| 101 | IDLE MODE | Engine operating in idle mode | Info | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop activated | Shutdown | Pull button out or turn clockwise to pop out; move Run/Off/Auto switch to Off; press Reset; select Run or Auto. Reset only at PCC front panel. |
| 200 | LOW OIL PRESSURE | Engine oil pressure dropped to an unacceptable level | Warning | Follow 201 Low Oil Pressure procedure. |
| 201 | LOW OIL PRESSURE | Engine oil pressure below shutdown trip point | Shutdown | Check oil level, replenish if low, reset control and restart; contact authorized service center. |
| 204 | OIL PRES SENDER | Engine oil pressure sender not functioning correctly | Warning | Check sender connection; contact authorized service center. |
| 210 | LOW COOLANT TEMP | Engine coolant temperature 70 F (21 C) or lower | Warning | Check coolant heater power, fuse and cord; check coolant level and leaks. |
| 211 | HIGH COOLANT TEMP | Engine operating near cooling system capacity | Warning | Review 212 correction list; increase in load or higher ambient may cause shutdown. |
| 212 | HIGH COOLANT TEMP | Engine overheated; coolant above shutdown trip point | Shutdown | Cool engine; check coolant level, airflow obstructions and fan belt; reset and restart. |
| 213 | COOLANT SENDER | Resistance of coolant temperature sender out of range | Warning | Contact authorized service center. |
| 214 | LOW COOLANT LVL | Engine coolant level below trip point | Warning | Cool engine; check coolant level and leaks; reset control and restart. |
| 215 | LOW COOLANT LVL | Engine coolant level below trip point | Shutdown | Cool engine; check coolant level and leaks; reset control and restart. Shutdown will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication not sensed or does not match output frequency | Shutdown | Restart and check RPM on digital display; contact authorized service center. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system | Shutdown | Clean and tighten battery cables; recharge or replace battery; contact service center. |
| 222 | OVERCRANK | Possible fuel system problem | Shutdown | Check fuel tank, leaks, plugged lines, fuel filter and air filter; reset control and restart. |
| 223 | OVERSPEED | Engine exceeded normal operating speed (2070 rpm @ 60 Hz; 1800 rpm @ 50 Hz) | Shutdown | Contact authorized service center. |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Battery voltage below 24 VDC | Warning | Check battery charger fuse; recharge or replace battery; clean and tighten cable terminals. |
| 231 | HIGH DC VOLTAGE | Battery voltage exceeds 32 VDC | Warning | Contact authorized service center. |
| 232 | WEAK BATTERY | Battery voltage drops below 60% of nominal for two seconds during starting | Warning | See warning message 230 LOW DC VOLTAGE. |
| 240 | LOW FUEL - DAY | Day tank fuel supply running low | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Fuel supply running low | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters | Shutdown | Contact authorized service center. |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters | Warning | Contact authorized service center. |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters | Warning | Contact authorized service center. |
| 260 | CUSTOMER FAULT 1 | Customer defined input closed to ground | | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 261 | GROUND FAULT | Customer defined input closed to ground | | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 262 | RUPTURE BASIN | Customer defined input closed to ground | | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 263 | HIGH GEN TEMP | Customer defined input closed to ground | | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Verify genset phase rotation matches bus; verify control wiring to bus PT module. |
| 272 | FIRST START | PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Verify Master First Start Sensor and interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or 110% of nominal for 10 seconds | Shutdown | Contact authorized service center. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds | Shutdown | Contact authorized service center. |
| 313 | UNDER FREQUENCY | Engine speed dropped below 90% of nominal for 10 seconds | Shutdown | Load Dump signal initiated five seconds before shutdown; contact authorized service center. |
| 320 | OVERCURRENT | Generator output current exceeded 110% of rated for 60 seconds | Warning | Contact authorized service center. |
| 321 | OVERCURRENT | Generator output current exceeded 110% of rated; PCC time/current calculation initiated shutdown | Shutdown | Contact authorized service center. |
| 322 | SHORT CIRCUIT | Generator output current exceeded 175% of rated | Shutdown | Contact authorized service center. |
| 330 | OVERLOAD | Three-phase power output exceeds 105% of standby (or 115% of prime) rating | Warning | Load Dump output activated after five seconds; warning activated after 60 seconds; contact authorized service center. |
| 335 | REVERSE POWER | Improper CT or PT phasing (non-parallel units only) | Shutdown | Contact authorized service center. |
| 337 | LOSS OF EXCITATION | Alternator excitation system is improperly adjusted or has failed. | Shutdown | Check output voltage calibration, load sharing lines, and leading power factor loads. |
| FAULT 1 | Fault 1 (Red) | Engine shut down because of a customer-connected system fault; part of a 10 second time delay shutdown circuit. | Shutdown | Service as required by the customer-supplied fault indicating switches. |
| FAULT 2 | Fault 2 (Red) | Engine shut down because of a customer-connected system fault; part of a non-time delay shutdown circuit. | Shutdown | Service as required by the customer-supplied fault indicating switches. |
