Home›Engines›Cummins/Onan KTTA50-G2

Cummins/Onan KTTA50-G2 Engine

The Cummins/Onan KTTA50-G2 is a 50.3 L 16-cylinder turbocharged and aftercooled engine rated at 1800 rpm, producing up to 1656.1 kW. It powers generator sets from Cummins/Onan, including the DFM. It holds 151.4 L (40.0 gal) of oil.

Also known as: Cummins KTTA50-G2

Part of the Cummins/Onan KTTA50 engine family — 3 variants share parts & fitment.

50.3 L
Displacement
16
Cylinders
1800 rpm
Rated speed
1656 kW
Gross power

Engine specifications

Oil capacity151.4 L
Displacement50.3 L
Cylinders16
Aspirationturbocharged and aftercooled
Rated speed1800 rpm
Gross power1656 kW

Common problems

15
  • LO OIL PRES lamp lights
    Cause: Low coolant level
    Fix: Check for low coolant level and replenish if required; look for possible coolant leakage points and repair as required
  • EEPROM ERROR — Warning 251
    Cause: Indicates PCC memory error. Data corruption of noncritical operating parameters.
    Fix: Contact an authorized service center.
  • WEAK BATTERY — Warning 232
    Cause: Indicates battery voltage drops below 60% of nominal for two seconds, during starting. Discharged or defective battery.
    Fix: See Warning message 230, LOW DC VOLTAGE.
  • Warning, Shutdown, and Non-Automatic lamps are not lit. Digital display shows main menu or selected menu.
    Cause: Indicates all engine systems are normal.
    Fix: No corrective action required.
  • UNDER FREQUENCY — Shutdown 313
    Cause: Indicates that engine speed has dropped below 90% of nominal for 10 seconds. NOTE: Five seconds before shutdown, a Load Dump signal is initiated.
    Fix: Contact an authorized service center.
  • The FAULT 1 or FAULT 2 fault lamp lights; engine shuts down immediately
    Cause: The standard undesignated fault functions are programmed to shut down the set when engine runs fo
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, or engine continues to run. FAULT 1 or FAULT 2
    Fix: A. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Discharged or defective battery. Recharge or replace the battery.
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.
    Cause: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
  • The BASIN (optional) fault lamp lights. Engine continues to run or is in standby mode. (Engine can be programmed to shut down.)
    Cause: Indicates fuel is leaking from inner tank to outer basin or the sensor may be defective.
    Fix: Contact an authorized service center for service.
  • SWITCH OFF lamp flashes.
    Cause: Indicates Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used.
    Fix: Move the Run/Stop/Remote switch to the Remote position for automatic starting.
  • SHORT CIRCUIT — Shutdown 322
    Cause: Indicates that generator output current has exceeded 175% of rated.
    Fix: Contact an authorized service center.
  • RUPTURE BASIN — Warning 262
    Cause: When any one of these customer defined inputs is closed to ground, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. These fault functions can be programmed to initiate a shutdown or a warning. As indicated by the Warning lamp, a warning response has been preselected.
    Fix: Note: Customer fault messages are editable. The message displayed for the code shown (260 thru 263) may have been edited and may not appear as shown in this table.
  • RUPTURE BASIN — Shutdown 262
    Cause: When any one of these customer defined inputs is closed to ground, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. These fault functions can be programmed to initiate a shutdown or a warning. As indicated by the Shutdown lamp, a shutdown response has been preselected.
    Fix: Contact an authorized service center. Note: Customer fault messages are editable. The message displayed for the code shown (260 thru 263) may have been edited and may not appear as shown in this table.
  • RUN or fault lamp(s) does not light when Lamp Test switch is engaged.
    Fix: Contact an authorized service center for assistance.
  • REVERSE POWER — Shutdown 335
    Cause: Indicates improper CT or PT phasing. (Non-parallel units only.)
    Fix: Contact an authorized service center.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan KTTA50-G2.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterMaximum Air Cleaner Restriction, 25.0 in. H2O (6.2 kPa)—
Fuel filter—
Oil filterFive spin-on, full flow—
Battery—200 hr
Belt—
Coolant386.1 L—500 hr
OilCummins151.4 L—250 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

