Ford SG875 Engine

The Ford SG875 is an engine. It powers generator sets from Cummins/Onan, including the EN SERIES.

Also known as: SG875, Ford SG875

Engine specifications

Generator sets powered by this engine

1
Cummins/Onan EN SERIES

Common problems

15
  • Engine will not crank
    Cause: Fault lamp on
    Fix: Correct fault and reset control
  • SWITCH OFF lamp flashes
    Cause: Run/Stop/Remote switch is in the STOP position which will prevent automatic starting if an automatic transfer switch is used
    Fix: Move the Run/Stop/Remote switch to the REMOTE position for automatic starting
  • OVERCRANK lamp lights and engine stops cranking
    Cause: Possible fuel or ignition system problem
    Fix: Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; check for dirty fuel filter and replace if necessary (see Maintenance section); check for dirty or plugged air filter and replace if necessary (see Maintenance section); check for loose connections in the ignition primary, ignition secondary, or solenoid valve circuits and correct as required; reset the control and restart after correcting the problem; contact an Onan dealer or distributor for service if none of the above
  • Engine runs and then shuts down, OVERSPEED lamp lights
    Cause: Engine has exceeded normal operating speed
    Fix: Contact an Onan dealer or distributor for service
  • Will not crank. Engine
    Fix: Indicates possible fault with control or starting system. Check for the following conditions: a. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections ... Clean the battery cable terminals and tighten all connections. c. Discharged or defective
  • The standard undesignated fault functions are lights; Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. FAULT 1 or FAULT 2
  • Remote circuit breaker is tripped. Engine starts from generator control panel but will not start automatically or from a remote panel (Note: Run/Stop/Remote switch must be in the REMOTE position for automatic or remote starting)
    Cause: Remote circuit breaker is tripped
    Fix: Reset breaker and restart; contact an Onan dealer or distributor if breaker trips after resetting
  • Remote circuit breaker is tripped. Remote circuit breaker
    Fix: Reset breaker but will not start automatically or from a remote panel (Note: Run/Stop/Remote switch must be in the REMOTE position for automatic or remote starting). Contact an Onan dealer or distributor if breaker trips after resetting.
  • PRE LO OIL PRES lamp lights. Engine continues to operate. PRE LO OIL PRES
    Fix: Indicates engine oil pressure has dropped to 20 psi (138 kPa). If engine can be stopped, follow procedures in step 5. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure.
  • PRE LO OIL PRES lamp lights. Engine continues to operate
    Cause: Engine oil pressure has dropped to 20 psi (138 kPa)
    Fix: If engine can be stopped, follow procedures in step 5; if generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure
  • PRE HI ENGINE TEMP lamp lights. Engine continues to operate. PRE HI ENGINE TEMP
    Fix: Indicates engine has begun to overheat and engine temperature has risen to approximately 205°F (97°C). If engine can be stopped, follow the procedures in step 3. Use the following procedures if generator is powering critical loads and cannot be shut down. a. Check air inlets and outlets and remove any obstructions to airflow. b. Open doors or windows in generator area to increase ventilation. c. Reduce load if possible by turning off non-critical loads.
  • PRE HI ENGINE TEMP lamp lights. Engine continues to operate
    Cause: Engine has begun to overheat and engine temperature has risen to approximately 205°F (97°C)
    Fix: If engine can be stopped, follow the procedures in step 3; if generator is powering critical loads and cannot be shut down: check air inlets and outlets and remove any obstructions to airflow; open doors or windows in generator area to increase ventilation; reduce load if possible by turning off non-critical loads
  • No AC output voltage
    Cause: Field breaker is tripped
    Fix: Reset breaker; contact an Onan dealer or distributor if voltage buildup causes breaker to trip
  • LO OIL PRES lamp lights. Engine shuts down. LO OIL PRES
    Fix: Indicates engine oil pressure has dropped to 14 psi (97 kPa). Check oil level and replenish if low. Reset control and restart. Contact an Onan dealer or distributor if oil pressure is not in the range of 35 to 60 psi (241 to 414 kPa) ...
  • LO OIL PRES lamp lights. Engine shuts down
    Cause: Engine oil pressure has dropped to 14 psi (97 kPa)
    Fix: Check oil level and replenish if low; reset control and restart; contact an Onan dealer or distributor if oil pressure is not in the range of 35 to 60 psi (241 to 414 kPa)

Compiled from service & troubleshooting documentation across every generator set that uses the Ford SG875.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter8419-1700-A600 hr Amazon eBay
Fuel filter8419-1600-A1200 hr Amazon eBay
Oil filter8419-1500-A1200 hr Amazon eBay
Batteryserviced and charged—
BeltDrive Belts8419-3500-A600 hr Amazon eBay
CoolantCooling System (Engine and Radiator)20.0 quarts (19 litres)—
Coolant filter—200 hr
OilReplace with Ford part number E4JL6754BA.E4JL6754BA Amazon eBay
Spark plug8419-2700-A3500 hr Amazon eBay

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Common questions

Which generators use the Ford SG875 engine?

The Ford SG875 powers 1 generator set(s), including Cummins/Onan EN SERIES.

What is a common problem with the Ford SG875 engine?

A commonly reported issue on generators using the Ford SG875 is: Engine will not crank. Cause: Fault lamp on. Fix: Correct fault and reset control.