Cummins/Onan QSB5-G2 NR3 Engine
The Cummins/Onan QSB5-G2 NR3 is an engine rated at 1800 rpm. It powers generator sets from Terex, including the T90C.
Also known as: Cummins QSB5-G2 NR3
Common problems
14- Voltage does not come up to the rated voltage
Cause: Internal problem with the generator end
Fix: Check for even reading across the lines, if they are not this would mean you probably have a problem with the wiring of the switch or generator. If the generator voltage reads correctly, contact the TEREX service department. - Uneven reading between the legs when applying 24 volts to the field wires
Fix: Recheck your wiring connections. After you have the field wire connected start the unit again and check your output voltage. It may still be necessary to flash the fields to restore residual voltage. - TROUBLE LIGHT on CONTROL PANEL is illuminated
Cause: Broken fan belt
Fix: Inspect fan belt and replace as needed - No generator output voltage
Cause: Circuit breaker tripped
Fix: Reset circuit breaker - Malfunction discovered
Fix: Identify symptoms, troubleshoot, perform repair, return to service - Low generator output voltage
Cause: Voltage adjustment set too low
Fix: Adjust voltage potentiometer - Low engine speed
Fix: Call TEREX Service - High generator output voltage
Cause: Voltage adjustment potentiometer set too high
Fix: Adjust potentiometer - High engine speed
Fix: Call TEREX Service - Fluctuating or surging generator output voltage
Fix: Check engine fuel, oil, and air filters - Fluctuating generator output voltage stability
Cause: Load may be the cause
Fix: Redistribute load if possible - Engine won't crank
Cause: Loose battery cable
Fix: Check cables and battery electrolyte level. Recharge as necessary - Engine shuts down
Cause: Oil Pressure Switch not opening automatically and TROUBLE LIGHT on
Fix: Improper coolant use a 50/50 on - Engine runs, but loses power under load
Cause: Clogged fuel system
Fix: Check fuel system
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSB5-G2 NR3.
Common questions
Which generators use the Cummins/Onan QSB5-G2 NR3 engine?
The Cummins/Onan QSB5-G2 NR3 powers 1 generator set(s), including Terex T90C.
What is a common problem with the Cummins/Onan QSB5-G2 NR3 engine?
A commonly reported issue on generators using the Cummins/Onan QSB5-G2 NR3 is: Voltage does not come up to the rated voltage. Cause: Internal problem with the generator end. Fix: Check for even reading across the lines, if they are not this would mean you probably have a problem with the wiring of the switch or generator. If the generator voltage reads correctly, contact the TEREX service department..