4
ItemActionHoursMonthsNotes
crankcase oilChange50 hrFirst service — Drain and replace the crankcase oil after the first 50 hours of operation on new generator sets (break-in)
Crankcase oil and filterChange250 hr12 moStandby applications: change oil every 12 months or 250 hours, whichever comes first
Generator bearing (P7 only)Lubricate4500 hrRe-lubrication period 4000-4500 hours; 75 grams Kluber ASONIC GHY72
Rupture basin leak detect switchTest12 moCheck once a year; in some areas weekly inspections may be required by safety code regulations

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceAir cleaner nozzle distance from elementat least 1 (25)inch (mm)
ClearanceAngular alignment T.I.R. limitnot more than .001in per inch of radiuscenter of shaft to indicator axis
ClearanceAngular alignment maximum T.I.R.0.001inch per inch of radius (center of shaft to indicator axis)measuring deflection to bolt heads
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
GapMPU sensor to flywheel ring gear toothback it out one quarter turnturnsensor threaded in until it just touches gear tooth
GapMagnetic sensor air gap.050- to .060-inch (1.27 to 1.52 mm)inch (mm)
OtherAVR Droop setting5% at full load, 0 PF
OtherAVR voltage regulation (load regulation)approximately ±0.5% RMS
OtherAir cleaner element cleaning air pressure30 (207)psi (kPa)low pressure compressed air through element from clean side
OtherAngular alignment maximum T.I.R..001 inches per inch of radiusin/incenter of shaft to indicator axis
OtherBattery electrolyte specific gravity1.260at 80°F
OtherBattery specific gravity (high ambient, above 95F/35C)1.225recommended to reduce electrolyte loss
OtherBattery specific gravity (recharge threshold)below 1.260
OtherBattery specific gravity, fully chargedapproximately 1.260specific gravityat 80 F (27 C)
OtherContinuous crank without cycle cranking option (PCC)up to 75seconds
OtherCycle Cranker crank cycle time (A14-R4)13- to 17-seconds
OtherCycle Cranker rest time (A14-R6)8- to 12-seconds
OtherFuel lift height limit6feet(1.8 meters) between fuel lift pump and bottom of dip tube
OtherGOV GAIN default value for paralleling applications70%
OtherLow oil pressure / high engine temperature fault time delay after starter disconnectabout 10seconds
OtherMaximum cranking voltage drop2voltsdifference between battery and starter terminals while cranking
OtherOutput frequency adjustment range+/- 5%set running, not in idle mode
OtherOver/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal55Hzreset 53 Hz
OtherOver/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal65Hzreset 63 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal45Hzreset 47 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal55Hzreset 57 Hz
OtherOver/Under Voltage Sensor Module time delaytypically 25 percent, approximately 2.5seconds
OtherOvercrank cranking limit75secondsthree 15-second cranking cycles with two 15-second rest periods
OtherOvercrank cranking limit (standard control)75seconds
OtherOvercrank cycle cranking (Detector, standard)three 15-second cranking cycles with two 15-second rest periodsseconds
OtherOvercrank cycle cranking (PCC)3, 4, or 5 cycles; crank and rest times 7 to 20seconds
OtherOvercrank cycling optionthree 15-second cranking cycles with two 15-second rest periods12-lamp control
OtherOvercrank limit (Detector, optional)75seconds
OtherOvercurrent shutdown threshold110% of rated% of ratedPCC time/current calculation
OtherOvercurrent warning threshold110% of rated for 60 seconds% of ratedgenerator output current
OtherOverload warning threshold105% of standby or 115% of prime% of ratingthree-phase power output; load dump after five seconds, warning after 60 seconds
OtherREG VHZ (underfrequency roll-off) adjustable range1 through 50; normal range 7 through 21
OtherShort circuit shutdown threshold175% of rated% of ratedgenerator output current
OtherStart delay (PCC, remote start in Auto)0 to 300seconds
OtherStart delay adjustment range0 to 300seconds
OtherStop delay (PCC, remote stop in Auto)0 to 600seconds
OtherStop delay adjustment range0 to 600seconds
OtherTime delay start (A15) adjustableup to 15-seconds
OtherTime delay stop (A15) adjustable30-seconds to 5 minutesminutes
OtherUnder Frequency Roll Off (UFRO) knee point, 50 Hz units48 to 49Hz
OtherUnder Frequency Roll Off (UFRO) knee point, 60 Hz units58 to 59Hz
OtherUnder-frequency roll-off threshold (UFRO)typically 59 Hz for 60 Hz applications and 49 Hz for 50 Hz applicationsHzAVR UFRO pot preset
OtherWeak battery warning thresholdbelow 60% of nominal for two seconds% of nominalduring starting
PressureAir cleaner element cleaning, compressed air pressure30psi (207 kPa)blow through element from clean side; nozzle at least 1 inch (25 mm) away
PressureDetector oil pressure normal range after reset25 to 40psi (172 to 275 kPa)
PressureEngine oil pressure - K19 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - K38 normal45-65psi (310-448 kPa)run mode
PressureEngine oil pressure - K50 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - L10/M11 normal30-50psi (207-345 kPa)run mode
PressureEngine oil pressure - NTA 855 normal35-50psi (241-345 kPa)run mode
PressureEngine oil pressure - V28 normal50-90psi (345-620 kPa)run mode
PressureEngine oil pressure shutdown limit - L10/M1120psi (138 kPa)run mode value
PressureEngine oil pressure shutdown limit - L10/M118psi (55 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1112psi (83 kPa)idle mode value

