Home›Engines›Cummins/Onan NTTA-855-G3

Cummins/Onan NTTA-855-G3 Engine

The Cummins/Onan NTTA-855-G3 is an engine. It powers generator sets from Cummins/Onan, including the DCBC, DCCB and DCDB. It holds 31 L (8.2 gal) of oil.

Also known as: Cummins NTTA-855-G3

Part of the Cummins/Onan NTTA855 engine family — 3 variants share parts & fitment.

31.0 L
Oil capacity

Engine specifications

Oil capacity31.0 L

Generator sets powered by this engine

3
Cummins/Onan DCBCCummins/Onan DCCBCummins/Onan DCDB

How to read your Cummins/Onan engine serial & model number →

Common problems

15
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run FAULT 1
    Cause: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is timed delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. FAULT 1 or FAULT 2
  • SWITCH OFF lamp flashes
    Cause: Indicates Run-Stop-Remote switch is in the Stop position which will prevent automatic starting
    Fix: Moving the Run-Stop-Remote switch to the Remote position will stop the lamp flashing and enable automatic starting.
  • PRE LO OIL PRES lamp lights. Engine continues to operate
    Cause: Indicates engine oil pressure has dropped to 20 psi (138 kPa)
    Fix: If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure. If engine can be stopped, follow procedure in step 5.
  • PRE HI ENGINE TEMP lamp lights. Engine continues to operate
    Cause: Indicates engine has begun to overheat and engine temperature has risen to approximately 205° F (97°C)
    Fix: If generator is powering non-critical and critical loads, and cannot be shut down, use the following: Reduce load if possible by turning off non-critical loads; Check air inlets and outlets and remove any obstructions to airflow; Open doors or windows in generator area to increase ventilation. If engine can be stopped, follow procedure in step 3.
  • OVERCRANK lamp lights and engine stops cranking. Or. Engine runs, shuts down, and LO OIL PRES lamp lights
    Cause: Indicates possible fuel system problem
    Fix: Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; Check for dirty fuel filter and replace if necessary (see MAINTENANCE section); Check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section); Refer to step 5; Reset the control and restart after correcting the problem. Contact your distributor for service if none of the above applies.
  • No AC output voltage
    Cause: Voltage regulator is inoperative
    Fix: Refer to Initial Start and Checks, and Adjustments sections of your Installation Manual for voltage check and adjustment procedures. Contact your distributor if voltage build-up is still a problem.
  • LO OIL PRES lamp lights. Engine shuts down
    Cause: Indicates engine oil pressure has dropped to 14 psi (97 kPa)
    Fix: Check oil level, replenish as necessary. Check oil lines and filters for leaks, repair as required. Reset control and restart. Contact your distributor if oil pressure is not in the range of 50 to 70 psi (345 to 483 kPa).
  • LO FUEL lamp lights. Engine shuts down and LO OIL PRES lamp lights
    Cause: Indicates engine has run out of fuel
    Fix: Check fuel level and replenish as required.
  • LO FUEL lamp lights. Engine continues to run
    Cause: Indicates diesel fuel supply is running low
    Fix: Check fuel supply and replenish as required.
  • LO ENG TEMP lamp lights. Set is in standby mode but is not operating. (Lamp lights when engine coolant temperature is 70° F (21° C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm if it remains lighted during initial generator set operation.)
    Cause: Indicates engine coolant heater is not operating or is not circulating coolant
    Fix: Check for the following conditions: Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required; Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required; Contact your distributor if none of the above applies.
  • HI ENG TEMP lamp lights. Engine shuts down
    Cause: Indicates engine has overheated (engine temperature has risen above 215° F/102° C) or coolant level is low (sets with coolant level sensor)
    Fix: Allow engine to cool down completely before proceeding with the following checks: Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary; Check for obstructions to cooling airflow and correct as necessary; Check for a slipping fan belt, tighten if loose; Reset control and restart after locating and correcting problem. Contact your distributor if none of the above applies.
  • Green RUN lamp lights following engine Start-up
    Fix: Indicates all engine systems are normal. No corrective action required.
  • Green RUN lamp does not light following engine start-up
    Cause: Indicates possible Start/Disconnect relay failure
    Fix: Contact your distributor for assistance.
  • Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits
    Cause: The monitor board or a sensor may be at fault
    Fix: Contact your distributor for service.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan NTTA-855-G3.

Parts cataloged across the Cummins/Onan NTTA855 family

4
Part #DescriptionCategory
903-0124NAService part / kit
903-0204NAService part / kit
903-0500NAService part / kit
903-0604NAService part / kit

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan NTTA-855-G3?

The Cummins/Onan NTTA-855-G3 engine has an oil capacity of 31.0 liters.

Which generators use the Cummins/Onan NTTA-855-G3 engine?

The Cummins/Onan NTTA-855-G3 powers 3 generator set(s), including Cummins/Onan DCBC, Cummins/Onan DCCB, Cummins/Onan DCDB.

What is a common problem with the Cummins/Onan NTTA-855-G3 engine?

A commonly reported issue on generators using the Cummins/Onan NTTA-855-G3 is: The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. Cause: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is timed delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay..