HomeEnginesCummins/Onan 6CT8.3G

Cummins/Onan 6CT8.3G Engine

The Cummins/Onan 6CT8.3G is an engine. It powers generator sets from Cummins/Onan, including the DGEA. It holds 19 L (5.0 gal) of oil and 26 L (6.9 gal) of coolant.

Also known as: Cummins 6CT8.3G

19.0 L
Oil capacity

Engine specifications

Oil capacity19.0 L
Coolant capacity26.0 L

Common problems

15
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.
    Fix: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
  • SWITCH OFF lamp flashes.
    Fix: Indicates Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used. Move the Run/Stop/Remote switch to the Remote position for automatic starting.
  • PRE LO OIL PRES lamp lights. Engine continues to operate.
    Cause: Indicates engine has overheated (engine temperature has risen above 222°F/106°C) or coolant level is low (sets with coolant level sensor).
  • PRE HI ENGINE TEMP lamp lights. Engine continues to operate.
    Cause: Indicates engine has begun to overheat and engine temperature has risen to approximately 215°F (102°C).
    Fix: If generator is powering non-critical and critical loads and cannot be shut down, use the following: a. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow.
  • OVERCRANK lamp lights and engine stops cranking.
    Fix: A. Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required. b. Check for dirty fuel filter and replace if necessary (see Maintenance section). c. Check for dirty or plugged air filter and replace if necessary (see Maintenance section). d. Reset the control and restart after correcting the problem. Contact an authorized service center for service if none of the above.
  • No AC output voltage.
    Fix: Field breaker is tripped. Reset breaker. Contact an authorized service center if voltage buildup causes breaker to trip.
  • LO OIL PRES lamp lights. Engine shuts down.
    Fix: Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Contact an authorized service center if oil pressure is not in the range of 25 to 40 psi (172 to 275 kPa).
  • LO FUEL LAMP lights. Engine shuts down and LO OIL PRES lamp lights.
    Fix: Indicates engine has run out of fuel. Check fuel level and replenish as required.
  • LO FUEL lamp lights. Engine continues to run.
    Fix: Indicates diesel fuel supply is running low. Check fuel supply and replenish as required.
  • LO ENG TEMP lamp lights. Set is in standby mode but is not operating.
    Fix: A. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required. c. Contact an authorized service center for service if none of the above.
  • Green RUN lamp does not light following engine startup.
    Fix: Indicates possible Start/Disconnect relay failure. Contact an authorized service center for assistance.
  • Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits.
    Fix: The monitor board or a sensor may be at fault. Contact an authorized service center for service.
  • Engine will not crank.
    Fix: A. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Discharged or defective battery. Recharge or replace the battery. d. Emergency stop button (if equipped) pushed in. To reset, pull switch out and move Run/Stop/Remote switch to Stop position. Then push test switch to Reset/Lamp position. e. Contact an authorized service center if none of the above.
  • Engine starts from generator control panel but will not start automatically or from a remote panel.
    Fix: Remote circuit breaker is tripped. Reset breaker and restart. Contact an authorized service center if breaker trips after resetting.
  • Engine runs and then shuts down, OVERSPEED lamp lights.
    Fix: Indicates engine has exceeded normal operating speed. Contact an authorized service center for service.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan 6CT8.3G.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter250 hr
Fuel filter100 hr
Oil filterLS1174s250 hr Amazon eBay
