compiled from service & troubleshooting documentation across every generator set that uses the General Motors Vortec (V-6).

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterN/A—500 hr
Fuel filterN/A—100 hr
Oil filterAPI Service Class SG, SH or SJ—9 hr
BatteryGroup 27F058665 Amazon eBay
BeltN/A—3 hr
OilSAE 15W-404.5 quarts0A379700019 hr Amazon eBay $16.00 NAPA $9.09
Spark plug0.045 inch (1.1 mm)—500 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

10
ItemActionHoursMonthsNotes
Engine oil levelCheck24 hrCheck the oil level in the crankcase every 24 hours of operation or before the engine is started each day
Air cleaner elementInspect100 hr
Change engine oil and filterChange100 hr
Check all bolts and nuts for tightnessCheck100 hr
Air cleaner elementReplace1000 hr
Belts and belt tensionCheck1000 hr
Engine coolantReplace5000 hr60 moWhen long-life coolant used
Check coolant levelCheck0 mo
Check engine oil levelCheck0 mo
Check for fluid leaksCheck0 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

12
TypeItemValueUnitCondition
GapSpark plug gap0.51mm (0.02 in.)
GapSpark plug gap0.7--0.8mm (0.028--0.030 in.)
GapSpark plug gap0.76mm (0.03 in.)
GapSpark plug gap0.8--0.9mm (0.03--0.04 in.)
GapSpark plug gap0.89mm (0.035 in.)
GapSpark plug gap0.9--1.0mm (0.036--0.04 in.)
TemperatureBlock heater thermostat cut-off temperature27--38°Ccoolant temperature
TemperatureBlock heater thermostat cut-off temperature80--100°Fcoolant temperature
TorqueSpark plug torque15Nm (11 ft. lb.)
TorqueSpark plug torque18Nm (13.3 ft. lb.)
TorqueSpark plug torque24.4--29.8Nm (18--22 ft. lb.)
TorqueSpark plug torque25Nm (18 ft. lb.)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% ethylene glycol0.6 LProvides freezing protection to --37_C (--34_F) and overheating protection to 129_C (265_F). Do not use alcohol or methanol antifreeze. Coolant added after block heater installation is approximately 0.6 L (0.2 gal).
CoolantLong-life coolantChange interval 5000 hours or 5 years when long-life coolant used; do not mix coolant types
Engine oilSAE 5W-30API Starburst (for gasoline engines)below -18°C4.7 LFor below -18C (0F)
Engine oilSAE 10W-30API Starburst (for gasoline engines)above -18°C4.7 LFor -18C (0F) and above; CC/CD classification and straight-weight industrial/stationary oils not acceptable

