| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only); move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can be reset only at the PCC front panel. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Reduce load if possible; check air inlets and outlets and remove obstructions to airflow. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature has risen above the shutdown trip point: 215 F (102 C) - standby or 207 F (97 C) - primary). | Shutdown | Check for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps; reset control and restart. |
| 213 | COOLANT SENDER | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; replenish if low; look for leaks. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Allow engine to cool; check coolant level and leakage points; reset control and restart. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM; check PCC model setting; inspect and test MPU. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board; check battery cable connections; recharge or replace the battery. |
| 222 | OVERCRANK | Possible fuel system problem. | Shutdown | Check for empty fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filter; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed. (115% ±1% of nominal). | Shutdown | Check mechanical fuel linkage and governor module/digital board duty cycle. |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Lower battery charger float level if applicable; check engine DC alternator. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | See LOW DC VOLTAGE 230. |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Low fuel signal received. | Warning | Check fuel supply and replenish; check for short to ground in external wiring. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform the initial start setup procedure; if the set shuts down on the same EEPROM ERROR message, replace the digital board (A32). |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform the adjustment procedures; if the same message occurs, perform calibration procedures; if the message persists, replace the digital board (A32). |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify values/choices selected and repeat the save operation; if the same message occurs, replace the digital board (A32). |
| 260 | CUSTOMER FAULT 1 | When this customer defined input is closed to ground, the corresponding fault message is displayed. Programmable to initiate a shutdown or a warning. | Warning | Isolate source of false signal; repair external wiring or replace A34. |
| 261 | GROUND FAULT | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Isolate source of false signal; repair external wiring or replace A34. |
| 262 | RUPTURE BASIN | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Isolate source of false signal; repair external wiring or replace A34. |
| 263 | HIGH GEN TEMP | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Isolate source of false signal; repair external wiring or replace A34. |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Verify genset phase rotation matches bus; verify control wiring to bus PT module. |
| 272 | FIRST START | PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Verify Master First Start Sensor and interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds. | Shutdown | Set display to GEN, VOLTS, L-N; determine if the output voltage the control sees is low or high; isolate PCC/alternator/excitation circuit. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check PMG/field wiring, rotating rectifier, load and connectors. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Check fuel supply, intake air supply and load. |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 330 | OVERLOAD | Three-phase power output exceeds 105% of standby (or 115% of prime) rating. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Power is flowing into the generator set rather than out from the unit. | Shutdown | Verify CT connections, load sharing lines, and generator set frequency/voltage. |
| 337 | LOSS OF EXCITATION | Alternator excitation system is improperly adjusted or has failed. | Shutdown | Check output voltage calibration, load sharing lines, and leading power factor loads. |
| FAULT 1 | Fault 1 (Red) | Engine shut down because of a customer-connected system fault; part of a 10 second time delay shutdown circuit. | Shutdown | Service as required by the customer-supplied fault indicating switches. |
| FAULT 2 | Fault 2 (Red) | Engine shut down because of a customer-connected system fault; part of a non-time delay shutdown circuit. | Shutdown | Service as required by the customer-supplied fault indicating switches. |
| GF | Ground Fault Alarm (Optional) | Ground fault relay monitors neutral to ground connection and line to neutral, activating a fault alarm when the connection is broken or a ground fault is sensed. | Warning | Clear fault condition by pushing the Run/Stop (Reset)/Remote switch to Reset (auto reset link set at factory). |
| HET | High Engine Temperature (Red) | Engine shut down because of excessively high engine coolant temperature (greater than 230 deg F). | Shutdown | Check coolant level and leaks; service cooling system; reset engine control. |
| LET | Low Engine Temperature (Yellow) | Engine temperature is less than 70 deg F and the engine might not start. | Warning | Plug in, repair or install engine coolant and oil heaters. |
| LOP | Low Oil Pressure (Red) | Engine shut down because of excessively low engine oil pressure (less than 14 psi). | Shutdown | Check oil level and oil leaks; service lubricating system; reset engine control. |
| LOW FUEL | Low Fuel (Yellow) | Fuel level in the supply tank has dropped below the reserve necessary to run the set at full load for the prescribed number of hours. | Warning | Fill the main fuel supply tank with the appropriate grade of fuel. |
| OC | Overcrank (Red) | Engine shut down because it did not start during the timed cranking period (approximately 75 seconds, including two rest periods). | Shutdown | Service the set as necessary; reset engine control. |
| OS | Overspeed (Red) | Engine shut down because of overspeed. | Shutdown | Adjust the Electronic Overspeed Module; check governor for binding; reset engine control. |
| PRE-HET | Pre High Engine Temperature (Yellow) | Engine coolant temperature is abnormally high (greater than 220 deg F). | Warning | Shut down if possible or disconnect non-critical loads; service cooling system. |
| PRE-LOP | Pre Low Oil Pressure (Yellow) | Engine oil pressure is abnormally low (less than 20 psi). | Warning | Shut down if possible or disconnect non-critical loads; service lubricating system. |
| RUN | Run (Green) | Generator set is running and the starter has been disconnected. | Info | |
| SWITCH OFF | Switch-off (Flashing Red) | The Run/Stop/Remote switch is in the Stop position, preventing remote automatic operation. | Info | Push the Run-Stop-Remote switch to Remote. |