Home›Engines›Cummins/Onan L634T

Cummins/Onan L634T Engine

The Cummins/Onan L634T is a turbocharged engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the DL6T. It holds 10.8 L (2.9 gal) of oil and 20.6 L (5.4 gal) of coolant.

Also known as: Onan L634T

1800 rpm
Rated speed
10.8 L
Oil capacity

Engine specifications

Oil capacity10.8 L
Coolant capacity20.6 L
Aspirationturbocharged
Rated speed1800 rpm

Common problems

15
  • Engine will not crank
    Cause: Indicates possible fault with control or starting system; fault lamp on
    Fix: Correct fault and reset control
  • SWITCH OFF lamp flashes
    Cause: Indicates Start/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used
    Fix: Move the Start/Stop/Remote switch to the Remote position for automatic starting
  • PRELO OIL PRES lamp lights. Engine continues to operate
    Cause: Indicates engine oil pressure has dropped to 20 psi (138 kPa)
    Fix: If engine can be stopped, follow procedures in step 5; if generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure
  • PRE HI ENG TEMP lamp lights. Engine continues to operate
    Cause: Indicates engine has begun to overheat and engine temperature has risen to approximately 215°F (102°C)
    Fix: If engine can be stopped, follow procedures in step 3; if generator is powering critical loads and cannot be shutdown: check air inlets and outlets and remove any obstructions to airflow; open doors or windows in generator area to increase ventilation; reduce load if possible by turning off non-critical loads
  • OVERCRANK lamp lights and engine stops cranking after 45 to 75 seconds
    Cause: Indicates possible fuel system problem
    Fix: When the engine has cooled, make the following checks: check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; check for dirty fuel filter and replace if necessary (see MAINTENANCE section); check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section); reset the control and restart after correcting the problem; contact an Onan Dealer or Distributor for service if none of the above
  • No AC output voltage
    Cause: Field breaker is tripped
    Fix: Reset breaker; contact an Onan Dealer or Distributor if voltage build up causes breaker to trip
  • LO OIL PRES lamp lights. Engine shuts down
    Cause: Indicates engine oil pressure has dropped to 14 psi (97 kPa)
    Fix: Check oil level and replenish if low; reset control and restart; contact an Onan Dealer or Distributor if oil pressure is not in the range of 30 to 55 psi (207 to 380 kPa)
  • LO ENG TEMP lamp lights. Generator set is in Standby mode or was just started
    Cause: Indicates engine block temperature has dropped below 70°F (21°C)
    Fix: Lamp will go out when block temperature rises
  • HI ENG TEMP lamp lights. Engine shuts down
    Cause: Indicates engine has overheated (engine temperature has risen above 220°F/104°C) or coolant level is low (sets with coolant level sensor)
    Fix: Allow engine to cool down completely before proceeding with the following checks: check coolant level and replenish if low, look for possible coolant leakage points and repair if necessary; check for obstructions to cooling airflow and correct as necessary; check for a slipping fan belt and tighten if loose; reset control and restart after locating and correcting problem; contact an Onan Dealer or Distributor if none of the above
  • Green RUN lamp lights following engine start-up
    Cause: Indicates all engine systems are normal
    Fix: No corrective action required
  • Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits
    Cause: The monitor board or a sensor may be at fault
    Fix: Reset control; if control will not reset, contact an Onan Dealer or Distributor for service
  • Engine starts from generator control panel but won't start automatically or from a remote panel (Note: The Start/Stop/Remote switch must be in the Remote position for automatic or remote starting)
    Cause: Remote circuit breaker is tripped
    Fix: Reset breaker and restart; contact an Onan Dealer or Distributor if breaker trips after resetting
  • Engine runs and then shuts down. OVERSPEED lamp lights
    Cause: Indicates engine has exceeded normal operating speed
    Fix: Contact an Onan Dealer or Distributor for service
  • Engine does not start after second starting attempt
    Cause: No fuel delivery (absence of blue/white exhaust smoke during cranking indicates no fuel delivery)
    Fix: Check fuel supply
  • Engine does not start after 30 seconds of cranking
    Fix: Place the Start/Stop/Remote switch in the Stop position; wait two minutes and then repeat steps 1 and 2

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan L634T.

