The Cummins/Onan g183g32 is a 60.2 L turbocharged and low temperature after-cooled engine. It powers generator sets from Cummins/Onan, including the DQKB and DQKC.
Also known as: Cummins g183g32
| Displacement | 60.2 L |
|---|---|
| Aspiration | turbocharged and low temperature after-cooled |
How to read your Cummins/Onan engine serial & model number →
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan g183g32.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Coolant heater(s) | Check | 8 hr | Daily | |
| Coolant level of radiators | Check | 8 hr | Daily | |
| Engine oil level | Check | 8 hr | Daily | |
| General set inspection | Inspect | 8 hr | Daily; check for oil, fuel, cooling and exhaust system leaks | |
| All hardware (fittings, clamps, fasteners) | Check | 100 hr | ||
| Battery charging system | Check | 100 hr | ||
| Battery electrolyte level | Check | 100 hr | ||
| Drive belts | Check | 100 hr | Visually check for wear or slippage; replace if hard or brittle | |
| Exhaust condensate trap | Drain | 100 hr | ||
| Generator air outlet | Check | 100 hr | ||
| Fan bearings (two) | Lubricate | 250 hr | 6 mo | |
| Radiator hoses | Inspect | 250 hr | 6 mo | Check for wear and cracks |
| Generator bearing (Frame 7 / Frame 8) | Lubricate | 500 hr | ||
| Generator insulation resistance | Test | 500 hr | ||
| Air cleaner | Check | 1000 hr | Replace as necessary | |
| Anti-freeze and DCA concentration | Check | 1000 hr | ||
| Crankcase breather | Clean | 1000 hr | ||
| Engine oil and filter | Change | 1000 hr | ||
| Fuel filter(s) | Drain | 1000 hr | ||
| Jacket Water & LTA cooling systems | Clean | 1000 hr | ||
| Jacket water coolant filters | Change | 1000 hr | ||
| Fuel filters | Change | 4000 hr |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Air gap (rotor to stator), normal | 0.3 | inch | |
| Clearance | Air gap (rotor to stator), normal | 7.5 | mm | |
| Clearance | Air gap (rotor to stator, Frame 8 removal), minimum | 0.2 | inch | |
| Clearance | Air gap (rotor to stator, Frame 8 removal), minimum | 5 | mm | |
| Clearance | Angular alignment T.I.R. limit | .001 per inch of radius | inch | |
| Clearance | Exhaust pipe to combustible wall or partition | 12 | inches (305 mm) | minimum |
| Clearance | Fan blade tips to fan shroud edge (Spec. A) | minimum 1/8 inch (3 mm) | inch | minimum |
| Clearance | Fan drive pulley alignment measurement (Spec. A) | 1.9 - 2.6 inch (48.3 - 66 mm) | inch | |
| Clearance | Fan drive pulley alignment offset (Spec. B) | 0.25 inch toward engine from straightedge | inch | |
| Clearance | Fan drive pulley position toward engine from straightedge | 0.25 | inch (nominal) | fan drive alignment |
| Clearance | Fuel lines to electrical wiring | 1/2 | inch (12.7 mm) | minimum |
| Clearance | Fuel lines to hot exhaust parts | 2 | inch (51 mm) | minimum |
| Clearance | Service/maintenance access clearance around genset | 1 | meter (3 feet) | generally, all sides |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | shimmed or grouted |
| Clearance | Vibration isolator base elevation difference | 0.25 inch (6 mm) | inch | maximum variation between isolator bases |
| Clearance | Vibration isolator top plate clearance | 0.25 inch (6 mm) or greater | inch | nominal or greater |
| Clearance | Vibration isolator top plate to base clearance | 0.25 | inch (6 mm) | minimum, on all isolators roughly equal |
| Other | Fan side bearing grease quantity | 39 | grams | |
| Other | Generator winding minimum insulation resistance (600 VAC or less), megger 500 VDC | 5.0 – 1.0 | megohms | main stator / main rotor |
| Other | Oil capacity, oil pan only, high capacity | 100 Gal (379 L) | Gal (L) | |
| Other | Oil capacity, oil pan only, standard capacity | 69 Gal (261 L) | Gal (L) | |
| Other | Oil capacity, system (w/Std. Filters), high capacity | 105 Gal (398 L) | Gal (L) | |
