Doosan P086 TI Engine

The Doosan P086 TI is a 8 L water-cooled engine rated at 1500 rpm. It powers generator sets from Caps and Doosan, including the CP180-TD1 and D220D5. It holds 12 L (3.2 gal) of oil and 48 L (12.7 gal) of coolant.

Also known as: Doosan P086 TI

8.0 L
Displacement
1500 rpm
Rated speed
12.0 L
Oil capacity

Engine specifications

Oil capacity12.0 L
Coolant capacity48.0 L
Displacement8.0 L
AspirationWater-cooled
Rated speed1500 rpm

Generator sets powered by this engine

2

Shared across brands: Caps, Doosan

Caps CP180-TD1Doosan D220D5

This engine also powers 3 machine(s) on Power Equipment Info.

How to read your Doosan engine serial & model number →

Common problems

15
  • Warning fault operates
    Fix: Check relevant switch and wiring of fault indicated on LCD display; Check configuration of input
  • Unit shuts down
    Fix: Check DC supply voltage is not above 35 Volts or below 9 Volts; Check the operating temperature is not above 70°C; Check the DC fuse
  • Unit is inoperative / Read/Write configuration does not operate
    Fix: Check the battery and wiring to the unit; Check the DC supply; Check the DC fuse
  • Starter motor inoperative
    Fix: Check wiring to starter solenoid; Check battery supply; Check battery supply is present on the Starter output of module; Ensure oil pressure switch or sensor is indicating the 'low oil pressure' state to the controller
  • Shutdown fault operates
    Fix: Check relevant switch and wiring of fault indicated on LCD display; Check configuration of input
  • Pre-heat inoperative
    Fix: Check wiring to engine heater plugs; Check battery supply; Check battery supply is present on the Pre-heat output of module; Check pre-heat configuration is correct
  • Module appears to 'revert' to an earlier configuration
    Fix: When editing a configuration using the PC software it is vital that the configuration is first 'read' from the controller before editing it. This edited configuration must then be 'written' back to the controller for the changes to take effect; When editing a configuration using the fascia editor, be sure to press the Auto Mode button to save the change before moving to another item or exiting the fascia editor
  • Low oil Pressure fault operates after engine has fired
    Fix: Check engine oil pressure; Check oil pressure switch/sensor and wiring; Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the module and is correctly configured
  • Incorrect reading on Engine gauges / Fail to stop alarm when engine is at rest
    Fix: Check engine is operating correctly; Check that sensor is compatible with the module and that the module configuration is suited to the sensor
  • Inaccurate generator measurements on controller display
    Fix: Check that the CT primary, CT secondary and VT ratio settings are correct for the application; Check that the CTs are wired correctly with regards to the direction of current flow (p1, p2 and s1, s2) and additionally ensure that CTs are connected to the correct phase (errors will occur if CT1 is connected to phase 2); Remember to consider the power factor (kW = kVA x powerfactor); The controller is true RMS measuring so gives more accurate display when compared with an 'averaging' meter such as an analogue panel meter or some lower specified digital multimeters; Accuracy of the controller is better than 1% of full scale. Generator voltage full scale is 415V ph-N, accuracy is ±4,15V (1% of 415V)
  • High engine temperature fault operates after engine has fired
    Fix: Check engine temperature; Check switch/sensor and wiring; Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the module
  • Generator fails to start on receipt of Remote Start signal
    Fix: Check Start Delay timer has timed out; Check signal is on 'Remote Start' input; Confirm correct configuration of input is configured to be used as 'Remote Start'; Check that the oil pressure switch or sensor is indicating low oil pressure to the controller; Depending upon configuration, then set will not start if oil pressure is not low
  • Fail to Start is activated after pre-set number of attempts to start
    Fix: Check wiring of fuel solenoid; Check fuel; Check battery supply; Check battery supply is present on the Fuel output of the module; Check the speed-sensing signal is present on the module's inputs; Refer to engine manual
  • Engine runs but generator will not take load
    Fix: Check Warm up timer has timed out; Ensure generator load inhibit signal is not present on the module inputs; Check connections to the switching device; Note that the set will not take load in manual mode unless there is an active load signal
  • Electrical Trip fault operates
    Fix: Check relevant switch and wiring of fault indicated on LCD display; Check configuration of input

Compiled from service & troubleshooting documentation across every generator set that uses the Doosan P086 TI.

Service intervals

1
ItemActionHoursMonthsNotes
Compressor oilChange1000 hr24 moCPS 11-10 and CPS 11-14: 1000 hours or once in every two years

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Aftermarket parts that fit this engine

6
65.06601-5050 FridayParts $243.94 250-III FridayParts $30.99 65.06601-0001A FridayParts $188.99 440211-00187 FridayParts $2798.99 TJ205DW5A FridayParts $2798.99 440211-00187C FridayParts $2950.99

Parts listed by aftermarket suppliers as fitting this engine — leads compiled from supplier catalogs; verify the exact part for your serial number.

Common questions

What is the oil capacity of the Doosan P086 TI?

The Doosan P086 TI engine has an oil capacity of 12.0 liters.

What is the displacement of the Doosan P086 TI?

The Doosan P086 TI has a displacement of 8.0 liters.

Which generators use the Doosan P086 TI engine?

The Doosan P086 TI powers 2 generator set(s), including Caps CP180-TD1, Doosan D220D5.

What is a common problem with the Doosan P086 TI engine?

A commonly reported issue on generators using the Doosan P086 TI is: Warning fault operates. Fix: Check relevant switch and wiring of fault indicated on LCD display; Check configuration of input.