Service intervals

16
ItemActionHoursMonthsNotes
Coolant LevelCheck50 hr
Crankcase Oil and FilterChange200 hrFirst service — Perform after first 50 hours on new sets
Fan BeltCheck50 hr
Generator SetInspect50 hrWith engine running, visually/audibly check exhaust for leaks
Oil LevelCheck50 hr
Valve Lash ClearanceCheck400 hrFirst service — Perform after first 50 hours on new sets; refer to L-Series Engine Service Manual
Air CleanerCheck100 hrPerform more often under extremely dusty/dirty conditions
Exhaust Condensate TrapDrain100 hr
Fuel LevelCheck100 hr
Battery ConditionCheck200 hr
Electrolyte LevelCheck200 hr
Generator AssemblyClean200 hr
Air Cleaner ElementChange400 hr
Crankcase Breather Cap (DL6TB)Clean400 hr
Fuel FilterChange400 hr12 moWhichever comes first
Generator BearingInspect500 hrReplace every five years

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapOverspeed switch magnetic air gap0.005inch (0.13 mm)must not be less than
GapOverspeed switch magnetic air gap0.005 inch (0.13 mm) minimuminch
OtherBattery electrolyte specific gravity1.260specific gravityfully charged battery at 80F (27C)
OtherBattery electrolyte specific gravity (fully charged)about 1.260specific gravityat 80 deg F (27 deg C)
OtherControl breaker rating7amperes
OtherField breaker rating5amperes
OtherLow Oil Pressure Delay before shutdown/pre-alarm7.5 to 12.5secondsafter Start-Disconnect Relay energized
OtherLow oil pressure delay circuit7.5 to 12.5secondsafter start-disconnect relay energized
OtherMaximum allowable exhaust back pressure41inches (1041 mm) H2O
OtherOil pressure gauge range0 to 100 psi (0 to 700 kPa)psi
OtherOvercranking timer cranking limit45 to 75seconds
OtherOvercranking timer limit45 to 75seconds
OtherRemote breaker rating7amperes
OtherSwitching regulator (standard setting) nominal switching frequencyapproximately 125Hz
OtherWater temperature gauge range100 to 250F (40 to 121C)F
PressureAir cleaner cleaning air pressure35psi (241 kPa)
PressureAir cleaner rinse water pressure maximum40psi (276 kPa)
PressureLow oil pressure shutdown (LO OIL PRES)14psi (97 kPa)
PressureLow oil pressure switch closes14psi (97 kPa)
PressureLow oil pressure switch closes14 psi (97 kPa)psi
PressureOil pressure gauge normal range30 to 55psi (207 to 380 kPa)operating temperature
PressureOil pressure gauge range0 to 100psi (0 to 700 kPa)
PressurePre-low oil pressure switch closes20psi (138 kPa)
PressurePre-low oil pressure switch closes20 psi (138 kPa)psi
PressurePre-low oil pressure warning20psi (138 kPa)
ResistanceCommutating reactor L21 coils 1-20.031 to 0.37ohmsat 77 deg F (25 deg C)
ResistanceCommutating reactor L21 coils 3-40.037 to 0.46ohmsat 77 deg F (25 deg C)
ResistanceCommutating reactor L21/L22 coil 1-2 resistance.031 to 0.37ohmsat 77F (25C)
ResistanceCommutating reactor L21/L22 coil 3-4 resistance0.037 to 0.46ohmsat 77F (25C)
ResistanceCommutating reactor coil to frameinfinityohms
ResistanceExciter rotor leads T1-T2, T2-T3, T1-T3 resistance0.6 to 0.7ohmsat 68F (20C)
ResistanceExciter rotor winding between lead pairs T1-T2, T2-T3, T1-T30.6 to 0.7ohmsat 68 deg F (20 deg C)
ResistanceExciter stator / rotor / generator winding insulation to ground1 megohm (1,000,000 ohms) or greaterohmsminimum
