Home›Engines›Cummins/Onan QSJ999G

Cummins/Onan QSJ999G Engine

The Cummins/Onan QSJ999G is a 1 L 2-cylinder naturally aspirated engine rated at 3600 rpm. It powers generator sets from Cummins/Onan, including the RS13A, RS13A C13N6H, RS17A and RS17A C17N6H.

Also known as: Cummins QSJ999G

1.0 L
Displacement
2
Cylinders
3600 rpm
Rated speed

Engine specifications

Displacement1.0 L
Cylinders2
AspirationNaturally aspirated
Rated speed3600 rpm

Service intervals

6
ItemActionHoursMonthsNotes
Engine Oil LevelCheck24 hrAlso check daily during power outages, or monthly without power outages.
Engine Oil and Oil FilterChange200 hr24 moFirst service — First 25 hours.
Complete System TestTest200 hr24 moMust be performed by a qualified service technician; see transfer switch manual.
Engine Air FilterReplace200 hrPerform more often in dusty conditions.
Engine Valve ClearanceAdjust200 hr24 moMust be performed by a qualified service technician.
Starting BatteryClean200 hrClean and check starting battery.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapSpark Plug Gap0.7 - 0.8mm (0.027 - 0.031 in)
PressureFuel Shutoff Solenoid Coil Voltage Threshold10.2VDCwhile attempting to start
PressureFuel supply pressure (LP)7-11in H2O
PressureFuel supply pressure (Natural gas)5-11in H2O
PressureLubricating Oil Pressure at Rated Speed (Minimum)310kPa (45 psi)at rated speed
PressureMaximum Fuel Supply Pressure (either fuel)3.2kPa (13 inch water column)under any condition
PressureNatural Gas Fuel Supply Pressure3.5 - 12inch water column (0.9 - 3.0 kPa)
PressurePropane Vapor Fuel Supply Pressure1.5 - 3.0kPa (6 - 12 inch water column)
ResistanceGovernor Actuator Resistance2.8 ±5%Ohms
ResistanceRotor Ground Resistance> 1 megohm on megger, or infinity on an ohmmetermegohm
ResistanceRotor Winding Resistance F1 to F2 (13 kW)26 +/-10%Ohmsat 75 °F room temperature
ResistanceRotor Winding Resistance F1 to F2 (17/20 kW)30.5 +/-10%Ohmsat 75 °F room temperature
ResistanceSense L1(W) - Sense L2(V) (13 kW)0.24 +/-10%Ohms
ResistanceSense L1(W) - Sense L2(V) (17/20 kW)0.107 +/-10%Ohms
ResistanceStator Ground Resistance> 1 megohm on megger, or infinity on an ohmmetermegohm
ResistanceStator Winding Resistance L1 to N (13 kW)0.112 +/-10%Ohmsat 75 °F room temperature
