| 101 | IDLE MODE | Indicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM. | Warning | Remove ground from the engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Pull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If powering critical loads, wait until next shutdown period and follow 201-SHUTDOWN procedure; check oil pressure via menu prior to clearing fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3. |
| 204 | OIL PRESS SENDER | The control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime. | Warning | Reduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature above the shutdown trip point: 223°F (106°C) standby or 215°F (102°C) prime). | Shutdown | Allow engine to cool; check for obstructions to cooling airflow, check fan belt, check coolant mixture, check blower fan and circulation pumps; reset control and restart after correcting problem. |
| 213 | COOLANT SENDER | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only). | Shutdown | Check coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display; isolate per troubleshooting table 4-18. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system; engine will not crank. | Shutdown | Check fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery. |
| 222 | OVERCRANK | Possible fuel system problem; engine stops cranking. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; check/replace dirty fuel filter and air filter; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Inspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated. |
| 224 | FAIL TO SYNCHRONIZE | The generator set has not synchronized to the system bus within the allowable time frame. | | Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay. |
| 226 | FAIL TO CLOSE | Indicates that the paralleling breaker has been given a signal to close, but has not closed properly. | | Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace battery; clean/tighten connections; check engine DC alternator; check battery charger float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Recharge or replace the battery; see 230 LOW DC VOLTAGE. |
| 240 | LOW FUEL-DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform the initial start setup procedure; if shutdown repeats, replace the digital board (A32). |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform the adjustment procedures and save; if the same EEPROM ERROR occurs, perform the calibration procedures; if it still occurs, replace the digital board (A32). |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify values/choices selected and repeat the save operation; if the same EEPROM ERROR message occurs, replace the digital board (A32). |
| 260 | CUSTOMER FAULT 1 | Customer defined input closed to ground; the nature of the fault is an optional customer selection which can be programmed to initiate a shutdown or a warning. Default message is editable. | Warning | Isolate the source of the false signal; disconnect the signal lead near the control and reset; if the message drops out there is a short to ground in the external wiring; if it remains replace A34. Customer fault messages are editable. |
| 261 | GROUND FAULT | Customer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable. | Warning | Isolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated. |
| 262 | RUPTURE BASIN / DAY TANK | Customer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable. | Warning | Isolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated. |
| 263 | HIGH GEN TEMP | Customer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable. | Warning | Isolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated. |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Using a phase rotation checker, verify that the generator set phase rotation matches the system bus; verify control wiring to the bus PT module is properly connected. |
| 272 | FIRST START | The PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Control reverts to fallback mode; verify the Master First Start Sensor is functioning and that the voltage pulse is present at the PowerCommand control (terminal TB1-50); check interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages has exceeded 130% of nominal, or has exceeded 110% of nominal for 10 seconds. | Shutdown | Set the display to GEN VOLTS L-N and observe; determine if the output voltage the control sees is low or high; isolate to the PCC, alternator, PT/CT module (A36), customer interface board (A34), analog board (A33) or digital board (A32). |
| 303 | LOW AC VOLTAGE | One or more of the phase voltages has dropped below 85% of nominal for 10 seconds. | Shutdown | Check and repair the PMG or field wiring; check rotating rectifier diodes; check the load and correct any overload; check connectors J8 and J9 on A36, J3 and J5 on A34, and J7 on A37; isolate to A33, A32, A37 or A31. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Check fuel supply, intake air supply and load; isolate governor output module (A38), A32 or A31. |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 330 | OVERLOAD | Three-phase power output exceeds 105% of standby (or 115% of prime) rating. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates that power is flowing into the generator set rather than out from the unit. | Shutdown | Verify connection of generator set CT's; verify proper connection of load sharing lines; verify correct frequency and voltage on all sets. |
