| Gap | Overspeed switch magnetic air gap | 0.005 | inch (0.13 mm) | must not be less than |
| Other | Battery electrolyte specific gravity (fully charged) | about 1.260 | specific gravity | at 80 deg F (27 deg C) |
| Other | Control breaker rating | 7 | amperes | |
| Other | Field breaker rating | 5 | amperes | |
| Other | Low oil pressure delay circuit | 7.5 to 12.5 | seconds | after start-disconnect relay energized |
| Other | Maximum allowable exhaust back pressure | 41 | inches (1041 mm) H2O | |
| Other | Overcranking timer limit | 45 to 75 | seconds | |
| Other | Remote breaker rating | 7 | amperes | |
| Other | Switching regulator (standard setting) nominal switching frequency | approximately 125 | Hz | |
| Pressure | Air cleaner cleaning air pressure | 35 | psi (241 kPa) | |
| Pressure | Air cleaner rinse water pressure maximum | 40 | psi (276 kPa) | |
| Pressure | Low oil pressure shutdown (LO OIL PRES) | 14 | psi (97 kPa) | |
| Pressure | Low oil pressure switch closes | 14 | psi (97 kPa) | |
| Pressure | Oil pressure gauge normal range | 30 to 55 | psi (207 to 380 kPa) | operating temperature |
| Pressure | Oil pressure gauge range | 0 to 100 | psi (0 to 700 kPa) | |
| Pressure | Pre-low oil pressure switch closes | 20 | psi (138 kPa) | |
| Pressure | Pre-low oil pressure warning | 20 | psi (138 kPa) | |
| Resistance | Commutating reactor L21 coils 1-2 | 0.031 to 0.37 | ohms | at 77 deg F (25 deg C) |
| Resistance | Commutating reactor L21 coils 3-4 | 0.037 to 0.46 | ohms | at 77 deg F (25 deg C) |
| Resistance | Commutating reactor coil to frame | infinity | ohms | |
| Resistance | Exciter rotor winding between lead pairs T1-T2, T2-T3, T1-T3 | 0.6 to 0.7 | ohms | at 68 deg F (20 deg C) |
| Resistance | Exciter stator / rotor / generator winding insulation to ground | 1 megohm (1,000,000 ohms) or greater | ohms | minimum |
| Resistance | Exciter stator winding between F1+ and F2- | 13.05 to 15.95 | ohms | at 77 deg F (25 deg C) |
| Resistance | Voltage reference transformer T21 primary winding (H leads) | 350-427 / 333-407 / 303-371 / 282-344 / 531-649 | ohms | |
| Speed | Engine rated speed (per flow charts) | 1800 | rpm | |
| Speed | Frequency-to-speed conversion | 1 | hertz = 30 r/min | |
| Speed | Overspeed switch contact closure | 2200 to 2250 | rpm | |
| Temperature | High engine temperature shutdown | 220 | F (104 C) | |
| Temperature | High engine temperature switch closes | 222 | deg F (106 deg C) | |
| Temperature | Low engine temperature switch closes below | 70 | deg F (21 deg C) | |
| Temperature | Low engine temperature warning (LO ENG TEMP) | 70 | F (21 C) | engine block temperature |
| Temperature | Oil temperature gauge range | 150 to 300 | deg F (66 to 149 deg C) | |
| Temperature | Pre-high engine temperature switch closes | 216 | deg F (102 deg C) | nominal |
| Temperature | Pre-high engine temperature warning | 215 | F (102 C) | |
| Temperature | Water temperature gauge normal range | 165 to 195 | F (74 to 91 C) | depending on load and ambient |
| Temperature | Water temperature gauge range | 100 to 250 | deg F (40 to 121 deg C) | |
| Torque | Capscrews holding drive disc to engine flywheel (8) | 39 | ft. lbs. (52 Nm) | |
| Torque | Drive disc placement bolts (8) | 70 to 80 | ft. lbs. (95 to 108 Nm) | |
| Torque | End bell stud nuts | 20 | ft. lbs. (27 Nm) | |
| Torque | Exciter rotor lock nut | 130 to 150 | ft. lbs. (176 to 203 Nm) | |
| Torque | Fan belt tension | 60 | lbs (267 N) | |
| Torque | Fuel injection line connecting nut torque | 18 | ft-lbs (24 N-m) | |
| Torque | Generator field leads F1+ and F2- terminals on exciter assembly | 23 to 26 | inch lbs. (2.6 to 2.9 Nm) | |
| Torque | Rotating rectifier nuts F1+, F2-, CR1, CR2, CR3, CR4, CR5, CR6 | 24 | lbs-in. (2.7 Nm) | |
| Torque | Stator attachment ring capscrews (12) on DL4 and DL6 | 39 | ft. lbs. (52 Nm) | |
| Voltage | Battery cable voltage drop (negative post to block; positive post to solenoid stud) | less than 0.3 | volt | |
| Voltage | Battery charge rate DC ammeter range | +/- 30 | amperes | |
| Voltage | Battery charging alternator output voltage | 13.8 to 14.8 | volts | engine running, stabilized |
| Voltage | Charge battery if specific gravity below | 1.215 | | |
| Voltage | Exciter field voltage across TB1-5 and 6 (or TB1-11) | 5 | VDC | or more |
| Voltage | Maximum charge rate for set-mounted battery charging alternator | 35 | amperes | |
| Voltage | Residual AC voltage across TB2-2 and H1 | 5 to 10 | VAC | |
| Voltage | Solenoid contact voltage drop across contacts | 1 | volt | maximum |
| Voltage | Specific gravity, fully charged battery | 1.260 | | 80F (27C) |
| Voltage | Standard regulator calibration (set V1 to 208 VAC) | 90-110 | VDC | V2 output |
| Voltage | Standard regulator range test A (V1=203 VAC) | > 180 | VDC | |
| Voltage | Standard regulator range test A (V1=211 VAC) | < 60 | VDC | |
| Voltage | Standard regulator range test B (V1=205 VAC) | > 140 | VDC | |
| Voltage | Standard regulator range test B (V1=213 VAC) | < 10 | VDC | |
| Voltage | Voltage at K1 start solenoid terminal S (S10 in Start) | at least 7 | VDC | |