BatteryB-4550 hr Amazon eBay $39.64 KuduParts $135.00
Belt300 hr
Coolant100 hr
Oil500 hr
Spark plug1000 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Check Coolant LevelCheck8 hrDaily
Check Fuel LevelCheck8 hrDaily
Check Oil LevelCheck8 hrDaily
Coolant HeaterCheck8 hrVerify hot coolant is being discharged from the outlet hose.
Coolant LevelCheck8 hr
Drain Water from Fuel FilterDrain8 hrDaily; drain 1 cup or more of fuel to remove water and sediment.
Exhaust Condensate TrapDrain8 hr
Fuel Filter(s)Drain8 hrDrain 1 cup or more of fuel to remove water and sediment. Refer to engine operation and maintenance manual for procedure.
Fuel LevelCheck8 hr
Fuel Tanks (water and sediment)Drain8 hrDrain 1 cup or more of fuel to remove water and sediment.
Inspect GensetCheck8 hrCheck for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair any leaks immediately.
Inspect SetInspect8 hrDaily; check for oil, fuel, cooling, and exhaust system leaks.
Oil LevelCheck8 hrKeep oil level near the dipstick high mark without overfilling.
Air CleanerClean50 hrClean if required. Perform more often in dusty conditions.
Battery Charging SystemCheck50 hr
Charge Air PipingCheck50 hr
Check Anti-freeze and DCA ConcentrationCheck50 hrWeekly
Check Battery Charging SystemCheck50 hrWeekly
Check Battery Level and Specific GravityCheck50 hrWeekly
Check Coolant HeaterCheck50 hrWeekly
Check Drive Belt TensionCheck50 hrWeekly; visually check belts for evidence of slippage.
Check Generator Air OutletCheck50 hrWeekly
Crankcase OilDrain50 hrFirst service — Break-in: drain and replace the crankcase oil after the first 50 hours of operation on new generator sets.
Crankcase oilChange50 hrFirst service — Drain and replace after first 50 hours of operation on new generator sets.
Drain Exhaust Condensate TrapDrain50 hrWeekly
Drain Water and Sediment from Fuel TanksDrain50 hrWeekly; drain 1 cup or more.
Starting BatteriesCheck50 hr
Check Air Cleaner (clean if required)Check100 hrMonthly; clean if required; perform more often in extremely dusty conditions.
Clean Generator AssemblyClean100 hrMonthly
Anti-freeze and DCA ConcentrationCheck250 hr3 moRefer to engine operation and maintenance manual.
Crankcase Oil and FilterChange250 hr3 moIf genset is used for prime power applications, change oil and filter every 3 months or 250 hours. If used for standby applications, change oil every 12 months or 250 hours, whichever comes first.
Drive Belt TensionCheck250 hr3 moVisually check belt for evidence of wear or slippage. Replace if hard or brittle. Refer to engine operation and maintenance manual.
Fuel FiltersChange250 hr3 moRefer to engine operation and maintenance manual.
Governor AdjustmentCheck250 hr3 mo
Radiator Hoses for Wear & CracksCheck250 hr3 mo
Air Cleaner ElementChange500 hrPerform more often in dusty conditions. Replace yearly or sooner if service indicator button pops up.
Change Air Cleaner ElementChange500 hr6 moPerform more often in extremely dusty conditions.
Change Crankcase Oil and FilterChange500 hr6 moPerform more often in extremely dusty conditions.
Change Fuel FiltersChange500 hr6 mo
Check Governor AdjustmentCheck500 hr6 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceFloat switch lift below C-clip stop1/8inch (3 mm)
ClearanceOverspeed switch magnet-to-fly arm air gap (minimum)0.005inches (0.13 mm)
GapMechanical overspeed switch air gap between magnet and fly arm (replace switch if less)0.005inches (0.13 mm)
OtherAVR DROOP preset at factoryfive percent droop at full load and zero power factor
OtherBattery electrolyte corrected specific gravity (fully charged)1.260electrolyte temperature corrected
OtherBattery recharge threshold specific gravity1.215
OtherBattery specific gravity1.260at 77°F (25°C)
OtherBattery specific gravity temperature correctionfour gravity points (0.004) for every ten degrees above 80 F (27 C)
OtherBattery specific gravity, fully chargedapproximately 1.260at 80°F (27°C)
