| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop activated | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, replenish if low, reset control and restart; contact authorized service center. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Review 212 correction list; increase in load or higher ambient may cause shutdown. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Shutdown | Cool engine; check coolant level, airflow obstructions and fan belt; reset and restart. |
| 213 | COOLANT SENDER | Resistance of the coolant temperature sender is out of range. | Warning | Contact authorized service center. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Cool engine; check coolant level and leaks; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Cool engine; check coolant level and leaks; reset control and restart. Shutdown will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication not sensed or does not match output frequency | Shutdown | Restart and check RPM; check PCC model setting; inspect and test MPU. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system. | Shutdown | Clean and tighten battery cables; recharge or replace battery; contact service center. |
| 222 | OVERCRANK | Possible fuel system problem. | Shutdown | Check fuel tank, leaks, plugged lines, fuel filter and air filter; reset control and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed. (115% ±1% of nominal). | Shutdown | Contact authorized service center. |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Lower battery charger float level if applicable; check engine DC alternator. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | See warning message 230 LOW DC VOLTAGE. |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Low fuel signal received. | Warning | Check fuel supply and replenish; check for short to ground in external wiring. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform initial start setup procedure; replace digital board (A32) if fault repeats. |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform adjustment and calibration procedures; replace digital board (A32) if fault repeats. |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify selected values; repeat save operation; replace digital board (A32) if fault repeats. |
| 260 | CUSTOMER FAULT 1 | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 261 | GROUND FAULT | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 262 | RUPTURE BASIN | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 263 | HIGH GEN TEMP | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Shutdown or warning preselected; message is editable; contact authorized service center. |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Verify genset phase rotation matches bus; verify control wiring to bus PT module. |
| 272 | FIRST START | PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Verify Master First Start Sensor and interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds. | Shutdown | Contact authorized service center. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Contact authorized service center. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Load Dump signal initiated five seconds before shutdown; contact authorized service center. |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Contact authorized service center. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Contact authorized service center. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Contact authorized service center. |
| 330 | OVERLOAD | Three-phase power output exceeds 105% of standby (or 115% of prime) rating. | Warning | Load Dump output activated after five seconds; warning activated after 60 seconds; contact authorized service center. |
| 335 | REVERSE POWER | Power is flowing into the generator set rather than out from the unit. | Shutdown | Verify CT connections, load sharing lines, and generator set frequency/voltage. |
| 337 | LOSS OF EXCITATION | Alternator excitation system is improperly adjusted or has failed. | Shutdown | Check output voltage calibration, load sharing lines, and leading power factor loads. |
| FAULT 1 | Fault 1 | Undedicated customer-defined fault; may be programmed as timed or non-timed shutdown or fault light only. | | |
| FAULT 2 | Fault 2 | Undedicated customer-defined fault, same features as Fault 1. | | |
| HI ENG TEMP | High Engine Temperature | Engine shut down due to critically high coolant temperature (above 215F/102C). | Shutdown | |
| LO FUEL | Low Fuel | Fuel supply is marginally low, if equipped (Detector-12). | Warning | |
| LO OIL PRES | Low Oil Pressure | Engine shut down due to critically low oil pressure (below 14 psi/97 kPa). | Shutdown | |
| LOW ENG TEMP | Low Engine Temperature | Engine water jacket temperature is 70F/21C or lower; indicates possible inoperative coolant heater (Detector-12). | Warning | |
| OVERCRANK | Overcrank | Starter locked out because of excessive cranking time (limited to 75 seconds). | Shutdown | |
| OVERSPEED | Overspeed | Engine shut down because of excessive speed. | Shutdown | |
| PRE HI ENG TEMP | Pre-High Engine Temperature | Coolant temperature is marginally high (205F/97C or higher). | Warning | Attend to when generator set is shut down. |
| PRE LO OIL PRES | Pre-Low Oil Pressure | Engine oil pressure is marginally low (20 psi/138 kPa or less). | Warning | Attend to when generator set is shut down. |
| RUN | Run | Green lamp comes on when both primary and secondary starter circuits open after unit starts. | Info | |
| SWITCH OFF | Switch Off | Generator set is not in automatic start operation mode (flashing red). | Info | |