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water / E.G. / DCA mixtureCooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist).
Coolantwater/antifreeze mixture (permanent type antifreeze)Clean, low mineral content water free of chloride, sulphate or acidMix water and antifreeze per supplier recommendation for lowest expected ambient temperature; do not use antifreeze containing anti-leak additives
Engine oilSAE 5W syntheticAPI class CC/CD; sulphated ash content not exceeding 1.85 percent; pour point 9°F (5°C) below lowest expected temperature; viscosity 10,000 mPa.s maximum at -31°F (-35°C) and 4.1 mm2/s minimum at 212°F (100°C)above -25°CRecommended when ambient temperature is consistently below -13°F (-25°C) and there is no provision to keep the engine warm; do not use petroleum base 5W grade oil
Engine oilmultigrade / multiviscosityAPI Class CC/CD; maximum sulphated ash content 1.85 percent-25°C to 35°CSpecifications section lists ambient ranges -13°F to 95°F (-25°C to 35°C), 14°F (-10°C) and above, and 32°F (0°C) and above; single grade oil not recommended; do not mix oils of another classification or brand
FuelDieselDay tank fuel transfer pump maintains reservoir of diesel fuel in the day tank.
FuelNo. 2 dieselEngine will also operate on No. 1 fuel or other similar fuels if they meet certain specifications
GreaseKluber, type ASONIC GHY7275.0 gramsP7 generator bearing re-lubrication grease fill quantity; fill period 4000-4500 hours. Must not be mixed with any other type.
GreaseLithium based greaseMobilux No. 2 or Shell Alvania R32.74 oz (81 ml)Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity.
GreaseMolykoteOnan #524-0118Apply a layer on the end-bell bearing bore before inserting bearing
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz (81 ml)End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity.
OtherDonaldsons D1400 solvent (or equivalent)Air cleaner element cleaning: soak filter at least 15 minutes in water and Donaldsons D1400 solvent.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