| Other | Oil capacity, system (w/Std. Filters), standard capacity | 74 Gal (280 L) | Gal (L) | |
| Other | Pulley side bearing grease quantity | 31 | grams | |
| Other | Start Delay adjustment range | 0 to 300 | seconds | remote starting in Auto mode |
| Other | Stop Delay adjustment range | 0 to 600 | seconds | remote stopping in Auto mode |
| Pressure | Maximum allowable exhaust back pressure | 6.8 | kPa (2.0 in [51 mm] H2O) | |
| Resistance | Exciter rotor (Frame 7G) | 0.096 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter rotor (Frame 7H) | 0.096 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter rotor (Frame 8, HV814C) | 0.084 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter rotor (Frame 8, HV814D) | 0.084 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter rotor (Frame 8, HV814E) | 0.084 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter rotor (Frame 8, LV814C/LV814D) | 0.096 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter rotor (Frame 8, MV814C/MV814D) | 0.084 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter stator (Frame 7G) | 17 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter stator (Frame 7H) | 17 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter stator (Frame 8, HV814C) | 15 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter stator (Frame 8, HV814D) | 15 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter stator (Frame 8, HV814E) | 15 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter stator (Frame 8, LV814C/LV814D) | 15 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Exciter stator (Frame 8, MV814C/MV814D) | 15 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 7G) | 1.64 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 7H) | 1.75 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 8, HV814C) | 1.21 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 8, HV814D) | 1.28 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 8, HV814E) | 1.38 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 8, LV814C) | 1.33 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 8, LV814D) | 1.426 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 8, MV814C) | 1.164 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor (Frame 8, MV814D) | 1.229 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main rotor insulation minimum resistance, 5001 thru 15000 VAC | 1000 | Meg | |
| Resistance | Main rotor insulation minimum resistance, 600 VAC or less | 5.0 – 1.0 | Meg | new – in service |
| Resistance | Main stator (Frame 8, HV814C, 11K 50Hz) | 0.945 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main stator (Frame 8, HV814C, 7.2K 60Hz) | 0.340 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main stator (Frame 8, HV814D, 11K 50Hz) | 0.780 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main stator (Frame 8, HV814D, 7.2K 60Hz) | 0.280 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main stator (Frame 8, HV814E, 11K 50Hz) | 0.615 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main stator (Frame 8, HV814E, 7.2K 60Hz) | 0.220 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main stator (Frame 8, LV814C, 440-480V 60Hz) | 0.000483 | ohms | approximately, at 68°F (20°C) +10% |
| Resistance | Main stator (Frame 8, LV814D, 440-480V 60Hz) | 0.000368 | ohms | approximately, at 68°F (20°C) +10% |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | 50% ethylene or propylene glycol and 50% water | PGA drawing 0880-0152 | 100.0 Gal (379 L) | Spec. A jacket water (front) radiator capacity; Spec. A low-temperature aftercooling (rear) radiator 34 Gal (129 L). 2P2L (two pump two loop) cooling system. | |
| Engine oil | Refer to Cummins QSK45/60 Series Engine Operation and Maintenance Manual for lubricating oil recommendations/specifications | Oil capacity: oil pan only standard 69 Gal (261 L), high 100 Gal (379 L); system with std filters standard 74 Gal (280 L), high 105 Gal (398 L) | |||