| GF | Ground Fault Alarm (Optional) | Ground fault relay monitors neutral to ground connection and line to neutral, activating a fault alarm when the connection is broken or a ground fault is sensed. | Warning | Clear fault condition by pushing the Run/Stop (Reset)/Remote switch to Reset (auto reset link set at factory). |
| HET | High Engine Temperature (Red) | Engine shut down because of excessively high engine coolant temperature (greater than 230 deg F). | Shutdown | Check coolant level and leaks; service cooling system; reset engine control. |
| HI ENG TEMP | High Engine Temperature | Engine shut down due to critically high coolant temperature (above 215F/102C). | Shutdown | |
| High Engine Temperature | High Engine Temperature | On a five-light system, the High Engine Temperature switch connects to module A13-20; closure applies a ground which turns on A13-Q6 triggering A13-CR7 to conduct, providing a ground path for the fault light and to relay A11-K2 for engine shutdown. On single-light systems it is connected in parallel with low oil pressure to pin 4 of A12 | Shutdown | Check coolant level, radiator cooling duct, fan belts, temperature sensor, thermostat and city water input solenoid valve |
| LET | Low Engine Temperature (Yellow) | Engine temperature is less than 70 deg F and the engine might not start. | Warning | Plug in, repair or install engine coolant and oil heaters. |
| LO FUEL | Low Fuel | Fuel supply is marginally low, if equipped (Detector-12). | Warning | |
| LO OIL PRES | Low Oil Pressure | Engine shut down due to critically low oil pressure (below 14 psi/97 kPa). | Shutdown | |
| LOP | Low Oil Pressure (Red) | Engine shut down because of excessively low engine oil pressure (less than 14 psi). | Shutdown | Check oil level and oil leaks; service lubricating system; reset engine control. |
| LOW ENG TEMP | Low Engine Temperature | Engine water jacket temperature is 70F/21C or lower; indicates possible inoperative coolant heater (Detector-12). | Warning | |
| Low Engine Temperature | Low Engine Temperature | Closure of the Low Engine Temperature Sensing switch applies a ground to A13-8; A13-Q4 conducts and set-panel and remote Low Engine Temperature lights indicate a fault; there is no alarm or engine shutdown with this fault | Warning | Indicates a fault only; no shutdown or alarm |
| LOW FUEL | Low Fuel (Yellow) | Fuel level in the supply tank has dropped below the reserve necessary to run the set at full load for the prescribed number of hours. | Warning | Fill the main fuel supply tank with the appropriate grade of fuel. |
| Low Oil Pressure | Low Oil Pressure | Closure of the low oil pressure switch applies a ground to pin 4 of the A12 module; A12-Q4 turns on causing unijunction A12-Q7 to fire and trigger A12-CR6; fault light illuminates and on standard installations alarm and engine shutdown are initiated (Penn State sets alarm only). An adjustable rheostat A12-R11 provides a timed-delay up to 10 seconds | Shutdown | Check oil level and oil pressure sensor; disconnect wire from TB11-30 and check if light remains on |
| OC | Overcrank (Red) | Engine shut down because it did not start during the timed cranking period (approximately 75 seconds, including two rest periods). | Shutdown | Service the set as necessary; reset engine control. |
| OS | Overspeed (Red) | Engine shut down because of overspeed. | Shutdown | Adjust the Electronic Overspeed Module; check governor for binding; reset engine control. |
| OVERCRANK | Overcrank | Starter locked out because of excessive cranking time (limited to 75 seconds). | Shutdown | |
| Overcrank | Overcrank | Engine fails to start after cranking for 75 seconds; capacitor A12-C1 on the Engine Monitor module charges to turn on A12-CR1, illuminates the fault light and applies a ground to pin 7 on A11 Engine Shutdown module which energizes A12-K1 allowing K12 to drop out and stop cranking | Shutdown | Check fuel system (valves open, tanks full) and ignition system; refer to engine manufacturer's troubleshooting |
| OVERSPEED | Overspeed | Engine shut down because of excessive speed. | Shutdown | |
| Overspeed | Overspeed | Engine speed in excess of 2010 rpm causes transistor A16-Q2 on the Overspeed Sensor module to conduct and apply a ground to pin 2 of A12 Engine Monitor module; A12-Q8 turns on and triggers A12-CR8 to illuminate the fault light and initiate shutdown and alarm | Shutdown | Check throttles for freedom of movement and governor linkage; check injector rack movement; verify governor setting |
| PRE HI ENG TEMP | Pre-High Engine Temperature | Coolant temperature is marginally high (205F/97C or higher). | Warning | Attend to when generator set is shut down. |
| PRE LO OIL PRES | Pre-Low Oil Pressure | Engine oil pressure is marginally low (20 psi/138 kPa or less). | Warning | Attend to when generator set is shut down. |
| PRE-HET | Pre High Engine Temperature (Yellow) | Engine coolant temperature is abnormally high (greater than 220 deg F). | Warning | Shut down if possible or disconnect non-critical loads; service cooling system. |
| PRE-LOP | Pre Low Oil Pressure (Yellow) | Engine oil pressure is abnormally low (less than 20 psi). | Warning | Shut down if possible or disconnect non-critical loads; service lubricating system. |
| RUN | Run | Green lamp comes on when both primary and secondary starter circuits open after unit starts. | Info | |
| SWITCH OFF | Switch-off (Flashing Red) | The Run/Stop/Remote switch is in the Stop position, preventing remote automatic operation. | Info | Push the Run-Stop-Remote switch to Remote. |