66
CodeNameMeaningSeverityAction
101IDLE MODEEngine operating in idle modeInfoRemove ground from engine idle input to return to normal speed and voltage.
102EMERGENCY STOPLocal or remote Emergency Stop activatedShutdownPull button out or turn clockwise to pop out; move Run/Off/Auto switch to Off; press Reset; select Run or Auto. Reset only at PCC front panel.
200LOW OIL PRESSUREEngine oil pressure dropped to an unacceptable levelWarningFollow 201 Low Oil Pressure procedure.
201LOW OIL PRESSUREEngine oil pressure below shutdown trip pointShutdownCheck oil level, replenish if low, reset control and restart; contact authorized service center.
204OIL PRES SENDEREngine oil pressure sender not functioning correctlyWarningCheck sender connection; contact authorized service center.
210LOW COOLANT TEMPEngine coolant temperature 70 F (21 C) or lowerWarningCheck coolant heater power, fuse and cord; check coolant level and leaks.
211HIGH COOLANT TEMPEngine operating near cooling system capacityWarningReview 212 correction list; increase in load or higher ambient may cause shutdown.
212HIGH COOLANT TEMPEngine overheated; coolant above shutdown trip pointShutdownCool engine; check coolant level, airflow obstructions and fan belt; reset and restart.
213COOLANT SENDERResistance of coolant temperature sender out of rangeWarningContact authorized service center.
214LOW COOLANT LVLEngine coolant level below trip pointWarningCool engine; check coolant level and leaks; reset control and restart.
215LOW COOLANT LVLEngine coolant level below trip pointShutdownCool engine; check coolant level and leaks; reset control and restart. Shutdown will not occur in Idle mode.
220MAG PICKUPMag pickup speed indication not sensed or does not match output frequencyShutdownRestart and check RPM on digital display; contact authorized service center.
221FAIL TO CRANKPossible fault with control or starting systemShutdownClean and tighten battery cables; recharge or replace battery; contact service center.
222OVERCRANKPossible fuel system problemShutdownCheck fuel tank, leaks, plugged lines, fuel filter and air filter; reset control and restart.
223OVERSPEEDEngine exceeded normal operating speed (2070 rpm @ 60 Hz; 1800 rpm @ 50 Hz)ShutdownContact authorized service center.
224FAIL TO SYNCHRONIZEGenerator set has not synchronized to the system bus within the allowable time frame.WarningCheck governor system stability; adjust governing and synchronizer parameters; check fuel system.
226FAIL TO CLOSEParalleling breaker has been given a signal to close, but has not closed properly.ShutdownVerify breaker charging mechanism; check close signal; verify auxiliary contact signals.
230LOW DC VOLTAGEBattery voltage below 24 VDCWarningCheck battery charger fuse; recharge or replace battery; clean and tighten cable terminals.
231HIGH DC VOLTAGEBattery voltage exceeds 32 VDCWarningContact authorized service center.
232WEAK BATTERYBattery voltage drops below 60% of nominal for two seconds during startingWarningSee warning message 230 LOW DC VOLTAGE.
240LOW FUEL - DAYDay tank fuel supply running lowWarningCheck fuel supply and replenish as required.
241LOW FUELFuel supply running lowWarningCheck fuel supply and replenish as required.
250EEPROM ERRORPCC memory error; data corruption of critical operating parametersShutdownContact authorized service center.
251EEPROM ERRORPCC memory error; data corruption of noncritical operating parametersWarningContact authorized service center.
252EEPROM ERRORPCC memory error; data corruption of noncritical operating parametersWarningContact authorized service center.
260CUSTOMER FAULT 1Customer defined input closed to groundShutdown or warning preselected; message is editable; contact authorized service center.
261GROUND FAULTCustomer defined input closed to groundShutdown or warning preselected; message is editable; contact authorized service center.
262RUPTURE BASINCustomer defined input closed to groundShutdown or warning preselected; message is editable; contact authorized service center.
263HIGH GEN TEMPCustomer defined input closed to groundShutdown or warning preselected; message is editable; contact authorized service center.
270PHASE ROTATIONThe phase relationship between the generator set and the system bus is not matched.ShutdownVerify genset phase rotation matches bus; verify control wiring to bus PT module.
272FIRST STARTPowerCommand control is not receiving a proper signal from the system master first start sensor.WarningVerify Master First Start Sensor and interconnection wiring.
301HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal, or 110% of nominal for 10 secondsShutdownContact authorized service center.
303LOW AC VOLTAGEOne or more phase voltages dropped below 85% of nominal for 10 secondsShutdownContact authorized service center.
313UNDER FREQUENCYEngine speed dropped below 90% of nominal for 10 secondsShutdownLoad Dump signal initiated five seconds before shutdown; contact authorized service center.
320OVERCURRENTGenerator output current exceeded 110% of rated for 60 secondsWarningContact authorized service center.
321OVERCURRENTGenerator output current exceeded 110% of rated; PCC time/current calculation initiated shutdownShutdownContact authorized service center.
322SHORT CIRCUITGenerator output current exceeded 175% of ratedShutdownContact authorized service center.
330OVERLOADThree-phase power output exceeds 105% of standby (or 115% of prime) ratingWarningLoad Dump output activated after five seconds; warning activated after 60 seconds; contact authorized service center.
335REVERSE POWERImproper CT or PT phasing (non-parallel units only)ShutdownContact authorized service center.
337LOSS OF EXCITATIONAlternator excitation system is improperly adjusted or has failed.ShutdownCheck output voltage calibration, load sharing lines, and leading power factor loads.
FAULT 1Fault 1 (Red)Engine shut down because of a customer-connected system fault; part of a 10 second time delay shutdown circuit.ShutdownService as required by the customer-supplied fault indicating switches.
FAULT 2Fault 2 (Red)Engine shut down because of a customer-connected system fault; part of a non-time delay shutdown circuit.ShutdownService as required by the customer-supplied fault indicating switches.
GFGround Fault Alarm (Optional)Ground fault relay monitors neutral to ground connection and line to neutral, activating a fault alarm when the connection is broken or a ground fault is sensed.WarningClear fault condition by pushing the Run/Stop (Reset)/Remote switch to Reset (auto reset link set at factory).
HETHigh Engine Temperature (Red)Engine shut down because of excessively high engine coolant temperature (greater than 230 deg F).ShutdownCheck coolant level and leaks; service cooling system; reset engine control.
HI ENG TEMPHigh Engine TemperatureEngine shut down due to critically high coolant temperature (above 215F/102C).Shutdown
High Engine TemperatureHigh Engine TemperatureOn a five-light system, the High Engine Temperature switch connects to module A13-20; closure applies a ground which turns on A13-Q6 triggering A13-CR7 to conduct, providing a ground path for the fault light and to relay A11-K2 for engine shutdown. On single-light systems it is connected in parallel with low oil pressure to pin 4 of A12ShutdownCheck coolant level, radiator cooling duct, fan belts, temperature sensor, thermostat and city water input solenoid valve
LETLow Engine Temperature (Yellow)Engine temperature is less than 70 deg F and the engine might not start.WarningPlug in, repair or install engine coolant and oil heaters.
LO FUELLow FuelFuel supply is marginally low, if equipped (Detector-12).Warning
LO OIL PRESLow Oil PressureEngine shut down due to critically low oil pressure (below 14 psi/97 kPa).Shutdown
LOPLow Oil Pressure (Red)Engine shut down because of excessively low engine oil pressure (less than 14 psi).ShutdownCheck oil level and oil leaks; service lubricating system; reset engine control.
LOW ENG TEMPLow Engine TemperatureEngine water jacket temperature is 70F/21C or lower; indicates possible inoperative coolant heater (Detector-12).Warning
Low Engine TemperatureLow Engine TemperatureClosure of the Low Engine Temperature Sensing switch applies a ground to A13-8; A13-Q4 conducts and set-panel and remote Low Engine Temperature lights indicate a fault; there is no alarm or engine shutdown with this faultWarningIndicates a fault only; no shutdown or alarm
LOW FUELLow Fuel (Yellow)Fuel level in the supply tank has dropped below the reserve necessary to run the set at full load for the prescribed number of hours.WarningFill the main fuel supply tank with the appropriate grade of fuel.
Low Oil PressureLow Oil PressureClosure of the low oil pressure switch applies a ground to pin 4 of the A12 module; A12-Q4 turns on causing unijunction A12-Q7 to fire and trigger A12-CR6; fault light illuminates and on standard installations alarm and engine shutdown are initiated (Penn State sets alarm only). An adjustable rheostat A12-R11 provides a timed-delay up to 10 secondsShutdownCheck oil level and oil pressure sensor; disconnect wire from TB11-30 and check if light remains on
OCOvercrank (Red)Engine shut down because it did not start during the timed cranking period (approximately 75 seconds, including two rest periods).ShutdownService the set as necessary; reset engine control.
OSOverspeed (Red)Engine shut down because of overspeed.ShutdownAdjust the Electronic Overspeed Module; check governor for binding; reset engine control.
OVERCRANKOvercrankStarter locked out because of excessive cranking time (limited to 75 seconds).Shutdown
OvercrankOvercrankEngine fails to start after cranking for 75 seconds; capacitor A12-C1 on the Engine Monitor module charges to turn on A12-CR1, illuminates the fault light and applies a ground to pin 7 on A11 Engine Shutdown module which energizes A12-K1 allowing K12 to drop out and stop crankingShutdownCheck fuel system (valves open, tanks full) and ignition system; refer to engine manufacturer's troubleshooting
OVERSPEEDOverspeedEngine shut down because of excessive speed.Shutdown
OverspeedOverspeedEngine speed in excess of 2010 rpm causes transistor A16-Q2 on the Overspeed Sensor module to conduct and apply a ground to pin 2 of A12 Engine Monitor module; A12-Q8 turns on and triggers A12-CR8 to illuminate the fault light and initiate shutdown and alarmShutdownCheck throttles for freedom of movement and governor linkage; check injector rack movement; verify governor setting
PRE HI ENG TEMPPre-High Engine TemperatureCoolant temperature is marginally high (205F/97C or higher).WarningAttend to when generator set is shut down.
PRE LO OIL PRESPre-Low Oil PressureEngine oil pressure is marginally low (20 psi/138 kPa or less).WarningAttend to when generator set is shut down.
PRE-HETPre High Engine Temperature (Yellow)Engine coolant temperature is abnormally high (greater than 220 deg F).WarningShut down if possible or disconnect non-critical loads; service cooling system.
PRE-LOPPre Low Oil Pressure (Yellow)Engine oil pressure is abnormally low (less than 20 psi).WarningShut down if possible or disconnect non-critical loads; service lubricating system.
RUNRunGreen lamp comes on when both primary and secondary starter circuits open after unit starts.Info
SWITCH OFFSwitch-off (Flashing Red)The Run/Stop/Remote switch is in the Stop position, preventing remote automatic operation.InfoPush the Run-Stop-Remote switch to Remote.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.

