| 121 | SPEED SIGNAL LOST | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking. |
| 135 | OIL PRESSURE SENSOR H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | OIL PRESSURE SENSOR L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 143 | PRE-LOW OIL PRES | Engine oil pressure dropped to an unacceptable level. | Warning | Check oil level, lines and filters; replenish if low; if powering critical loads wait until next shutdown period and follow code 415. |
| 144 | COOL SENSOR HIGH | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 145 | COOL SENSOR LOW | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 146 | PRE-HIGH COOL TMP | Engine has begun to overheat (coolant temperature risen to an unacceptable level). | Warning | Reduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151. |
| 151 | HIGH COOLANT TEMP | Engine has overheated (coolant temperature above the shutdown trip point). | Shutdown | Allow engine to cool; check coolant level; check airflow obstructions; check fan belt; check blower fan/remote radiator pumps; reset control and restart. |
| 197 | LOW COOLANT LEVEL | Engine coolant level has fallen below the warning trip point. | Warning | Allow engine to cool; check coolant level and replenish; look for leaks; reset control and restart. |
| 212 | OIL TEMP SENSOR H | Engine oil temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM). |
| 213 | OIL TEMP SENSOR L | Engine oil temperature signal is shorted low. | Warning | Check sender/connectors/wires; check shorts and resistance between P7-22 and P7-26. |
| 234 | OVERSPEED | Engine has exceeded normal operating speed. | Shutdown | Clear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator. |
| 235 | LOW COOLANT LEVEL | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level and replenish; look for leaks; reset control and restart. |
| 359 | FAIL TO START | Engine cranks but fails to start (possible fuel system problem). | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; replace dirty fuel filter; replace dirty air filter; reset control and restart. |
| 415 | LOW OIL PRESSURE | Engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. |
| 421 | OIL TEMP | Engine has begun to overheat (oil temperature above unacceptable level) (Optional). | Warning | Reduce load; check air inlets/outlets; if engine can be stopped follow code 151 and check engine oil level. |
| 441 | LOW BAT VOLTAGE | Battery voltage supply to the control approaching a low level. | Warning | Check battery charger fuse; recharge or replace battery; clean and tighten cable connections; check engine DC alternator. |
| 442 | HIGH BAT VOLTAGE | Battery voltage supply approaching a high level at which control damage can occur. | Warning | Check float level on battery charger; check battery wiring/calibration. |
| 1122 | Rated/Idle Trans | | Info | |
| 1123 | SHUTDOWN AFTER BS | A shutdown fault occurred while Battle Short was enabled and transitioned from enabled to disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | DELAYED SHUTDOWN | A shutdown fault became active while the Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | BATTLE SHORT ACTIVE | Control is in Battle Short mode (bypasses several critical fault shutdowns). | Warning | None; used for genset operation during emergencies. |
| 1311 | Customer Input #1 | | Warning | Optional customer selection (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Programmable: enable/disable, status/warning/shutdown, active closed or open, and display name. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. |
| 1312 | Customer Input #2 | | Warning | Optional customer selection; programmable (enable/disable, status/warning/shutdown, active open/closed, display name). Default #2 thru #4 - Warning. |
| 1317 | Customer Input #3 | | Warning | Optional customer selection; programmable (default #3 - Low Fuel). |
| 1318 | Customer Input #4 | | Warning | Optional customer selection; programmable (default #4 - Rupture Basin Fault). |
| 1334 | CRIT SCALER OR | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | NONCRIT SCALER OR | Incorrect feature or calibration was entered into control. | Warning | Reload correct feature/calibration file. |
| 1337 | No Message | | Info | |
| 1416 | FAIL TO SHUTDOWN | Genset continues to run after receiving shutdown command (Battle Short feature enabled). | Warning | Check Battle Short feature setting. |
| 1417 | POWER DOWN ERROR | Controller cannot power down because of an unknown condition. | Warning | Check for possible battery drain. |
| 1433 | EMERGENCY STOP | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | REMOTE E-STOP | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | LOW COOLANT TEMP | Engine coolant heater is not operating or not circulating coolant (coolant <=70 F [21 C]). | Warning | Check coolant heater power/fuse/cord; check coolant level; check heater element (10 to 60 ohms); check sensor. |