ResistanceExciter stator field leads F1-F2 resistance13.05 to 15.95ohmsat 77F (25C)
ResistanceExciter stator winding between F1+ and F2-13.05 to 15.95ohmsat 77 deg F (25 deg C)
ResistanceGenerator rotor field leads F1-F2 resistance (60 Hz)2.9ohmsat 77F (25C)
ResistanceGenerator rotor field leads F1-F2 resistance (60 Hz)3.1ohmsat 77F (25C)
ResistanceReference transformer T21 primary coil resistance333-407ohms
ResistanceReference transformer T21 primary coil resistance350-427ohms
ResistanceReference transformer T21 primary coil resistance531-649ohms
ResistanceStator resistance Code 15R (60 Hz)33.5milliohmsTest between T1-LO, T2-LO, T3-LO at 77F (25C)
ResistanceStator resistance Code 15R (60 Hz)39.4milliohmsTest between T1-LO, T2-LO, T3-LO at 77F (25C)
ResistanceStator resistance Code 15R (60 Hz)9.8milliohmsTest between T1-LO, T2-LO, T3-LO at 77F (25C)
ResistanceStator resistance Code 515R (50 Hz)46.5milliohmsat 77F (25C)
ResistanceVoltage reference transformer T21 primary winding (H leads)350-427 / 333-407 / 303-371 / 282-344 / 531-649ohms
SpeedEngine rated speed (per flow charts)1800rpm
SpeedFrequency-to-speed conversion1hertz = 30 r/min
SpeedNominal switching frequency (switching regulator)125Hzapproximately
SpeedOverspeed switch contact closure2200 to 2250rpm
SpeedOverspeed switch contacts close3950 to 4050rpm
TemperatureHigh engine temperature shutdown220F (104 C)
TemperatureHigh engine temperature switch closes222deg F (106 deg C)
TemperatureHigh engine temperature switch closes222F (106C)F
TemperatureLow engine temperature switch closes70F (21C)Fcoolant drops below
TemperatureLow engine temperature switch closes below70deg F (21 deg C)
TemperatureLow engine temperature warning (LO ENG TEMP)70F (21 C)engine block temperature
TemperatureOil temperature gauge range150 to 300deg F (66 to 149 deg C)
TemperaturePre-high engine temperature switch closes216deg F (102 deg C)nominal
TemperaturePre-high engine temperature switch closes216F (102C)Fnominal
TemperaturePre-high engine temperature warning215F (102 C)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantEthylene glycol anti-freeze (permanent type) with rust/corrosion inhibitor, no stop-leak additiveUse at least 50/50 mixture of anti-freeze and clean, soft water
Engine oil15W-40, 30W, 20, 20W-20, 10W (API CD/SF, CD/SE, or MIL-L-2104C); synthetic 5W-20 or 5W-30 (MIL-L-46167, MIL-L-2104C, MIL-L-46152B)API CD/SF, CD/SE, MIL-L-2104CMineral base 5W-20/5W-30 not recommended under any conditions; select grade for lowest expected temperature
FuelASTM 2-D (No. 2 Diesel) or ASTM 1-D (No. 1 Diesel), Cetane 45 minimumASTM 2-D / ASTM 1-DUse No. 1 diesel below 0C (32F) and during long light-load periods; cloud point at least 10 degrees below lowest expected fuel temperature
GreaseMolyKote grease or equivalentApply thin film to mating surfaces of end bearing and end bell bearing hole
GreaseMolykote grease or equivalentApply a thin film to the mating surfaces of the end bearing and the end bell bearing hole.
OtherApproved water for battery electrolyteAdd approved water to keep battery electrolyte at proper level.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