Tools: Dial indicator, Wooden shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point on capscrew head or flat surface of drive disc at bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Record maximum positive and negative dial indicator readings as the engine completes one revolution.
  5. T.I.R. equals the sum of the maximum positive and negative readings.
  6. Maximum T.I.R. should not be more than .001 inch for each inch of radius.
  7. Remove equal shims from under both generator mounting feet to lower the generator.
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Gain Adjustment adjustment
  1. Close the main line circuit breaker and apply approximately 1/4 of the rated load.
  2. Make sure the engine speed is constant.
  3. Turn the GAIN potentiometer clockwise slowly until the engine speed is not constant.
  4. Slowly turn the potentiometer counterclockwise until a constant speed is achieved, then an additional 1/2 division.
Governed Speed Adjustment adjustment
  1. For 60 Hz full load, set engine no-load governed speed to 60.0 Hz (1800 RPM) isochronous, 61.8 Hz (1854 RPM) for 3% droop, or 63.0 Hz (1890 RPM) for 5% droop.
  2. For 50 Hz full load, set engine no-load governed speed to 50.0 Hz (1500 RPM) isochronous, 51.5 Hz (1545 RPM) for 3% droop, or 52.5 Hz (1575 RPM) for 5% droop.
  3. Use the SPEED ADJUST potentiometer on the engine instrument panel for fine speed adjustments of less than ±100 RPM.
Governor Calibration Checks adjustment