ResistanceStator Winding Resistance L1 to N (17/20 kW)0.042 +/-10%Ohmsat 75 °F room temperature
ResistanceStator Winding Resistance Q1 to Q2 (13 kW)2.56 +/-10%Ohmsat 75 °F room temperature
ResistanceStator Winding Resistance Q1 to Q2 (17/20 kW)1.45 +/-10%Ohmsat 75 °F room temperature
SpeedRated RPM3600rpm
TemperatureAlternator Temperature Switch Contacts Open197 - 210°F (92 - 99 °C)
TorqueAC Battery Charger Screws0.9 - 1.2Nm
TorqueAccess Panel Fasteners (oil drain)5.0 - 6.6Nm
TorqueAir-Fuel Mixer Flange Bolts13ft-lb (17.5 Nm)
TorqueAirbox Cover Bolts3.2 - 4.0Nm
TorqueAirbox Mounting Brackets Bolts3.2 - 4.0Nm
TorqueAirbox to Mixer/Throttle Body Nuts3.2 - 4.0Nm
TorqueAlternator Fan/Rotor Retention Nut113 - 139Nm
TorqueAlternator Ground Strap to Skid Bolt5 - 6.2Nm
TorqueAlternator Ground Strap/B- to End Bell Bolt12.3 - 15Nm
TorqueAlternator Heater18 - 22Nm
TorqueAlternator Leads into Circuit Breaker4 - 5Nm
TorqueAlternator Leads into Circuit Breaker: Bonding Jumper4 - 5Nm
TorqueAlternator Leads into Circuit Breaker: Neutral Lead/Lug Bolt5.5 - 6.5Nm
TorqueAlternator Leads into Circuit Breaker: Neutral Lug Hex Screw4 - 5Nm
TorqueBattery Charge Alternator Mounting Bolts8 - 12Nm
TorqueBattery Tray Bolt3.2 - 4Nm
TorqueBrush Block Access Panel (Plastic) Bolt3.2 - 4Nm
TorqueBrush Block Bolts2.3 - 3.2Nm
TorqueControl Board Bracket to Enclosure Bolt9.8 - 11.9Nm
TorqueControl Board to Bracket Mounting Bolt2.8 - 3.5Nm
TorqueCrankcase Reed Valve Cover Bolts8 - 12Nm
TorqueCylinder Head Bolts50Nmtighten in pattern shown
TorqueDipstick (Shipped Separately)9.8 - 11.9Nm
TorqueEnclosure Hood Hinge Assembly Bolts5.6 - 6.6Nm
TorqueEnclosure M6 Bolts - All Panel Connections and Cross Bars5.6 - 6.6Nm
TorqueExhaust Baffle to Muffler Clamp Nuts13.9 - 16.8Nm
TorqueExhaust Manifold Nuts33 - 40Nm
TorqueFlywheel Nut90 - 105Nm
TorqueGovernor Actuator Bracket to Engine Bolts5.0 - 6.2Nm
TorqueGovernor Actuator Mounting Bolts9.8 - 11.9Nm
TorqueHead Bolts50 - 55Nm
TorqueHood Latch Bolt5.6 - 6.6Nm
TorqueInner Enclosure Panel to Skid Nuts/Bolts5.6 - 6.6Nm
TorqueIntake Manifold Nuts11 - 14NmLocking feature of nut faces outward
TorqueIsolator Bolts - Alternator24 - 29Nm
TorqueIsolator Bolts - Engine24 - 29Nm
TorqueLower Fuel System Mounting Bolts9.8 - 11.9Nm
TorqueMixer Fuel Inlet Fitting/Lock Nut58.3 - 77.3Nm
TorqueMuffler Mounting Bolts9.8 - 11.9Nm

