Cummins/Onan KTTA-50-G1 Engine
The Cummins/Onan KTTA-50-G1 is an engine. It powers generator sets from Cummins/Onan, including the DBMA, DCMA and DMMA. It holds 38.5 L (10.2 gal) of oil and 97.3 L (25.7 gal) of coolant.
Also known as: Cummins KTTA-50-G1
Part of the Cummins/Onan KTTA50 engine family — 3 variants share parts & fitment.
Engine specifications
| Oil capacity | 38.5 L |
|---|
| Coolant capacity | 97.3 L |
|---|
Common problems
15- The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run — The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay 12
- SWITCH OFF lamp flashes — Indicates Run-Stop-Remote switch is in the Stop position which will prevent automatic starting 8
Cause: Run-Stop-Remote switch is in the Stop position
Fix: Moving the Run-Stop-Remote switch to the Remote position will stop the lamp flashing and enable automatic starting. - PRE-LO OIL PRES lamp lights. Engine continues to operate — Indicates engine oil pressure has dropped to 20 psi (138 kPa) 4
Cause: Engine oil pressure has dropped to 20 psi (138 kPa)
Fix: If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure. If engine can be stopped, follow procedure in step 5. - PRE-HI ENGINE TEMP lamp lights. Engine continues to operate — Indicates engine has begun to overheat and engine temperature has risen to approximately 205° F (97°C) 2
Fix: If generator is powering non-critical and critical loads, and cannot be shut down: reduce load if possible by turning off non-critical loads; check air inlets and outlets and remove any obstructions to airflow; open doors or windows in generator area to increase ventilation. If engine can be stopped, follow procedure in Step 3. - OVERCRANK lamp lights and engine stops cranking — Or: Engine runs, shuts down, and LO OIL PRES lamp lights — Indicates possible fuel system problem 6
Cause: Possible fuel system problem
Fix: Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; check for dirty fuel filter and replace if necessary (see MAINTENANCE section); check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section); refer to step 5; reset the control and restart after correcting the problem; contact your distributor for service if none of the above applies. - No AC output voltage (Note: If unit is equipped with an excitation breaker located on back side of output box, near regulator box, confirm it is at ON position) 16
Cause: Voltage regulator is inoperative
Fix: Refer to Initial Start and Checks, and Adjustments sections of your Installation Manual for voltage check and adjustment procedures; contact your distributor if voltage build-up is still a problem. - LO OIL PRES lamp lights. Engine shuts down — Indicates engine oil pressure has dropped to 14 psi (97 kPa) 5
Cause: Engine oil pressure has dropped to 14 psi (97 kPa)
Fix: Check oil level, replenish as necessary; check oil lines and filters for leaks, repair as required; reset control and restart; contact your distributor if oil pressure is not in the range of 50 to 70 psi (345 to 483 kPa). - LO FUEL lamp lights. Engine shuts down and LO OIL PRES lamp lights — Indicates engine has run out of fuel 10
Cause: Engine has run out of fuel
Fix: Check fuel level and replenish as required. - LO FUEL lamp lights. Engine continues to run — Indicates diesel fuel supply is running low 9
Cause: Diesel fuel supply is running low
Fix: Check fuel supply and replenish as required. - LO ENG TEMP lamp lights. Set is in standby mode but is not operating — Indicates engine coolant heater is not operating or is not circulating coolant (lamp lights when engine coolant temperature is 70° F (21° C) or lower; since the lamp goes out after the engine warms up, there should be no cause for alarm if it remains lighted during initial generator set operation) 11
Cause: Engine coolant heater is not operating or is not circulating coolant
Fix: Check for the following conditions: coolant heater not connected to power supply, check for blown fuse or disconnected heater cord and correct as required; check for low coolant level and replenish if required, look for possible coolant leakage points and repair as required; contact your distributor if none of the above applies. - HI ENG TEMP lamp lights. Engine shuts down — Indicates engine has overheated (engine temperature has risen above 215° F/102° C) or coolant level is low (sets with coolant level sensor) 3
Cause: Engine has overheated (engine temperature has risen above 215° F/102° C); coolant level is low (sets with coolant level sensor)
Fix: Allow engine to cool down completely before proceeding: check coolant level and replenish if low, look for possible coolant leakage points and repair if necessary; check for obstructions to cooling airflow and correct as necessary; check for a slipping fan belt, tighten if loose; reset control and restart after locating and correcting problem; contact your distributor if none of the above applies. - Green RUN lamp lights following engine start-up — Indicates all engine systems are normal 1
Fix: No corrective action required. - Green RUN lamp does not light following engine start-up — Indicates possible Start/Disconnect relay failure 17
Cause: Possible Start/Disconnect relay failure
Fix: Contact your distributor for assistance. - Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits 13
Cause: The monitor board or a sensor may be at fault
Fix: Contact your distributor for service. - Engine will not crank — Indicates possible fault with control or starting system 15
Cause: Fault lamp on; poor battery cable connections; discharged or defective battery
Fix: Correct fault and reset control; clean the battery cable terminals and tighten all connections; recharge or replace the battery; contact your distributor for assistance if none of the above applies.
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan KTTA-50-G1.
Parts cataloged across the Cummins/Onan KTTA50 family
11| Part # | Description | Category |
|---|
| 140-2503 | Bracket, Mounting | Air filter |
| 140-3163 | Cleaner, Air (No Replaceable Element) | Air filter |
| 140-3230 | Cleaner, Air (Includes Elements - See Ref. No. 25 and 26) | Air filter |
| 0300-4623-33 | DFLE (600V) | Current transformer |
| 0300-4623-57 | DFLE BR (0-480V) | Current transformer |
| 140-1260 | Fitting, Safety Filter | Service part / kit |
| 140-2395 | Tube, Air Inlet | Service part / kit |
| 140-2504-01 | Bracket - Right Side | Service part / kit |
| 140-2504-02 | Bracket - Left Side | Service part / kit |
| 140-2509 | Tube, Air Inlet | Service part / kit |
| 140-2528 | Shield – Air In Heat | Service part / kit |
Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.
Common questions
What is the oil capacity of the Cummins/Onan KTTA-50-G1?
The Cummins/Onan KTTA-50-G1 engine has an oil capacity of 38.5 liters.
Which generators use the Cummins/Onan KTTA-50-G1 engine?
The Cummins/Onan KTTA-50-G1 powers 3 generator set(s), including Cummins/Onan DBMA, Cummins/Onan DCMA, Cummins/Onan DMMA.
What is a common problem with the Cummins/Onan KTTA-50-G1 engine?
A commonly reported issue on generators using the Cummins/Onan KTTA-50-G1 is: The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run — The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.