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

27
CodeNameMeaningSeverityAction
AC Sens LostAC Sensing LostIn Auto mode, generator output AC sensing is lost; starts 10 seconds after crank disconnect. Warning after 1 second if no output detected after crank disconnect; shutdown after 3 seconds if voltage was present and then lost.WarningContact an authorized distributor/dealer for service.
Accy PwrOverAccessory Power OverloadOver current fault on the accessory controller power outputWarning
Accy PwrOver WarningAccessory Power OverloadAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized distributor/dealer for service.
Alt Protect ShtdwnAlternator Protection ShutdownHigh generator current detected; shuts down to protect alternator windings from overheating (38RCL only).ShutdownReduce the load.
ATS Com ErrorATS Communication ErrorWarning is displayed if RXT interface connection is lost.WarningCheck communication wiring between transfer switch interface board and generator set.
ATS PhaseRotATS Phase Rotation MismatchTransfer switch phase rotation does not match; ATS will not transfer.WarningCorrect the ATS connection per the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
Aux InputAuxiliary InputAn optional customer-connected input is closed (digital input from optional PIM).ShutdownCheck customer-supplied equipment.
Batt Chg FltBattery Charger FaultInput to PIM from an external battery charger (not the built-in charger).WarningCheck external battery charger.
Battery Voltage HighBattery Voltage HighEngine starting battery voltage rises above 125% of the battery voltage setting for more than 10 seconds; inhibited during crank cycle.WarningCheck the battery rating and condition; check the battery charger operation.
Battery Voltage LowBattery Voltage LowEngine starting battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds when engine not running; inhibited during crank cycle.WarningCheck the battery rating and condition; check the battery charger operation; charge or replace the battery.
CAN comm faultCAN Communications FaultEngine CAN communications fault.ShutdownCheck wiring to ECM; check power to ECM.
Engine Coolant Temperature HighEngine Coolant Temperature HighEngine coolant temperature exceeds the maximum temperature for more than 5 seconds; active after crank disconnect.ShutdownCheck for blocked air inlets and exhaust outlets.
Engine Oil Pressure LowEngine Oil Pressure LowEngine ECM indicates low oil pressure for more than 5 seconds; active 30 seconds after crank disconnect.ShutdownCheck for leaks in the lubrication system; check the oil level and add oil if low.
EngineSpeed HighEngine Speed HighEngine speed exceeds 115% of normal running speed for more than 0.3 seconds.ShutdownContact an authorized distributor/dealer for service.
EngineSpeed LowEngine Speed LowEngine speed drops below 85% of normal running speed for more than 3 seconds.ShutdownReduce the load; contact an authorized distributor/dealer for service.
Exer Not SchExercise Not ScheduledNo exercise has been scheduled on the RDC2 controller.WarningSee exerciser setup instructions.
Generator Frequency HighGenerator Frequency HighGoverned frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds; active 10 seconds after engine start.ShutdownContact an authorized distributor/dealer for service.
Generator Frequency LowGenerator Frequency LowGoverned frequency falls below 90% of system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds; active 10 seconds after engine start.ShutdownReduce the load and restart the generator set; contact an authorized distributor/dealer for service.
Generator VoltageL1-L2 HighGenerator Voltage HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized distributor/dealer for service.
Generator VoltageL1-L2 LowGenerator Voltage LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart the generator set; contact an authorized distributor/dealer for service.
Lo Crank VltLow Cranking VoltageBattery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged.WarningCharge or replace the battery.
Locked RotorLocked RotorNo engine rotation is sensed during cranking; shuts down 3 seconds after the fault is detected.ShutdownCheck the battery; check for loose connections; contact an authorized distributor/dealer for service.
MainPwrOverL ShutdownMain Power OverloadAn over current fault on the controller power output (short circuit).ShutdownContact an authorized distributor/dealer for service.
Not in AutoNot in Automatic ModeThe generator set is not in Automatic (standby) mode; remote start/stop commands from a transfer switch or remote switch will be ignored.WarningPress AUTO to place the generator set in Automatic mode, when appropriate.
Over CrankOver CrankThree unsuccessful starting attempts.ShutdownCheck the fuel supply, spark plug, and battery; check for loose connections; contact an authorized distributor/dealer for service.
Speed Sensor FaultSpeed Sensor FaultEngine speed sensor has failed or engine stalled.ShutdownContact an authorized distributor/dealer for service.
Total Power High ShtDwnTotal Power High ShutdownMeasured load is greater than 102% of the generator set power rating for more than 1 minute (38RCL only).ShutdownReduce the load.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
RDC2 Voltage Calibration Using SiteTech adjustment

Tools: digital voltmeter, personal computer, SiteTech software

  1. Connect PC to controller via USB
  2. With generator off, connect multimeter across L1/L2 (AC volts)
  3. Start generator set
  4. Compare voltmeter reading to controller display
  5. Calculate new Genset Calibration Factor Voltage using (Vmeter / Vcontrol) x Fold = Fnew
  6. Enter new value into SiteTech and click Apply Changes
  7. Verify voltmeter matches controller display
  8. Repeat for L2-L3 and L3-L1 if three-phase
  9. Press OFF to stop generator set
RDC2 Voltage Calibration Using the Controller Keypad adjustment

Tools: digital voltmeter

  1. With generator off, connect digital multimeter across L1 and L2, set to AC volts
  2. Start generator set with RUN button
  3. Navigate to Generator Metering menu, press Select; Volts L1-L2 displayed
  4. Press Select; voltage number flashes
  5. Use up/down arrows to match voltmeter reading
  6. Press Select to confirm
  7. Step to Return screen
  8. Press OFF to stop generator set
VSC Current (Load) Calibration Using the Controller Keypad adjustment