| 337 | LOSS OF EXCITATION | Indicates that the alternator excitation system is improperly adjusted or has failed. | Shutdown | Check output voltage with calibrated meter and adjust; check load sharing lines; see Section 6 Servicing the Generator. |
| BASIN | Day tank BASIN lamp | Fuel has overflowed into the rupture basin, indicating possible failure of pump-off and hi-fuel float switches or a leak in the day tank | Warning | RESET the control after fuel in the basin is safely disposed of and cause of overflow corrected |
| BLANK | Blank lamp | For customer use | | |
| F1 | ECM fuse F1 | Starter solenoid circuit, 20 amps | | Replace with a fuse of the same type and amp rating |
| F2 | ECM fuse F2 | Fuel solenoid (switched B+) circuits, 20 amps | | Replace with a fuse of the same type and amp rating |
| F3 | ECM fuse F3 | Continuous B+ out to remote circuits, 15 amps | | Replace with a fuse of the same type and amp rating |
| F4 | ECM fuse F4 | ECM circuits, 5 amps | | Replace with a fuse of the same type and amp rating |
| F5 | ECM fuse F5 | Engine gauge circuits, 5 amps | | Replace with a fuse of the same type and amp rating |
| Fault 1 (Red) | Fault 1 (Detector-12) | Engine shut down because of a system fault; part of a 10 second time delay shutdown circuit (customer connections) | Shutdown | Service as required; selection jumpers may choose warning only or non-timed shutdown |
| Fault 2 (Red) | Fault 2 (Detector-12) | Engine shut down because of a system fault; part of a non-time delay shutdown circuit (customer connections) | Shutdown | Service as required; selection jumpers may choose warning only or 10 second time delay shutdown |
| HI FUEL | Day tank HI FUEL lamp | Fuel in the day tank has reached an abnormally high level, indicating possible failure of the pump-off float switch | Warning | High-fuel float switch takes over as automatic pump-off switch; reset when level drops to normal |
| High Engine Temperature (Red) | High Engine Temperature shutdown | Engine shut down because of excessively high engine coolant temperature (greater than 230 F) | Shutdown | Reset ECM; fill coolant as necessary and repair all leaks |
| LO FUEL | Day tank LO FUEL lamp | Fuel in the day tank has dropped to an abnormally low level, indicating possible failure of the pump-on float switch | Warning | Lo-fuel float switch takes over as automatic pump-on switch; reset when level rises to normal |
| LO SHUTDOWN | Day tank LO SHUTDOWN lamp | Fuel has dropped to a level near the bottom of the tank (empty main tank, pump failure, or float switch failure) | Shutdown | Check and fill main fuel tank; RESET both pump control and engine control |
| Low Engine Temperature (Yellow) | Low Engine Temperature (Detector-12) | Engine temperature is less than 70 F; possibility the engine might not start | Warning | Plug in, repair or install engine coolant and engine oil heaters |
| Low Fuel (Yellow) | Low Fuel (Detector-12) | Fuel level in the supply tank has dropped below reserve necessary for full load | Warning | Fill the main fuel supply tank with the appropriate grade of fuel |
| Low Oil Pressure (Red) | Low Oil Pressure shutdown | Engine shut down because of excessively low engine oil pressure (less than 14 psi) | Shutdown | Reset ECM (Stop then Reset); fill engine oil as necessary and repair all oil leaks |
| Overcrank (Red) | Overcrank shutdown | Engine shut down because it did not start during the timed cranking period (approximately 75 seconds, including two rest periods) | Shutdown | Reset control (Stop then Reset), then push Run or Remote |
| Overspeed (Red) | Overspeed shutdown | Engine shut down because of overspeed | Shutdown | Adjust cutout speed or replace overspeed module/switch; check governor and speed pickup |
| Pre High Engine Temperature (Yellow) | Pre High Engine Temperature | Engine coolant temperature is abnormally high (greater than 220 F) | Warning | Shut down the set if possible or disconnect non-critical loads; service engine cooling system |
| Pre Low Oil Pressure (Yellow) | Pre Low Oil Pressure | Engine oil pressure is abnormally low (less than 20 psi) | Warning | Shut down the set if possible or disconnect non-critical loads; service the engine lubricating system |
| Run (Green) | Run lamp | Generator set is running and the starter has been disconnected | Info | |
| Switch-off (Flashing Red) | Switch-off (Detector-12) | Run/Stop/Remote switch is in the Stop position, preventing remote automatic operation | Info | Push the Run-Stop-Remote switch to Run or Remote |