Doosan G40-SIIIA Engine

The Doosan G40-SIIIA is a 3 L turbocharged engine rated at 2500 rpm. It powers generator sets from Doosan. It holds 5.5 L (1.5 gal) of oil and 5.5 L (1.5 gal) of coolant.

Also known as: Doosan G40-SIIIA

3.0 L
Displacement
2500 rpm
Rated speed
5.5 L
Oil capacity

Engine specifications

Oil capacity5.5 L
Coolant capacity5.5 L
Displacement3.0 L
AspirationTurbocharged
Rated speed2500 rpm

Troubleshooting

15

Symptoms & remedies

SymptomCauseRemedy
Engine runs but generator will not take loadCheck Warm up timer has timed out. Ensure generator load inhibit signal is not present on the module inputs. Check connections to the switching device.
Incorrect reading on Engine gaugesFail to stop alarm when engine is at rest Check engine is operating correctly. Check that sensor is compatible with the module and that the module configuration is suited to the sensor.
CAN ECU WARNING CAN ECU SHUTDOWNThis indicates a fault condition detected by the engine ECU and transmitted to the DSE controller.
CAN DATA FAILIndicates failure of the CAN data link to the engine ECU. Check all wiring and termination resistors (if required).
Inaccurate generator measurements on controller displayCheck that the CT primary, CT secondary and VT ratio settings are correct for the application. Check that the CTs are wired correctly with regards to the direction of current flow (pt, p2 and s1, s2) and additionally ensure that CTs are connected to the correct phase (errors will occur if CT1 is connected to phase 2). Remember to consider the power factor (kW = kVA x powerfactor). The controller is true RMS measuring so gives more accurate display when compared with an 'averaging' meter such as an analogue panel meter or some lower specified digital multimeters. Accuracy of the controller is better than 1% of full scale. Generator voltage full scale is 415V ph-N, accuracy is ±4,15V (1% of 415V).
Module appears to 'revert' to an earlier configurationWhen editing a configuration using the PC software it is vital that the configuration is first 'read' from the controller before editing it. This edited configuration must then be 'written' back to the controller for the changes to take effect. When editing a configuration using the fascia editor, be sure to press the Auto Mode button to save the change before moving to another item or exiting the fascia editor.
Engine does not startStarter does not turn.Battery discharged, Bad cable connections., Starter or starter switch failure., Safety relay failure.
Engine fires but stalls immediatelyAir in the fuel system.
Unit is inoperativeRead/Write configuration does not operate Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse.
Unit shuts downCheck DC supply voltage is not above 35 Volts or below 9 Volts. Check the operating temperature is not above 70°C. Check the DC fuse.
Fail to Start is activated after pre-set number of attempts to start.Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery supply is present on the Fuel output of the module. Check the speed-sensing signal is present on the module's inputs.
Continuous starting of generator when in the Auto Mode.Check that there is no signal present on the 'Remote Start' input. Check configured polarity is correct. Check the mains supply is available and within configured limits.
Generator fails to start on receipt of Remote Start signal.Check Start Delay timer has timed out. Check signal is on 'Remote Start' input. Confirm correct configuration of input is configured to be used as 'Remote Start'. Check that the oil pressure switch or sensor is indicating low oil pressure to the controller.
Pre-heat inoperativeCheck wiring to engine heater plugs. Check battery supply. Check battery supply is present on the Pre-heat output of module. Check pre-heat configuration is correct.
Starter motor inoperativeCheck wiring to starter solenoid. Check battery supply.

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.

Common problems

15
  • Unit shuts down
    Fix: Check DC supply voltage is not above 35 Volts or below 9 Volts. Check the operating temperature is not above 70°C. Check the DC fuse.
  • Unit is inoperative
    Fix: Read/Write configuration does not operate Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse.
  • Starter motor inoperative
    Fix: Check wiring to starter solenoid. Check battery supply.
  • Pre-heat inoperative
    Fix: Check wiring to engine heater plugs. Check battery supply. Check battery supply is present on the Pre-heat output of module. Check pre-heat configuration is correct.
  • Module appears to 'revert' to an earlier configuration
    Fix: When editing a configuration using the PC software it is vital that the configuration is first 'read' from the controller before editing it. This edited configuration must then be 'written' back to the controller for the changes to take effect. When editing a configuration using the fascia editor, be sure to press the Auto Mode button to save the change before moving to another item or exiting the fascia editor.
  • Incorrect reading on Engine gauges
    Fix: Fail to stop alarm when engine is at rest Check engine is operating correctly. Check that sensor is compatible with the module and that the module configuration is suited to the sensor.
  • Inaccurate generator measurements on controller display
    Fix: Check that the CT primary, CT secondary and VT ratio settings are correct for the application. Check that the CTs are wired correctly with regards to the direction of current flow (pt, p2 and s1, s2) and additionally ensure that CTs are connected to the correct phase (errors will occur if CT1 is connected to phase 2). Remember to consider the power factor (kW = kVA x powerfactor). The controller is true RMS measuring so gives more accurate display when compared with an 'averaging' meter such as an analogue panel meter or some lower specified digital multimeters. Accuracy of the controller is better than 1% of full scale. Generator voltage full scale is 415V ph-N, accuracy is ±4,15V (1% of 415V).
  • Generator fails to start on receipt of Remote Start signal.
    Fix: Check Start Delay timer has timed out. Check signal is on 'Remote Start' input. Confirm correct configuration of input is configured to be used as 'Remote Start'. Check that the oil pressure switch or sensor is indicating low oil pressure to the controller.
  • Fail to Start is activated after pre-set number of attempts to start.
    Fix: Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery supply is present on the Fuel output of the module. Check the speed-sensing signal is present on the module's inputs.
  • Engine runs but generator will not take load
    Fix: Check Warm up timer has timed out. Ensure generator load inhibit signal is not present on the module inputs. Check connections to the switching device.
  • Engine fires but stalls immediately
    Cause: Air in the fuel system.
  • Engine does not start
    Cause: Starter does not turn.
    Fix: Battery discharged, Bad cable connections., Starter or starter switch failure., Safety relay failure.
  • Continuous starting of generator when in the Auto Mode.
    Fix: Check that there is no signal present on the 'Remote Start' input. Check configured polarity is correct. Check the mains supply is available and within configured limits.
  • CAN ECU WARNING CAN ECU SHUTDOWN
    Fix: This indicates a fault condition detected by the engine ECU and transmitted to the DSE controller.
  • CAN DATA FAIL
    Fix: Indicates failure of the CAN data link to the engine ECU. Check all wiring and termination resistors (if required).

Compiled from service & troubleshooting documentation across every generator set that uses the Doosan G40-SIIIA.

Common questions

What is the oil capacity of the Doosan G40-SIIIA?

The Doosan G40-SIIIA engine has an oil capacity of 5.5 liters.

What is the displacement of the Doosan G40-SIIIA?

The Doosan G40-SIIIA has a displacement of 3.0 liters.

Which generators use the Doosan G40-SIIIA engine?

The Doosan G40-SIIIA powers 1 generator set(s), including Doosan G40-SIIIA.

What is a common problem with the Doosan G40-SIIIA engine?

A commonly reported issue on generators using the Doosan G40-SIIIA is: Unit shuts down. Fix: Check DC supply voltage is not above 35 Volts or below 9 Volts. Check the operating temperature is not above 70°C. Check the DC fuse..