Tools: clamp-on DC current probe or DC current meter

  1. Connect DC current probe/clamp meter to measure generator current
  2. Start generator with RUN button
  3. Adjust system voltage to obtain rated current output with battery bank attached (or use load bank)
  4. Trip output breaker
  5. Navigate to Generator Metering menu, select Generator Load
  6. Press and hold Select for No-Load Calibration; verify breaker open, confirm Yes
  7. Close output breaker; verify rated output current, confirm Yes
  8. Verify displayed load is correct; recalibrate if necessary
  9. Press OFF to stop generator set
Obtain DC2 Controller Password and Serial Number diagnostic
  1. Press OFF and verify that the generator set is not running.
  2. Press and hold the Exercise button until Press Again to Reset OnCue Plus PW is displayed.
  3. Release the Exercise button and press it again within 5 seconds.
  4. Write down the serial number (S/N) and password.
Obtain RDC/DC Controller Password diagnostic
  1. Press OFF to place the controller into OFF mode.
  2. Press the down arrow button (RDC) or exercise button (DC) 5 times.
  3. Note the four-digit code displayed on the controller; this is the controller password.
  4. Write down the password and press OFF to clear the display.
Obtain RDC2 or VSC Controller Password and Serial Number diagnostic
  1. Press the controller down arrow button to navigate to the Networking Information menu.
  2. Follow the reset password procedure shown in Figure 1-3.
  3. Write down the serial number (S/N) and password displayed for 10 seconds.
Power Cycle the Controller diagnostic
  1. Disconnect all input power for two minutes to allow capacitors to discharge.
  2. Remove the battery negative cable or disconnect P1 from the back of the controller.
  3. Disconnect the battery charger 120 VAC input power supply or disconnect P5 from the back of the controller.
  4. Unplug the USB mini-B connector from the front of the controller if plugged in.
  5. Wait two minutes, then reconnect power, hooking up battery power (P1) first.
Procedure to Reset the Controller after a Fault Shutdown diagnostic

⚠ Always identify and correct the cause of a fault shutdown before resetting the controller.

  1. Press the Select button to go to the Overview menu.
  2. Press Select again to display the active fault.
  3. Press Select; Confirm Clear Fault: NO is displayed.
  4. Press the Up arrow button; Confirm Clear Fault: YES is displayed.
  5. Press the Select button to enter YES and clear the fault.
  6. Press the Select button to return to the overview menu.
  7. Press AUTO to put the generator set into automatic mode.
Use Telnet to Check Server Connection diagnostic

Tools: Command prompt, Telnet Client

  1. Activate Telnet Client on the computer if necessary.
  2. Open a command prompt window.
  3. Enter telnet devices.kohler.com 5253.
  4. Successful connection displays the symbols shown in Figure 3-8.
Connect OnCue Plus for RDC/DC installation
  1. Install the Ethernet option board on the generator set controller. See TT-1566.
  2. Connect a network cable from the Ethernet board to your router or modem.
Connect OnCue Plus for RDC2/DC2/VSC installation
  1. Set the controller password before connecting the generator set Ethernet cable to the router.
  2. Connect the RJ45 inline connector included in the OnCue Plus kit to the Ethernet cable inside the generator enclosure.
  3. Connect one end of the customer-provided network cable to the RJ45 connector.
  4. Connect the other end of the network cable to the customer router or modem.
Install OnCue Plus Wireless for RDC2/DC2 installation
  1. Set the controller password.
  2. Follow instructions in TT-1618 to install, connect, and set up the wireless access point.
  3. The customer must have a wireless router for Internet access.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
100/2001Single
100/2003Delta
110/2201Single
110/2203Delta
115/2301Single
1201SingleGenset System Voltage/Frequency/Phase table for controller setup
120/2083Wye
120/2401Single
120/2403Delta
127/2203Wye
2201Single
220/3803Wye
2301Single
230/4003Wye
2401Single
240/4163Wye
277/4803Wye

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the General Motors Vortec family

7
Part #DescriptionCategory
0A4637Air CleanerAir filter
GM16944Element, air cleanerAir filter
NGE012014Charge Air Cooler BoltsBolt
058665BATTERY 12VDC 90-AH 27FService part / kit
GM36247Exhaust pipeService part / kit
GM58703Assy, J1939/ModBus/Ethernet Converter (network bridge)Service part / kit
GM71612-MA1X-612-25Service part / kit

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the General Motors Vortec (V-6)?

The General Motors Vortec (V-6) engine has an oil capacity of 4.5 liters.

What is the displacement of the General Motors Vortec (V-6)?

The General Motors Vortec (V-6) has a displacement of 4.3 liters.

Which generators use the General Motors Vortec (V-6) engine?

The General Motors Vortec (V-6) powers 1 generator set(s), including Kohler 38RCL.

How often should you change the oil in the General Motors Vortec (V-6)?

The General Motors Vortec (V-6) oil change interval is every 9 hours.

What is a common problem with the General Motors Vortec (V-6) engine?

A commonly reported issue on generators using the General Motors Vortec (V-6) is: The generator set cranks but does not start, starts hard, lacks power, or operates erratically. Cause: Air cleaner clogged. Fix: Clean and/or replace the air cleaner..