8
CodeNameMeaningSeverityAction
HI ENG TEMPHigh Engine TemperatureEngine overheated above 220F (104C) or low coolantShutdownCheck coolant level, airflow, fan belt
LO ENG TEMPLow Engine TemperatureEngine block temperature below 70F (21C)InfoWait for block temperature to rise
LO OIL PRESLow Oil PressureOil pressure dropped to 14 psi (97 kPa)ShutdownCheck oil level, reset control
OVERCRANKOvercrankEngine failed to start after 45-75 seconds crankingShutdownCheck fuel system
OVERSPEEDOverspeedEngine exceeded normal operating speedShutdownContact Onan Dealer or Distributor
PRE HI ENG TEMPPre-High Engine TemperatureEngine temperature approximately 215F (102C)WarningCheck ventilation, reduce load
PRE LO OIL PRESPre-Low Oil PressureOil pressure dropped to 20 psi (138 kPa)WarningCheck oil level
SWITCH OFFSwitch OffStart/Stop/Remote switch in Stop positionInfoMove switch to Remote for automatic starting

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Changing Sensitivity Reference adjustment

⚠ Do not mark on printed circuit boards with a pencil; graphite lines are conductive.

Tools: soldering iron

  1. Unsolder W1 on VR21 at hole F for frequency sensitive.
  2. Resolder W1 to hole S for semi-frequency sensitive.
  3. Resolder W1 to hole N for non-frequency sensitive.
Fan Belt Adjustment adjustment

Tools: belt adjustment tool

  1. Loosen alternator bolt through elongated slot in mounting bracket
  2. Slide alternator until fan belt tension of 60 lbs (267 N) is obtained
  3. Tighten alternator mounting bolt to lock in place
  4. Check tension and repeat if necessary
Governor Control Adjustment adjustment

⚠ Hold the throttle linkage so that the set will not overspeed.

Tools: frequency meter

  1. Place Start/Stop/Remote switch in STOP.
  2. Attach frequency meter to generator output leads if none on panel.
  3. Locate governor control in control box.
  4. Adjust GAIN potentiometer fully counterclockwise.
  5. Hold throttle linkage to prevent overspeed; start the set.
  6. Adjust SPEED potentiometer to correct frequency (50 or 60 hertz).
  7. Adjust GAIN clockwise until governor hunts, then counterclockwise until stable.
  8. Test by tapping actuator lever; set should return to speed without hunting.
  9. Stop and restart set to verify it does not overspeed.
Magnetic Pickup Sensor Adjustment adjustment
  1. Place Start/Stop/Remote switch in the STOP position.
  2. Loosen stop-nut on the magnetic sensor on the flywheel housing.
  3. Turn sensor IN until it just contacts flywheel ring gear.
  4. Back sensor OUT 1/2 turn and tighten stop-nut.
Reconnection (Test Q) adjustment
  1. Refer to the generator reconnection possibilities when changing voltage.
  2. Reconnect lead W12 (inside control box) to the proper H terminal (H2, H3, H4, H5, or H6) depending on voltage selected.
  3. Change jumper W12 from TB2-2 to the proper TB2 terminal.
Voltage Adjustment (Standard Regulator) adjustment
  1. Center the panel mounted voltage adjustment knob with pointer vertical.
  2. Start the set and allow it to stabilize at correct frequency and speed.
  3. Turn R18 counterclockwise to decrease voltage or clockwise to increase.
  4. Set voltage with no load connected (e.g., 246 volts for 120/240).
  5. Turn R26 counterclockwise until unstable, then clockwise until voltage stabilizes.
Voltage Adjustment (Test P) adjustment

Tools: voltmeter

  1. Center the panel-mounted voltage adjustment knob vertically.
  2. Start the set and allow it to stabilize at the correct frequency and speed.
  3. Standard regulator: turn R18 counterclockwise to decrease voltage, clockwise to increase; set no-load voltage (e.g. 246 volts for 120/240 connection).
  4. Standard regulator: turn R26 counterclockwise until voltage hunts, then clockwise until stable.
  5. Switching regulator: turn R36 counterclockwise to increase voltage, clockwise to decrease; set no-load voltage.
  6. Switching regulator: turn R5 counterclockwise until voltage hunts, then clockwise until stable.
Alternator Checkout diagnostic

Tools: voltmeter

  1. With engine running, check battery charge rate DC ammeter.
  2. Ammeter should show slight charge tapering to zero as battery becomes charged.
  3. If constant discharge or high charge, stop set and check drive belt, terminals, leads.
  4. Measure alternator output voltage: positive lead to output terminal, negative to ground.
  5. Nominal output voltage should be 13.8 to 14.8 volts.
  6. If over 15 volts, check voltage regulator leads; replace regulator if shorted.
Alternator Checkout (C) diagnostic