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oil0W30Full synthetic gasoline engine oil which meets or exceeds API service SN/SN-RC and ILSAC GF-52.3 LAll temperatures, required below -17 °C (0 °F)
Engine oil5W30Full synthetic gasoline engine oil which meets or exceeds API service SN/SN-RC and ILSAC GF-5above -17°C2.3 LTemperatures above -17 °C (0 °F)
Engine oilAutomotive-style lubrication system-7°C to 50°C2.3 LOil cooler and spin-on filter included
FuelLP vaporNominal fuel rating 93 MJ/M3 (2500 Btu/ft3)Fuel supply pressure LP 7-11 in H2O
FuelNatural gasNominal fuel rating 37 MJ/M3 (1000 Btu/ft3)Fuel supply pressure NG 5-11 in H2O

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

18
CodeNameMeaningSeverityAction
2Low Oil Pressure FaultContinuous ground (greater than or equal to 3 seconds) at the generator set control for oil pressure input. The switch opens the control circuit with pressure.ShutdownMeasure the oil level; disconnect the oil pressure switch and measure continuity from P1-6 and GND; verify switch operation; measure oil pressure with a mechanical gauge; repair or replace relief valve and oil pump if necessary.
4OvercrankThe generator set control did not sense alternator quad winding frequency after cycle crank (30 seconds of cranking and 15 seconds between each crank attempt for a total of 3 crank attempts).ShutdownCheck fuel supply, air/fuel mixture, ignition system, starter, battery and wiring. Check air filter and exhaust. Measure quad voltage during cranking and winding resistances.
12OvervoltageInstantaneous Fault: AC voltage S1-S2 greater than 300 VAC. Delayed Fault: AC voltage line-to-line greater than 268 VAC but less than 300 VAC for 3 continuous seconds.ShutdownMeasure AC voltage at the circuit breaker and pins P1-34/P1-35. Cycle loads. Reseat P1. Measure field, quadrature and main winding resistance.
13UndervoltageAC voltage 240 line-to-line is less than 216 VAC for 5 continuous seconds.ShutdownMeasure AC voltage and frequency. Balance loads within 10% line-to-line. Reseat P1. Measure winding resistance and check brush alignment.
14OverfrequencyInstantaneous Fault: Frequency greater than 72 Hz. Delayed Fault: Frequency greater than 66 Hz but less than 72 Hz for 6 continuous seconds.ShutdownMeasure AC current and frequency. Check exhaust, fuel supply, governor actuator, demand regulator and throttle plate. Measure winding resistance and check brush alignment.
15UnderfrequencyFrequency less than 54 Hz (for the 60 Hz model) for 8 continuous seconds.ShutdownMeasure AC current, frequency and load capability. Check air filter, exhaust, fuel supply, governor and ignition. Measure winding resistance and check brush alignment.
19Governor Actuator ShutdownController sensed governor actuator circuit is open or shorted.ShutdownMeasure and verify governor actuator resistance (2.8 Ohms ±5%). Verify governor wiring to the control. Replace if necessary.
22Governor Actuator OverloadMaximum governor output (PWM) for 10 continuous seconds.ShutdownMeasure AC current. Check air filter, fuel supply, intake manifold and gaskets, exhaust and ignition. Verify the actuator function and check the governor linkage.
27Voltage Sense LostThe generator set frequency is greater than 40 Hz and voltage sensed is less than 5 VAC on one or both lines.ShutdownMeasure the AC voltage. Reseat P1. Measure field, quadrature and main winding resistance. Check brush alignment.
29High Battery VoltageDC voltage to controller greater than 19 VDC.ShutdownMeasure DC voltage at the battery, at the generator set and at connector P1. Measure DC voltage with the battery charger turned on and diagnose the faulty charger.
32Low Cranking Speed SenseQuadrature frequency is less than 1 Hz (engine RPM is less than 180) for 3 continuous seconds after pressing start.ShutdownCheck battery and connections. Verify engine and alternator rotation. Check J1 pins. Measure DC voltage at the starter. Check air filter, exhaust, fuel supply and ignition.
35Control Card FailureEEPROM (programming variables) error during self-test.ShutdownReplace the control.
36Generator Set Stopped Without Fault ConditionRPM is less than 500 and sense voltage S1-S2 is at 0 VAC and no other fault condition occurred.ShutdownVerify engine and alternator rotation. Check air filter, exhaust, fuel supply, governor and ignition. Measure winding resistance.
37Invalid Set ConfigurationGenerator set control configuration does not meet any valid configuration.ShutdownUsing the display, reset and save the generator set configuration. If correct and the fault will not clear, replace the control.
43Processor FaultRAM (programming variables) error during self-test.ShutdownReplace the control as necessary.
45Speed Sense FaultWhile running, the quadrature frequency dropped to 0 Hz for 1 continuous second.ShutdownInspect and clean slip rings. Measure quadrature winding resistance between P1-2 and P1-3. Check harness continuity. Measure frequency and droop.
46Generator Set OverloadThe total generator set load is above 105% of rated.ShutdownMeasure the AC current and voltage while running with all connected loads. Identify faulty or short cycling loads and reduce loads as necessary.
76Alternator Over TempThe temperature at the alternator is too high. The high temperature switch opens between 197 - 209 °F (91.5 - 98.5 °C). An open condition on this circuit triggers the fault.ShutdownVerify the air inlet and air outlet panels are not obstructed. Measure the temperature sensor wiring (P1-33 to GND) for continuity. Inspect the cooling fan.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Converting the Fuel System Type adjustment

⚠ Do not rotate the center section of the valve beyond the detent.

Tools: 6 mm external hex wrench

  1. From the Main screen, select Menu; hold the Next key at least 5 seconds to view the Config Menu.
  2. Highlight 'Config' and click Enter. Use the Next key to navigate to the Fuel Type field; select NG or LP.
  3. Do not change the number in the Config field.
  4. Use a 6 mm external hex wrench to rotate the center section of the fuel valve.
  5. Turn the center section clockwise until the detent is reached; do not rotate beyond this point.
  6. Keep selecting the Back button to save the settings and return to the Main screen.
Generator Config Screen Setup adjustment

⚠ Failure to configure will result in Fault Code 37.

