| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | all isolator bases within this elevation of each other |
| Clearance | Vibration isolator clearance between top plate and base | 0.25 | inch (6 mm) | nominal or greater |
| Clearance | Vibration isolator top plate to base clearance | 0.25 | inch (6 mm) | nominal, or greater |
| Gap | Angular alignment total indicator reading (T.I.R.) | 0.001 | inch per inch of radius | maximum |
| Other | Angular alignment maximum T.I.R. | .001 | inch per inch of radius | center of shaft to indicator axis |
| Other | Глубина фундамента/цоколя и выступ за пределы агрегата | не менее 150 | мм (6 дюймов) | |
| Other | Минимальное расстояние от генератора до стены, резервуара или панели в машинном зале | 1 | м | |
| Other | Нагрузка на грунт (ННГ) от агрегата, охладителя, топлива и фундамента | менее 9800 | кг/м2 (2000 фунтов на кв. фут) или 96 кПа | требует проверки по местным нормам |
| Other | Площадь впускного отверстия воздуха для агрегатов с радиаторным охлаждением | в 1,5-2 раза больше площади радиатора | | |
| Other | Просвет выхлопной трубы глушителя | 12 | дюйма (300 мм) | двигатель QSK60 |
| Other | Просвет выхлопной трубы глушителя | 3 | дюйма (76 мм) | двигатели B3.3, 4B, 6B |
| Other | Просвет выхлопной трубы глушителя | 4 | дюйма (100 мм) | двигатель 6C |
| Other | Просвет выхлопной трубы глушителя | 6 | дюйма (152 мм) | двигатели L, N, K19, V28 |
| Other | Просвет выхлопной трубы глушителя | 6×2 | дюйма (152 мм) | двигатели K38, QSK30 |
| Other | Просвет выхлопной трубы глушителя | 8 | дюйма (200 мм) | двигатели K50, QSK15 |
| Other | Прочность бетона фундамента на сжатие (28 суток) | не менее 17200 | кПа (2500 фунтов на кв. дюйм) | |
| Pressure | Idle oil pressure shutdown limit (PCC) | 12 | psi (83 kPa) | idle |
| Pressure | Idle oil pressure warning limit (PCC) | 15 | psi (104 kPa) | idle |
| Pressure | Low oil pressure shutdown (Detector) | 14 | psi (97 kPA) | |
| Pressure | Normal engine oil pressure (PCC) | 35-50 | psi (242-345 kPa) | |
| Pressure | Oil pressure shutdown limit (PCC) | 25 | psi (172 kPa) | |
| Pressure | Oil pressure warning limit (PCC) | 30 | psi (207 kPa) | |
| Pressure | Pre-low oil pressure alarm (Detector) | 20 | psi (137 kPA) | |
| Pressure | Предел обратного давления в выхлопной системе (большинство агрегатов Cummins) | 3 | дюйма рт. ст. (76 мм рт. ст.) | у последних моделей при максимальном потоке снижено до 2 дюймов рт. ст. (50 мм рт. ст.) |
| Resistance | Thermistor relay trip resistance | 3000 ±500 | ohms | thermistor chain resistance reaches |
| Resistance | Сопротивление электрода заземления при глухом занулении генераторной установки | не более 20 | Ом | рекомендуется, независимо от системы защиты |
| Speed | Generator frequency/RPM (nameplate rating) | 60 / 1800 | hz / RPM | or 50 hz / 1500 RPM |
| Speed | Idle speed adjustment range | 800 ±100 | RPM | default value 800 RPM; adjustable only in idle mode |
| Speed | Overspeed shutdown (Detector) | 1850 +50 | r/min | 50 hertz units |
| Speed | Overspeed shutdown (Detector) | 2100 ±90 | r/min | 60 hertz units |
| Speed | Overspeed shutdown (PCC) | 1800 | rpm | @ 50 Hz |
| Speed | Overspeed shutdown (PCC) | 2070 | rpm | @ 60 Hz |
| Speed | PCC frequency adjust range | ±5 | percent of nominal | |
| Temperature | Ambient temperature above which coolant heaters are recommended | 40 | °F (4°C) | |
| Temperature | Engine coolant temperature (heat exchanger cooling) | 165 to 195 | °F (74 to 91 °C) | adjust flow to maintain while viewing water temperature gauge |
| Temperature | Engine coolant temperature (heat exchanger systems) | 165 to 195 | °F (74 to 91°C) | while viewing water temperature gauge |
| Temperature | High coolant temperature shutdown (PCC) | 215 | °F | primary |
| Temperature | High coolant temperature shutdown (PCC) | 223 | °F | standby |
| Temperature | High coolant temperature warning (PCC) | 207 | °F | primary |
| Temperature | High coolant temperature warning (PCC) | 215 | °F | standby |
| Temperature | High engine temperature shutdown (Detector) | 222 | °F (106° C) | |
| Temperature | LOW COOLANT TEMP (Code 210) engine cold sensing threshold | 70 | °F (21 °C) | engine jacket water coolant temperature below |
| Temperature | Low coolant temperature warning sensing (PCC/Detector) | 70 | °F (21° C) | |
| Temperature | NFPA 110 minimum engine jacket water coolant temperature | 90 | °F (32 °C) | maintained by coolant heaters |
| Temperature | NFPA 110 minimum maintained engine coolant temperature | 90 | °F (32°C) | |
| Temperature | Pre-high engine temperature alarm (Detector) | 215 | °F (102° C) | |
| Temperature | Допустимое повышение температуры в машинном зале при полной нагрузке | 10-15 | °C (18-27 °F) | если температура в зале превышает 40 °C – подавать аспирационный воздух извне или снизить нагрузку |
| Temperature | Расчетная температура окружающей среды для размеров машинного зала | 40 | °C | |
| Temperature | Температура хладагента для облегчения пуска аварийного агрегата | выше 40 | °C | |
| Temperature | Температура эксплуатации батарей для оптимальной работы | 15-25 | °C | |
| Torque | AC distribution panel 100 A main breaker lugs | 50 | in-lbs | #4 to 2/0 conductors, AL or CU |
| Torque | AC distribution panel 100A main breaker terminals | 50 | in-lbs | listed for #4 to 2/0 conductors, AL or CU |
| Torque | AC distribution panel ground bar | 17 | ft-lbs | #1 to 2/0 conductors, AL or CU |
| Torque | AC distribution panel neutral bus | 21 | ft-lbs | #5 to 300 KCMIL conductors, AL or CU |
| Torque | Oil drain plug | 60-70 | ft-lb (81-95 N•m) | |
| Voltage | Megger test setting, 5001 thru 15000 VAC generator | 5000 | VDC | main stator minimum resistance 1000-200 meg; main rotor 1000-1000-5.0-1.0 meg |
| Voltage | Megger test setting, 600 VAC or less generator | 500 | VDC | main stator and main rotor minimum resistance 5.0-1.0 meg |
| Voltage | Megger test setting, 601 thru 5000 VAC generator | 2500 | VDC | main stator minimum resistance 400-50 meg; main rotor 5.0-1.0 meg |
| Voltage | PCC voltage adjust range | ±5 | percent of nominal | |