| 1438 | FAIL TO CRANK | Engine failed to crank after the PCC received a start signal. | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 1442 | WEAK BATTERY | During cranking battery voltage at or below weak battery trip point. | Warning | Recharge or replace battery; check electrolyte level and connections; check harness. |
| 1443 | BATTERY FAILED | Dead battery - engine will not start. | Shutdown | See code 1438 instructions. |
| 1444 | KW OVERLOAD | Generator output power exceeded 105% of genset rating (3 sec at 110% of rated). | Warning | Check load and load lead connections; check CTs and CT connections. |
| 1445 | SHORT CIRCUIT | Generator output current exceeded 175% of rated. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 1446 | HIGH AC VOLTAGE | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | LOW AC VOLTAGE | Phase voltage dropped below 85% of nominal for 10 seconds. | Shutdown | Check load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections. |
| 1448 | UNDER FREQUENCY | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load; check P8 connections. |
| 1449 | OVER FREQUENCY | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery problem; repair P7/P8 connections. |
| 1452 | GEN CB NOT CLOSE | Genset circuit breaker (S2) failed to close when PTC enabled. | Warning | Refer to Section 5. |
| 1453 | GEN CB NOT OPEN | Genset circuit breaker (S2) failed to open when PTC enabled. | Warning | Refer to Section 5. |
| 1459 | REVERSE POWER | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 1461 | LOSS OF FIELD | Loss of field (electric) due to reverse kVAR. | Shutdown | Check field circuit. |
| 1466 | MODEM FAILURE | Control cannot communicate with the modem. | Warning | Check for open, short circuit to ground, and loose connections to the modem. |
| 1468 | NETWORK ERROR | Momentary loss of communication from the LonWorks Network. | Warning | Refer to the LonWorks Network publications. |
| 1469 | SPEED/HZ MATCH | Measured speed and measured AC output frequency do not agree. | Shutdown | Check calibration file. |
| 1471 | OVER CURRENT | Generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 1472 | OVER CURRENT | Generator output current exceeded 110% of rated; time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 2327 | PTC FAULT | PTC module or communication link not working properly when PTC enabled. | Warning | Check blinking light on PTC module; check B+ TB3-3 to TB3-4; check PTC status voltage TB3-5 to TB3-6 (~0.2 VDC); repower control. |
| 2329 | LOW S1 FREQUENCY | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | LOW S1 VOLTAGE | Low utility (S1) voltage. | Warning | Repower PCC 2100 control to clear; check S1 AC inputs at TB5; check S1 pickup/dropout set points. |
| 2335 | EXCITATION FAULT | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Check field wiring (X1 and X2) for shorts or opens. |
| 2336 | MEMORY ERROR | Control memory error; data corruption of critical operating parameters. | Shutdown | Try reloading calibration file. |
| 2337 | PWR TRAN DISABLED | PTC module available but PTC feature not enabled. | Warning | Use InPower to enable PTC feature; cycle power off for 5 seconds then repower. |
| 2338 | PWR TRAN FAILURE | PTC module trim enabled but control could not communicate with PTC module. | Warning | Check blinking light and B+ TB3-3 to TB3-4; check connections between TB2 and TB3; cycle power. |
| 2339 | PWR DOWN ENABLED | Power Down (sleep) function enabled but PTC module or network board is active. | Warning | None required. |
| 2341 | HIGH CONTROL TEMP | Control temperature above normal (158 F [70 C]) for time greater than set time. | Warning | Check genset room air flow. |
| 2342 | TOO LONG IN IDLE | Genset has been in Idle mode too long. | Warning | Exit idle mode. |
| 2358 | HIGH S1 VOLTAGE | Utility (S1) voltage increased above over voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check utility nominal voltage; check sensor set points. |
| 2396 | S1 CB NOT CLOSE | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5. |
| 2397 | S1 CB NOT OPEN | Utility contact (S1) failed to open with PTC enabled. | Warning | Refer to Section 5. |
| 2966 | PTC TIMEOUT | PTC module is not responding; no longer communicating (PTC status may be okay). | Warning | Check PTC status light; check cable connections between PTC module and control; cycle power. |
| 2967 | GOVERNOR FAULT | Governor hardware drive circuitry contains a fault condition. | Warning | Check governor hardware drive circuitry. |
| 2968 | AVR FAULT | AVR hardware contains a fault condition. | Warning | Check AVR hardware. |
| 2969 | LON FAILURE | No communications with LonWorks board. | Warning | Check communications with LonWorks board. |
| 2971 | No message (PTC Test Mode Active) | PTC Test Mode active. | Info | None required. |
| 2972 | FIELD OVERLOAD | AVR Field has been at Max Field for a time greater than the allowed Max Field Time. | Shutdown | Check field load. |