| Fuel | ASTM No. 2 Diesel | Cummins engines normally use ASTM No. 2 Diesel fuel; will operate on alternate diesel fuels within QSK45/QSK60 specifications. Fuel filter/strainer/water separator of 100-120 mesh required. Never use galvanized or copper fuel lines. | |||
| Grease | lithium based grease (Mobilux EP 2, Mobilith AW 2, or Shell Alvania R3) | Fan side bearing 39 grams, pulley side bearing 31 grams | |||
| Other | Fleetguard supplemental coolant additive (SCA), tradename DCA4 | 200.0 units (5 gallons [19 liters]) | Shipped with each radiator-cooled genset. If not filled using Fleetguard 'Compleat' antifreeze or equivalent, add 120 units (3 gallons [11.5 liters]) to jacket water (front) radiator and 80 units (2 gallons [7.5 liters]) to LTA (rear) radiator. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 111 | Internal ECM error | Shutdown | ||
| 112 | Actuator not responding | Shutdown | ||
| 113 | Actuator sensor fault | Warning | ||
| 115 | No speed signal | Shutdown | ||
| 116 | Time press sensor high | Shutdown | ||
| 117 | Time press sensor low | Shutdown | ||
| 118 | Pump press sensor high | Warning | ||
| 119 | Pump press sensor low | Warning | ||
| 121 | No engine speed signal | Warning | ||
| 122 | Manifold air press sensor | Warning | ||
| 123 | Manifold air press sensor | Warning | ||
| 1311 | Customer input #1 | Customer defined fault; nature is an optional customer selection | ||
| 1312 | Customer input #2 | Customer defined fault | ||
| 1313 | Network Fault 1 | |||
| 1314 | Network Fault 2 | |||
| 1315 | Network Fault 3 | |||
| 1316 | Network Fault 4 | |||
| 1317 | Customer input #3 | |||
| 1318 | Customer input #4 | |||
| 1319 | High alternator temp | Warning | ||
| 1321 | Common warning driver | Warning | ||
| 1322 | Load gov kW setpoint oor hi | Shutdown | ||
| 1323 | Load gov kW setpoint oor lo | Shutdown | ||
| 1324 | Load gov kVAR oor hi | Warning | ||
| 1325 | Load gov kVAR oor lo | Warning | ||
| 1326 | Backup starter disconnect | Warning | ||
| 1327 | Load gov kW analog oor | Shutdown | ||
| 1328 | Genset CB tripped | Warning | ||
| 1329 | AVR DC power failure | Warning | ||
| 1331 | AVR driver shorted | Shutdown | ||
| 1332 | Manual switch oor lo | Shutdown | ||
| 1333 | Manual switch oor hi | Shutdown | ||
| 1334 | Critical scaler oor | Shutdown | ||
| 1335 | Non critical scaler oor | Warning | ||
| 1336 | Cooldown complete | Shutdown | ||
| 1337 | Network wink | Info | ||
| 1341 | Load demand stop | Shutdown | ||
| 1342 | Slot 0 card | Shutdown | ||
| 1343 | Slot 1 card | Shutdown | ||
| 1344 | Slot 2 card | Shutdown | ||
| 1345 | Slot 3 card | Shutdown | ||
| 1346 | Slot 4 incorrect | Shutdown | ||
| 1347 | Slot 5 card | Shutdown | ||
| 1348 | Slot 6 card | Shutdown | ||
| 1349 | Slot 7 card | Shutdown | ||
| 135 | Oil pressure sensor | Warning | ||
| 1351 | Slot 4 / network enabled | Warning | ||
| 141 | Oil pressure sensor | Warning | ||
| 1414 | Run relay contact | Warning | ||
| 1415 | Run relay driver | Warning | ||
| 1416 | Fail to shutdown | Fault Bypass mode is enabled; used by service personnel for troubleshooting; ignores majority of system shutdown faults | Warning | |
| 1417 | Power down error | Control cannot power down due to unknown condition; possible drain on battery | Warning | Contact an authorized service center for service |
| 1419 | Fuel rail driver | Warning | ||
| 1421 | Timing rail driver #1 | Warning | ||
| 1422 | Timing rail driver #2 | Warning | ||
| 1424 | High side driver | Warning | ||
| 1427 | Overspeed relay driver | Warning | ||
| 1428 | LOP shutdown relay driver | Warning | ||
| 143 | Low oil pressure | Warning | ||
| 1433 | Emergency stop – local | Local Emergency Stop | Shutdown | Pull button out, move O/Manual/Auto switch to O, press Fault Acknowledge, select Manual or Auto |
