HomeEnginesCummins/Onan LRG-423

Cummins/Onan LRG-423 Engine

The Cummins/Onan LRG-423 is an engine. It powers generator sets from Cummins/Onan, including the GEAA and GEAB. It holds 4 L (1.1 gal) of oil and 11 L (2.9 gal) of coolant.

Also known as: Onan Modified Ford LRG-423

Part of the Cummins/Onan LRG-423 engine family — 2 variants share parts & fitment.

4.0 L
Oil capacity

Engine specifications

Oil capacity4.0 L
Coolant capacity11.0 L

Common problems

15
  • The OVERLOAD lamp lights. Engine shuts down.
    Cause: If load exceeds generator current rating, the breaker will trip preventing the generator from being overloaded.
    Fix: Locate the source of overload and correct as necessary. Manually reset breaker to reconnect the load to the generator.
  • The O/U VOLTAGE lamp lights. Engine shuts down.
    Fix: Contact an authorized service center for service.
  • SWITCH OFF lamp flashes.
    Fix: Indicates Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used. Move the Run/Stop/Remote switch to the Remote position for automatic starting.
  • Pre-Low Oil Pressure
    Fix: A pre-low oil pressure sensor and lamp provides an alarm that oil pressure is marginally low, 20 psi (137 kPA) or less. The cause should be found and corrected as soon as possible.
  • Pre-High Engine Temperature
    Fix: A pre-high engine temperature sensor and lamp provides an alarm that engine temperature is marginally high, 215° F (102° C). The cause should be found and corrected as soon as possible.
  • PRE HET/LOP lamp lights. Engine continues to operate.
    Cause: Indicates engine has begun to overheat and engine temperature has risen to approximately 205°F (97°C) or coolant level is low.
    Fix: A. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow.
  • OVERCRANK lamp lights and engine stops cranking.
    Cause: Indicates possible fuel system problem.
    Fix: A. Check for empty fuel tank (LPG Vapor), fuel leaks, or plugged fuel lines and correct as required. b. Check for dirty fuel filter and replace if necessary (see Maintenance section). c. Check for dirty or plugged air filter and replace if necessary (see Maintenance section). d. Reset the control and restart after correcting the problem. Contact an authorized service center for service if none of the above.
  • No AC output voltage.
    Fix: Field breaker is tripped. Reset breaker. Contact an authorized service center if voltage buildup causes breaker to trip.
  • Low Oil Pressure
    Fix: Shuts down the engine immediately if oil pressure drops below 14 psi (97 KPA) and lights a fault lamp. The fault is time-delayed about 10 seconds following starter disconnect and inhibited during cranking.
  • Low Coolant Level Shutdown
    Fix: An electronic switch that provides engine shutdown and turns on the high engine temperature fault lamp if coolant level fails too low.
  • LO OIL PRES lamp lights. Engine shuts down.
    Cause: Indicates engine oil pressure has dropped to 30 psi (207 kPa).
    Fix: NOTE: See also step 5.
  • LO FUEL (Pressure) lamp lights. Shutdown will occur if unit runs out of fuel. LO FUEL (Pressure)
    Fix: Install the fuel hose and regulator supplied with the unit and connect to a propane fu
  • Hl ENG TEMP lamp lights. Engine shuts down. Hl ENG TEMP
    Cause: Engine has overheated (engine temperature has risen above 215°F/102°C) or coolant level is low.
    Fix: A. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt and tighten if loose. d. Reset control and restart after locating and correcting problem. Contact an authorized service center if none of the above.
  • High Engine Temperature
    Fix: Shuts down the engine immediately if coolant temperature rises above 222° F (106° C) and lights a fault lamp. The fault is time-delayed about 10 seconds following starter disconnect and inhibited during cranking.
  • HI ENG TEMP lamp lights. Engine shuts down.
    Cause: Indicates engine has overheated (engine temperature has risen above 215°F/102°C) or coolant level is low.
    Fix: A. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt and tighten if loose. d. Reset control and restart after locating and correcting problem. Contact an authorized service center if none of the above.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan LRG-423.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterCheck Air Cleaner Xx X xX xX Check or Replace Spark Plugs X90 hr
Fuel filter
Oil filterChange Crankcase Oil and Filter X5200 hr
BatteryCheck battery voltage and charge system. Replace if necessary.90 hr
BeltInspect belts for wear and replace if necessary. Replace every 500 hours or as needed.500 hr
CoolantChange coolant at each oil change. Add or top off as needed.11.0 L90 hr
Coolant filter
OilChange Crankcase Oil and Filter X54.5 X1200 hr
Spark plugReplace spark plugs every 100 hours or as needed.100 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Parts cataloged across the Cummins/Onan LRG-423 family

5
Part #DescriptionCategory
FS-1176sCrankcase Oil and Filtergas_mixer
928-0129Oil Filteroil_filter
LS1169sFILTERoil_filter
928-0606other_service
D1400DONALDSONS D1400 SOLVENTother_service

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan LRG-423?

The Cummins/Onan LRG-423 engine has an oil capacity of 4.0 liters.

Which generators use the Cummins/Onan LRG-423 engine?

The Cummins/Onan LRG-423 powers 2 generator set(s), including Cummins/Onan GEAA, Cummins/Onan GEAB.

How often should you change the oil in the Cummins/Onan LRG-423?

The Cummins/Onan LRG-423 oil change interval is every 200 hours.

What is a common problem with the Cummins/Onan LRG-423 engine?

A commonly reported issue on generators using the Cummins/Onan LRG-423 is: The OVERLOAD lamp lights. Engine shuts down.. Cause: If load exceeds generator current rating, the breaker will trip preventing the generator from being overloaded.. Fix: Locate the source of overload and correct as necessary. Manually reset breaker to reconnect the load to the generator..