Tools: Frequency meter or tachometer, Jumper wire

  1. Start the generator set.
  2. Adjust engine no-load speed to the desired allowable speed droop using the Run Speed potentiometer.
  3. With no load, turn GAIN clockwise slowly until engine speed oscillates.
  4. Reduce GAIN slowly counterclockwise until engine speed is stable.
  5. Upset the governor by momentarily shorting terminals 7 and 10 on the governor control.
  6. Apply and remove loads to check generator set response.
HC4-7 Axial Alignment Procedure adjustment

Tools: Dial indicator with magnetic base or clamp

  1. Check only when an objectionable vibration is present.
  2. Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
  3. Position sensor point on the generator shaft hub.
  4. Bar the engine over in a clockwise rotation as viewed from engine flywheel through a couple of rotations.
  5. Record indicator readings in eight equally spaced points around the shaft diameter.
  6. Remove the capscrews connecting drive discs and flywheel and mark discs and flywheel.
  7. Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
  8. Put capscrews back in and retorque. Recheck shaft alignment.
  9. If runout unchanged, rotate discs to 30, 60 or 90 degrees from original location.
  10. If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
P7 Axial Alignment Procedure adjustment
  1. Check only when an objectionable vibration is present.
  2. Remove the capscrews connecting drive discs and flywheel.
  3. Mark the drive discs and flywheel with respect to each other.
  4. Rotate engine or generator so drive discs holes are repositioned two bolt holes from original location.
  5. Put capscrews back in and retorque. Recheck/record vibration levels.
  6. Repeat this test until drive disc holes are repositioned 180 degrees from original location.
  7. Review vibration data and position drive disc in lowest recorded level location.
Preliminary Governor Adjustments adjustment
  1. Idle Speed potentiometer: turn screw counterclockwise 20 turns then clockwise 10 turns to set mid position.
  2. Run Speed potentiometer: turn screw counterclockwise 20 turns then clockwise 10 turns to set mid position.
  3. Gain potentiometer: turn the screw fully counterclockwise.
  4. Droop potentiometer: turn fully counterclockwise for isochronous operation; approximately 40 for 3 percent droop; approximately 80 for 5 percent droop.
Reconnection adjustment
  1. Reconnect bus-bars for the different voltage per Figure 16
  2. Reconnect lead from terminal 63 (inside control box) to either H3, H4 or H5
  3. Select the proper tap on voltage reference transformer (T21) per Figure 2
Sensitivity Reference Circuit adjustment