| 1434 | Emergency stop – remote | Remote Emergency Stop | Shutdown | Pull button out, move O/Manual/Auto switch to O, press Fault Acknowledge, select Manual or Auto |
| 1435 | Engine cold | Warning | ||
| 1436 | PT fuel system drivers | Warning | ||
| 1437 | E-stop path fuse blown | Shutdown | ||
| 1438 | Fail to crank | Possible fault with control or starting system | Warning | Check battery cable connections; recharge or replace discharged/defective battery |
| 1439 | Fuel level low in day | Fuel supply is running low | Warning | Check fuel supply and replenish |
| 144 | Coolant temperature sensor | Warning | ||
| 1441 | Fuel level low in main | Fuel supply is running low | Warning | Check fuel supply and replenish |
| 1442 | Battery is weak | Battery voltage drops below 14.4 volts for two seconds during starting | Warning | See warning message 441 Low Battery Voltage |
| 1443 | Battery is dead | Battery has dropped below genset operating range (3.5 volts when cranking) to power starter and control circuitry | Warning | See warning message 441 Low Battery Voltage |
| 1444 | kW overload | Warning | ||
| 1445 | Alternator short circuit | Shutdown | ||
| 1446 | AC output voltage is high | Shutdown | ||
| 1447 | AC output voltage is low | Shutdown | ||
| 1448 | AC output frequency low | Shutdown | ||
| 1449 | AC output frequency high | Warning | ||
| 145 | Coolant temperature sensor | Warning | ||
| 1451 | Gen/Bus voltage differ | Warning | ||
| 1452 | Gen CB failed to close | Shutdown | ||
| 1453 | Gen CB failed to open | Shutdown |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ The fan belt idler is under tension; do not allow hands between idler and belt or fan hub.
Tools: Straightedge at least 48 inches (1219 mm), 8 mm hexagon wrench, 8-point socket and breaker bar or large wrench, Torque wrench
Tools: Straightedge at least 48 inches (1219 mm) long
⚠ The fan belt idler is under tension. Do not allow hands between the idler and the belt or the fan hub.
Tools: Straightedge at least 48 inches (1219 mm) long, 8-point socket and breaker bar
Tools: Dial indicator holding device, Magnetic base or clamp
Tools: Calibrated voltmeter
⚠ Disconnect negative battery cable(s) before beginning; accidental starting presents hazard of severe personal injury or death.
Tools: Dial indicator, Shims
Tools: Calibrated ammeter
⚠ Contacting high voltage components can cause electrocution; calibration must be performed by technically qualified personnel only.
Tools: Calibrated RMS multimeter (Fluke 87 or 8060A)
⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.
Tools: Jumper leads, 12 volt battery, Voltmeter
⚠ Hazardous voltage. After DC test voltage applied, reconnect Grounding Cluster to remove static charge after each test.
Tools: Megger
⚠ Layers of dust can cause diodes to overheat and fail. Brush dust off regularly.
Tools: Ohmmeter
Tools: Wheatstone bridge, Megger
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| Generator load terminals stamped U, V, W (line) and N (neutral); U, V, W correspond with L1, L2, L3 and N with L0 | Stranded load wires bolted to generator reconnection terminal block | Factory-connected to specified voltage; reconnection diagram located on upper side cover of control housing. Line-to-neutral voltage is the lower voltage shown and line-to-line is the higher rating. | ||
| 3 | Customer connections terminal blocks TB3, TB4 (Genset PCB), TB5 (Parallel/Extended I/O PCB), TB8 (Base PCB) | Digital connections: <1000 ft (305 m) use 20 gauge stranded copper; 1000-2000 ft (305-610 m) use 18 gauge stranded copper | B+ and Switched B+ fused at 20 amps. Use separate metal conduit from AC power cables. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Cummins/Onan g183g32 has a displacement of 60.2 liters.
The Cummins/Onan g183g32 powers 2 generator set(s), including Cummins/Onan DQKB, Cummins/Onan DQKC.
A commonly reported issue on generators using the Cummins/Onan g183g32 is: Time press sensor low.