Tools: DC ammeter, voltmeter

  1. With engine running, check the battery charge rate DC ammeter; it should show a slight charge tapering to zero.
  2. If constant discharge or constant high charge, stop set and check drive belt, terminal connections, and lead wires.
  3. Use a voltmeter between output terminal and ground; nominal output should be 13.8 to 14.8 volts.
  4. If output high (over 15 volts), check for loose or corroded voltage regulator leads; replace regulator if shorted.
  5. If output low, problem could be worn/broken brushes, open regulator, or open field diode.
Battery Cable Checkout (B) diagnostic

Tools: voltmeter

  1. With the starter motor operating, check voltage drop from battery negative post to cylinder block.
  2. Check voltage drop from battery positive post to battery terminal stud on the solenoid.
  3. Normally each should be less than 0.3 volt.
  4. Clean all connections in any part of the circuit showing excessive voltage drop.
Fuel Solenoid Checkout diagnostic
  1. Listen for a click in the injection pump when start switch is placed in run position.
  2. If no click is heard and there is power to solenoid, replace the fuel solenoid.
Fuel Solenoid Checkout (F) diagnostic
  1. To check energized-to-run operation, listen for a click in injection pump when start switch is placed in run position.
  2. If no click and there is power to solenoid, the fuel solenoid must be replaced.
  3. To check energized-to-stop operation, listen for a click when switch is placed in stop position.
  4. If no click and there is no power to solenoid, the fuel solenoid must be replaced.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Connect loose wire W12 from TB2-2 to TB2 (H terminal)H2, H3, H4, H5 or H6 depending on voltage selectedW12 reconnection lead inside control box; must be reconnected to proper H terminal when reconnecting for a different voltage
X1 (red) to VR21-9, X2 (red) to VR21-10X1, X2Reference transformer T21 secondary connections
110/1903Figure 26 generator voltage connections
110/2201Connect lead W12 to H6 (per Figure 26 reconnection table)50 Hz. Figure 26 generator voltage connections. OCR partially garbled.
115/2003Figure 26 generator voltage connections
115/2301Connect lead W12 to H6 (per Figure 26 reconnection table)50 Hz. Figure 26 generator voltage connections. OCR partially garbled.
120/2083Figure 26 generator voltage connections
120/2401Connect lead W12 to H5 (per Figure 26 reconnection table)60 Hz. Figure 26 generator voltage connections. OCR partially garbled.
120/2401Reconnectible generator (code 15/515)W12 (TB2) to H3/H4/H5/H6 on voltage reference transformer12-lead generator reconnection
127/2203Figure 26 generator voltage connections
130/4003Figure 26 generator voltage connections
139/2403Figure 26 generator voltage connections
220/3803Figure 26 generator voltage connections
220/3803Non-reconnectible (code 7)H3
240/4163Figure 26 generator voltage connections
254/4403Figure 26 generator voltage connections
277/4803Figure 26 generator voltage connections
347/6003Non-reconnectible (code 9X)H5
VariousReconnect lead W12 (inside control box) from TB2-2 to the proper H terminal (H2, H3, H4, H5, or H6) depending on voltage selectedW12, H2, H3, H4, H5, H6Figure 25. Single phase generators use leads 1 and 4 (lead 2 not used); three phase generators use leads 4, 7, 8, 9 and 10 for control input and metering.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Cummins/Onan L634T?

The Cummins/Onan L634T engine has an oil capacity of 10.8 liters.

Which generators use the Cummins/Onan L634T engine?

The Cummins/Onan L634T powers 1 generator set(s), including Cummins/Onan DL6T.

What is a common problem with the Cummins/Onan L634T engine?

A commonly reported issue on generators using the Cummins/Onan L634T is: Engine will not crank. Cause: Indicates possible fault with control or starting system; fault lamp on. Fix: Correct fault and reset control.