Tools: Soldering iron

  1. Solder wire W1 to terminal E1 for frequency sensitivity
  2. Solder wire W1 to terminal E2 for non-frequency sensitivity

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12 lead generator setsLoad wires are routed through the CTsReconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
6 lead generator setsGenerator output leads are routed through the CTsNon-reconnectable gensets (6 leads) have single secondary CTs (2 pins).
Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F)Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100).
ACT21 – U load leadsA phaseCT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground.
A (U)Bus PT module TB1 Abus A phaseBus PT module A39.
A (U)CT21U load leads (A phase)CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground.
BCT22 – V load leadsB phaseCT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground.
B (V)Bus PT module TB1 Bbus B phaseBus PT module A39.
B (V)CT22V load leads (B phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
CCT23 – W load leadsC phaseCT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground.
C (W)Bus PT module TB1 Cbus C phaseBus PT module A39.
C (W)CT23W load leads (C phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
NBus PT module TB1 Nbus neutralBus PT module A39.
110/1903Code 51750 Hz; transformer tap H3
115/2003Code 51750 Hz; transformer tap H4
120/2083Code 1760 Hz; transformer tap H3
120/2083Code 51750 Hz; transformer tap H4
120/2403Code 5DNot reconnectible; frequency 60 Hz; transformer tap H5
127/2203Code 1760 Hz; transformer tap H4
127/2203Code 51750 Hz; transformer tap H5
139/2403Code 1760 Hz; transformer tap H5
220/3803Code 517 / Code 750 Hz H3 and 60 Hz H3; transformer tap H3
230/4003Code 51750 Hz; transformer tap H4
240/4163Code 517 / Code 1750 Hz H4 and 60 Hz H3; transformer tap H4
240/4803Code 6DNot reconnectible; frequency 60 Hz; transformer tap H5
254/4403Code 517 / Code 1750 Hz and 60 Hz; transformer tap H5
277/4803Code 1760 Hz; transformer tap H5
347/6003Code 9X60 Hz; transformer tap H5
high voltage genset12-lead CT secondary wire marked 2/3 to pin 22/3For high voltage gensets.
low voltage genset12-lead CT secondary wire marked 2/3 to pin 32/3For low voltage gensets.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan KTTA50 family

11
Part #DescriptionCategory
140-2503Bracket, MountingAir filter
140-3163Cleaner, Air (No Replaceable Element)Air filter
140-3230Cleaner, Air (Includes Elements - See Ref. No. 25 and 26)Air filter
0300-4623-33DFLE (600V)Current transformer
0300-4623-57DFLE BR (0-480V)Current transformer
140-1260Fitting, Safety FilterService part / kit
140-2395Tube, Air InletService part / kit
140-2504-01Bracket - Right SideService part / kit
140-2504-02Bracket - Left SideService part / kit
140-2509Tube, Air InletService part / kit
140-2528Shield – Air In HeatService part / kit

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan KTTA50-G2?

The Cummins/Onan KTTA50-G2 engine has an oil capacity of 151.4 liters.

What is the displacement of the Cummins/Onan KTTA50-G2?

The Cummins/Onan KTTA50-G2 has a displacement of 50.3 liters with 16 cylinders.

Which generators use the Cummins/Onan KTTA50-G2 engine?

The Cummins/Onan KTTA50-G2 powers 1 generator set(s), including Cummins/Onan DFM.

How often should you change the oil in the Cummins/Onan KTTA50-G2?

The Cummins/Onan KTTA50-G2 oil change interval is every 250 hours.

What is a common problem with the Cummins/Onan KTTA50-G2 engine?

A commonly reported issue on generators using the Cummins/Onan KTTA50-G2 is: LO OIL PRES lamp lights. Cause: Low coolant level. Fix: Check for low coolant level and replenish if required; look for possible coolant leakage points and repair as required.