The Cummins/Onan C550D5e is an engine. It powers generator sets from Cummins/Onan, including the C550.
Also known as: Cummins C550D5e
How to read your Cummins/Onan engine serial & model number →
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Exhaust pipe clearance to combustible wall or partition | 305 | mm | |
| Clearance | Fuel lines - minimum clearance from electrical wiring | 12.7 | mm | |
| Clearance | Fuel lines - minimum clearance from hot exhaust parts | 51 | mm | |
| Clearance | Minimum clearance of fuel lines from electrical wiring | 12.7 | mm (1/2 inch) | |
| Clearance | Minimum clearance of fuel lines from hot exhaust parts | 51 | mm (2 inch) | |
| Clearance | Service/maintenance access clearance around generator set | 1 | meter | |
| Other | Exhaust flow at rated load | 2900 | cfm (1370 L/s) | 1500 RPM |
| Other | Exhaust flow at rated load | 3200 | cfm (1510 L/s) | 1800 RPM |
| Other | Exhaust outlet size | 4 | in. NPD | |
| Other | Mounting bolt size securing bedframe to base | 16 | mm | |
| Pressure | Max allowable exhaust back pressure | 76 | mmHg (3 in.) | |
| Pressure | Max fuel inlet restriction | 5 | in. Hg (127 mmHg) | |
| Pressure | Max fuel return restriction | 6.5 | in. Hg (165 mmHg) | |
| Speed | Engine speed - C400 D5e / C450 D5e / C500 D5e / C550 D5e | 1500 | RPM | |
| Speed | Engine speed - C450 D6e / C500 D6e | 1800 | RPM | |
| Temperature | Exhaust temperature | 909 | °F (488°C) | 1800 RPM |
| Temperature | Exhaust temperature | 960 | °F (515°C) | 1500 RPM |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel fuel specified to ASTM No. 2 or BS EN 590:2000, Automotive fuels | ASTM No. 2 / BS EN 590:2000 | An electric solenoid valve in the supply line is recommended for all installations and required for indoor automatic or remote starting installations. Never use galvanized or copper fuel lines, fittings or fuel tanks. | ||
| Fuel | diesel | ASTM No. 2 or BS EN 590:2000 | Cummins engines normally use a diesel fuel specified to ASTM No. 2 or BS EN 590:2000; alternate diesel fuels within the specifications shown in the Generator Set Operator Manual (0908-0219) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Accidental starting of the generator set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative (–) cable from the battery terminal.
⚠ Improper wiring can cause a fire or electrical hazard.
⚠ Backfeed to utility system can cause electrocution or property damage. Do not connect to any building electrical system except through an approved device.
⚠ Ignition of explosive battery gases can cause severe personal injury or death. Always connect negative (–) battery cable last to prevent arcing.
⚠ Ventilate battery area before working on or near battery.
⚠ The coolant heater must not be operated while the cooling system is empty or damage to the heater will occur.
⚠ Hazardous voltage! Ensure all power is off before performing control wire installation.
⚠ Always run control circuit wiring in separate metal conduit from AC power cables.
Tools: cable ties, flexible conduit
⚠ Water or moisture inside a generator increases the possibility of flashing and electrical shock. Do not use a generator which is not dry inside and out.
⚠ Bonding and grounding must be done properly. All metallic parts that could become energized under abnormal conditions must be properly grounded.
⚠ The use of unapproved isolators may result in harmful resonances and may void the generator set warranty.
Tools: anchored mounting bolts, flat washer, hexagonal nut, 38mm x 152mm pipe
⚠ Do not lift the generator set by attaching to the engine or alternator lifting points.
⚠ Before lifting/transportation of the generator set ensure the fuel tank is empty.
⚠ Never stand underneath a lifted generator set.
Tools: shackles, chains, spreader bars, crane/hoist, ropes
⚠ Do not attempt to lift a generator set with an undersized forklift truck.
⚠ Transportation and handling by forklift trucks must only be undertaken by suitably trained and experienced personnel.
Tools: forklift truck
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| U, V, W, N terminals (U,V,W = L1,L2,L3; N = L0) | Stranded load wires bolted to generator reconnection terminal block or circuit breaker lugs | Generators can be configured to the nameplate voltages as shown on the Reconnection Diagram decal attached to the backside of the control box cover; many voltages require reconfiguration of the generator output leads. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Cummins/Onan C550D5e powers 1 generator set(s), including Cummins/Onan C550.