The Cummins/Onan V1710-P500 is a 1.71 L natural engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the DFT Series. It holds 21 L (5.5 gal) of coolant.
Maintenance schedule
| Item | Spec | Capacity | Part # | Interval | |
|---|
| Air filter | Air Filter | | — | | |
| Fuel filter | Fuel Filter | | — | | |
| Oil filter | Engine Oil Filter | | — | | |
| Battery | Battery | | — | | |
| Belt | Belt | | — | | |
| Coolant | Coolant | 21.0 Gallons | — | | |
| Oil | Engine Oil | 21.0 Gallons | — | | |
| Spark plug | Spark Plug | | — | | |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
Procedures
10Engine Speed Adjustment adjustment
⚠ Original factory governor setting should not be disturbed.
Tools: tachometer, frequency meter
- See that injection pump is properly timed to engine. Refer to Cummins engine manual.
- Refer to instructions in Cummins manual for governor adjustment.
- Adjust engine speed to 1800-rpm for 60-cycle operation and 1500-rpm for 50-cycle operation.
- Use accurate tachometer or frequency meter connected to AC generator output terminals. Multiply frequency by 30 to obtain engine speed.
- Check generator voltage. Make slight re-adjustment of speed setting to obtain preferred voltage at average load. A range of 1830 to 1890-rpm (61 to 63 cycles) should give desired voltage.
Testing Rotating Rectifier Assembly diagnostic
Tools: ohmmeter
- Remove access cover from exciter end of generator.
- Isolate each of the six diodes before proceeding.
- Use an ohmmeter to measure resistance in individual diode. Reverse leads and repeat.
- A good diode should have high resistance one measurement and low when leads are reversed.
- Check all diodes in accordance with reverse measurement step.
Generator Alignment for DFT Generating Plants installation
Tools: mounting bolts as jackscrews, shims
- Set plant on its mounting foundation.
- Remove two mounting bolts securing generator support to skid base. Remove shims.
- Secure skid base to mounting foundation.
- Measure clearance from top surfaces of skid base to both mounting surfaces of generator support.
- Add clearance and weight correction figure to determine total shims required.
- Use mounting bolts as jackscrews to increase clearance and place shims.
- Lower generator to rest on shims. Total clearance must equal base-to-support clearance plus weight correction.
- Remove jackscrew bolts and install as mounting bolts. Secure and lock.
Battery Electrolyte Dilution for Hot Locations maintenance
⚠ Avoid skin or clothing contact with electrolyte. Dispose safely.
Tools: hydrometer, filler bulb
- Fully charge the battery.
- With battery still on charge, draw off electrolyte above plates in each cell using hydrometer or filler bulb.
- Refill each cell with distilled water to normal level.
- Continue charging for 1 hour at 4- to 6-ampere rate.
- Test each cell. If specific gravity still above 1.225, repeat steps 2-4 until reading is 1.225.
Dust and Dirt maintenance
- Keep plant clean. Keep cooling system free of dirt, etc.
- Service air cleaners as frequently as necessary.
- Change crankcase oil every 100 operating hours.
- Keep oil and fuel in dust-tight containers.
- Keep injector pump linkage clean.
Out-of-Service Protection maintenance
Tools: rust inhibitor, SAE #50 oil, clean cloth, cover
- Run plant until thoroughly warm.
- Drain oil from oil base while still warm. Refill and attach warning tag stating oil viscosity used.
- Remove each injector. Pour 1 oz. (two tablespoons) of rust inhibitor or SAE #50 oil into each cylinder. Install injector.
- Service air cleaner as outlined in Cummins manual.
- Clean governor linkage and protect by wrapping with clean cloth.
- Plug exhaust outlets to prevent entrance of moisture, bugs, dirt, etc.
- Wipe entire unit. Coat parts susceptible to rust with light film of grease or oil.
- Provide suitable cover for entire unit.
- If battery is used, disconnect and follow standard battery storage procedure.
High Temperature Operation operation
- See that nothing obstructs air flow to and from plant.
- Keep cooling system clean.
- Use correct SAE No. oil for temperature conditions.
Low Temperature Operation operation
- Use correct SAE No. oil for temperature conditions. Change oil only when engine is warm.
- Use fresh fuel. Protect against moisture condensation.
- Keep fuel system clean, and batteries in well charged condition.
- Partially restrict cool air flow but use care to avoid overheating.
- Refer to Cummins manual for additional information.
Brush Assembly Removal repair
Tools: screwdriver
- Remove three No. 10-24 screws fastening voltage regulator to DC alternator. Remove regulator to access phenolic cover, disconnecting leads as required.
- Remove two No. 8-32 screws on phenolic cover and lift out cover and gasket.
- Pull brush assembly straight up and lift out.
- For reassembly, reverse procedure.
Replacement of Diodes repair
⚠ Excessive heat can damage a diode.
Tools: soldering iron, wrenches, needle nose pliers
- Unsolder leadwires from diode terminal.
- Use proper size wrenches to hold body of diode while removing nut attaching diode to heat sink.
- Push diode free of its mounting hole in heat sink.
- Install new diode in same position (or direction) as defective diode.
- Insert new diode into mounting hole in heat sink or bracket. Secure with nut and washer.
- Connect leadwires to appropriate terminals.
- Solder leadwires removed from defective diode to terminal of new diode. Use needle nose pliers to absorb heat.
- Replace access cover.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Parts cataloged across the Cummins/Onan V1710 family
8| Part # | Description | Category |
|---|
| 305C455 | Regulator, Voltage | Avr |
| 511-37 | Belt, Alternator Drive | Belt |
| 320P240 | Bracket, Mounting - Engine | Bracket |
| 364-6 | Rectifier, Gate Controlled 300-Volt, 5.5 Ampere - Neg. Base | Service part / kit |
| B184 | PHASE SELECTOR SWITCH | Service part / kit |
| 309B178 | Switch, High Water Temperature Cut-Off - Non - Adjustable - Replaces 309B1 | Sensor |
| 309B64 | Switch, Low Oil Pressure Cut-off (Mounts on Engine) Optional Equipment - Replaces switch used Prior to Spec "F" with higher pressure break. | Sensor |
| 309-0253 | Thermostat | Thermostat |
Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.
Common questions
What is the displacement of the Cummins/Onan V1710-P500?
The Cummins/Onan V1710-P500 has a displacement of 1.71 liters.
Which generators use the Cummins/Onan V1710-P500 engine?
The Cummins/Onan V1710-P500 powers 1 generator set(s), including Cummins/Onan DFT Series.
What is a common problem with the Cummins/Onan V1710-P500 engine?
A commonly reported issue on generators using the Cummins/Onan V1710-P500 is: Fault lamp lights after engine is running. Cause: Oil level - engine will shut down after approximately 12-1/2 seconds if low oil pressure sensor does not open. Fix: Check oil level.