  1. From the Main screen, select Menu.
  2. Press and hold the Next key on the Menu screen for at least 5 seconds to view the Config Menu.
  3. Highlight 'Config' and click the Enter key. The Generator Config screen appears.
  4. Use the Next key to navigate to the Config field. Use the arrow keys to select the appropriate config option (20 = C20N6H/C20N6HC, 21 = C17N6H, 22 = C13N6H).
  5. Use the Next key to navigate to the Fuel Type field. Select NG (natural gas; default) or LP (liquid propane).
  6. Keep selecting the Back button to save the settings and return to the Main screen.
Fuel Shutoff Solenoid Troubleshooting diagnostic

Tools: Multi-meter, Soapy water solution

  1. Disconnect the four harness leads from the fuel solenoid coils.
  2. Check that battery voltage is being supplied through the generator set harness using a multi-meter between FSOL1+/FSGND1 and FSOL2+/FSGND2 while trying to start.
  3. Verify that the voltage is 10.2 VDC. If no voltage, check for bad wiring; if less than 10.2 VDC, check for bad wiring or discharged battery.
  4. Check for proper solenoid operation by applying 12 VDC to a coil and listening/feeling for activation. Repeat for all solenoids.
  5. If either solenoid does not activate, replace the gas valve assembly.
  6. Check for fuel leaks at the solenoid with a soapy water solution on pipe threads and around the base; tighten or replace as required.
Line Circuit Breaker Troubleshooting diagnostic

⚠ Automated Machinery: accidental or remote starting can cause severe personal injury or death.

Tools: Ohmmeter

  1. Shut down and disable the generator set; disconnect the negative (–) battery cable and reconnect it last when done.
  2. Disconnect the leads going into and out of the circuit breaker (two leads from the alternator at the top L1 and L2, and two from customer wiring at the bottom L1 and L2).
  3. Check continuity: with the breaker on, very low resistance between the L1 lugs and between the L2 lugs.
  4. With the breaker off, the continuity check between L1 and L2 pairs should show open.
  5. Replace the breaker if either of the continuity tests fails.
Testing the Alternator diagnostic

⚠ Disconnect the AVR before doing any insulation resistance test. Discharge the windings by shorting to earth through an earthing rod for at least 5 minutes.

Tools: Ohmmeter, Megger or insulation resistance meter, Wheatstone bridge (0.001 Ohms precision)

  1. Test the rotor for grounded, open and shorted windings using an ohmmeter, testing at the brush block terminals first.
  2. For rotor ground resistance, set the ohmmeter to the highest scale or use a megger; touch one probe to the rotor shaft and the other to a slip ring.
  3. For rotor winding resistance, connect each meter test lead to a separate slip ring and compare to the resistance table.
  4. Test for a short between the main windings and the quad windings.
  5. For stator ground resistance, touch one test probe to the stack and, in turn, the other to each stator lead.
  6. Measure stator winding resistance with a meter having precision down to 0.001 Ohms.
  7. Measure each winding to the stator laminations to check for bad insulation.
Adding Oil maintenance

⚠ Ensure that the generator set engine has cooled down before adding or draining the oil.

  1. Ensure that the oil fill cap area is clean, and prevent debris from entering the engine.
  2. Add the appropriate amount of oil, based on the engine oil level check.
  3. Recheck the engine oil level. Based on the results, add or drain oil.
  4. Clean up and dispose of any oil in accordance with local/state regulations.
Brush Block/Slip Ring Service maintenance

⚠ Make sure the brushes are aligned correctly with the slip rings; otherwise they may break when the generator set is started.

Tools: Scotch Brite pad or commutator stone

  1. Disconnect the field leads from the brush block (F1, F2).
  2. Remove the two mounting screws.
  3. Withdraw the brush block from the alternator end bell.
  4. Inspect the brush block: if either brush is shorter than 11 mm (7/16 inch), binds, or is damaged, replace the brush block assembly.
  5. When installing the brush block, keep the brushes retracted with the wire through the hole; remove the wire after bolting the block in place.
  6. If the slip rings have grooves, pits, or other damage, use a Scotch Brite pad or commutator stone to remove light wear or corrosion.
Changing Engine Oil and Oil Filter maintenance

⚠ Contact with used engine oil can cause cancer or reproductive toxicity.

⚠ Accidental or remote starting can cause severe personal injury or death.

  1. Open the generator set's circuit breaker to prevent the ATS from transferring to generator set source when manually starting.
  2. Manually start the generator set and allow it to run 2 to 5 minutes to warm the engine oil.
  3. Remove the access panels to get to the drain hose.
  4. Stop the generator set and allow it to thoroughly cool. Disconnect the battery charger and the negative (–) battery cable.
  5. Open the oil drain cap to release oil from the engine into the appropriate container, close it, and wipe it clean.
  6. Place an appropriate container below the oil filter. Remove the oil filter by turning it counterclockwise and remove the old gasket.
  7. Clean the filter mounting surface on the engine block.
  8. Make sure the gasket is in place on the new filter and apply a thin film of clean oil to the gasket.
  9. Install the new filter until the gasket just touches the block. Turn it an additional 1/2 to 3/4 turn. Do not over-tighten.
  10. Add the appropriate amount of oil and check the engine oil level.
  11. Reconnect the battery cables, positive (+) cable first, and reconnect the battery charger.
  12. Operate the generator set with no load for approximately 5 minutes to check for leaks at the oil filter or oil drain hose.
  13. Shut down the generator set, wait 5 minutes, and confirm the correct oil level. Check for leaks and repair any identified.
  14. Dispose of the used oil and oil filter according to local environmental regulations.
  15. Re-install the access panels and restore the original generator set settings, then close the generator set breaker.
Checking Engine Oil Level maintenance

⚠ Do NOT check oil while the generator set is operating.

⚠ Overfilling can cause foaming or aeration of the oil.

  1. Make sure that the generator set has not been running for approximately five minutes.
  2. Clean off the area surrounding the dipstick port and prevent debris from entering the engine.
  3. Pull out the dipstick and wipe it clean.
  4. Reinsert and fully seat the dipstick.
  5. Remove the dipstick and check the oil level.
  6. Reinsert and fully seat the dipstick.
Draining Excessive Oil maintenance
  1. Remove the access panels to get to the drain hose.
  2. Place the end of the drain hose into an appropriate container.
  3. Open the oil drain cap to release oil from the engine into the appropriate container.
  4. Re-check the engine oil level. Based on the results, add or drain oil.
  5. When a sufficient amount of oil has been drained, close the oil drain cap and wipe it clean.
  6. Re-install the access panels. Torque the fasteners 3.5 - 5.0 ft-lb (5.0 - 6.6 Nm).
  7. Dispose of the used oil in accordance with local and state regulations.
Immobilize the Generator Set maintenance

⚠ Accidental or remote starting of the generator set can cause severe personal injury or death.

Tools: Insulated wrench, E-Stop button

  1. Press the Off switch from the display and then press the E-Stop button to shut down the engine.
  2. Thoroughly ventilate the generator set before disconnecting any leads.
  3. Turn off and disconnect the heater (where fitted) from the AC source before disconnecting the battery cables.
  4. Turn off and disconnect the battery charger (where fitted) from the AC source.
  5. Turn off the fuel supply to the engine.
  6. Disconnect the battery. Disconnect the negative (–) cable first, using an insulated wrench.
  7. Place warning notices at each location that state, 'Maintenance in Progress – Immobilized for Safe Working.'
Clock Setup operation
  1. From the Main screen, select Menu. Use the arrow keys to highlight Clock. Select the Enter key.
  2. Use the arrow keys to set the time and date. Select the Next key to go to the Daylight Savings screen.
  3. Use the arrow keys to enable/disable Daylight Savings. If enabling, select Next to highlight the Offset field.
  4. Use the arrow keys and Next key to set the offset value for Daylight Savings time.
  5. Select Next to set when Daylight Savings starts: set Month (1 – 12), Week (0 – 5), Day (Sun – Sat) and Hour (12AM – 12PM).
  6. Select Next to set when Daylight Savings ends using the same fields.
  7. Keep selecting the Back button to save the settings and return to the main screen.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
115/2301Split phaseAvailable on RS14AF model at 50 Hz
120/2401Split phaseAvailable on RS20A and RS20AC models at 60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the displacement of the Cummins/Onan QSJ999G?

The Cummins/Onan QSJ999G has a displacement of 1.0 liters with 2 cylinders.

Which generators use the Cummins/Onan QSJ999G engine?

The Cummins/Onan QSJ999G powers 7 generator set(s), including Cummins/Onan RS13A, Cummins/Onan RS13A C13N6H, Cummins/Onan RS17A, Cummins/Onan RS17A C17N6H, Cummins/Onan RS20A.