OtherCoolant level50mmbelow radiator cap opening
OtherCycle crank crank and rest time7 to 20seconds
OtherCycle crank number of cycles3, 4, or 5
OtherCycle cranking (12-lamp control)3 cycles of 15 seconds
OtherECM fuse F1 (starter solenoid circuit)20amps
OtherECM fuse F2 (fuel solenoid circuit)20amps
OtherECM fuse F3 (continuous B+ to remote circuits)15amps
OtherECM fuse F4 (ECM circuits)5amps
OtherECM fuse F5 (engine gauge circuits)5amps
OtherFrequency adjustment range±5%%genset running
OtherFuse A31-F1 (control B+)5AmpEngine Interface board
OtherFuse A31-F3 (auxiliary B+)5AmpEngine Interface board; panel lights, run and start relays
OtherFuse A38-F1 (Network B+)10AmpGovernor Output Module
OtherFuse A38-F2 (Switched B+)10AmpGovernor Output Module
OtherFuse A38-F3 (Governor B+)10AmpGovernor Output Module
OtherFuse TB-Bat F1 (Customer B+)20AmpEngine Harness Assembly
OtherGOV RAMP adjustment range0 through 10seconds
OtherGovernor droop adjustment rangewithin 5percent of nominal frequency (3 Hz for 60Hz sets, 2.5 Hz for 50Hz sets)
OtherLow oil pressure / high engine temperature fault time delayabout 10secondsfollowing starter disconnect and inhibited during cranking
OtherOvercrank limit (Sentinel)60seconds
OtherOvercrank option limit (Detector)75seconds
OtherOvercrank time limit75seconds
OtherOverspeed warning range 60 Hz sets2000 to 2200RPM
OtherREG VHZ adjustment range1 through 50 (normal range 7 through 21)
OtherRandom voltage variation±1%for constant loads
OtherResponse jumper setting - 90 to 550 kWB to C
OtherResponse jumper setting - over 550 kWA to B
OtherResponse jumper setting - under 90 kWA to C
OtherSetup/calibration menu access code574
OtherStandard cycle cranking (Detector)three 15-second cranking cycles with two 15-second rest periods
OtherStart delay adjustment range0 to 300secondsremote starting in Auto mode
OtherStarter disconnect speed450 to 570RPM
OtherStop delay adjustment range0 to 600secondsremote stopping in Auto mode
OtherTrailer brake shoe adjustment back-off10clicks
OtherTrailer surge brake actuator stroke length (service brakes if exceeds)1inch (25 mm)
OtherUnder-frequency roll-off (UFRO) threshold, 50 Hz applications49Hz
OtherUnder-frequency roll-off (UFRO) threshold, 60 Hz applications59Hz
OtherVoltage adjustment range±5%%genset running
OtherVoltage regulation±2%from no load to full load
PressureEngine oil pressure (normal)30 to 65psi (207 to 449 kPa)at normal operating temperature
PressureEngine oil pressure range (low oil pressure troubleshooting)25 to 65psi (172 to 449 kPa)
PressureFuel shutoff valve rating (TB1-8 and TB1-5)not more than 0.5amps120 or 240 VAC
PressureIdle oil pressure10 - 30psi (69 - 207 kPa)idle
PressureIdle oil pressure10-30psi (69-207 kPa)idle
PressureIdle oil pressure (normal)10-30psi (69-207 kPa)Engine model 6C, idle
PressureIdle oil pressure shutdown limit8psi (55 kPa)idle
PressureIdle oil pressure warning limit12psi (83 kPa)idle
PressureLow Oil Pressure shutdown threshold14psi (97 kPa)
PressureLow Oil Pressure shutdown threshold (less than)14psi
PressureLow oil pressure cutout switch test threshold (service lubricating system if less)10psiwhile cranking
PressureLow oil pressure shutdown14psi

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water/E.G./DCA mixtureInstallation review checklist item: cooling system must be filled with soft water/E.G./DCA mixture.
Coolant50/50 mix of water and antifreezeBalanced coolant mixture of water, antifreeze and coolant additivesDrain and replace the mixture every 6 months or after 500 hours of operation. Do not add cold coolant to a hot engine; allow engine to cool below 120 F (50 C) before adding coolant.
Engine oilRefer to the Cummins engine Operation and Maintenance Manual for lubricating oil classification/recommendations/specificationsGensets are shipped with oil added.
Engine oilSAE 5W syntheticAPI CC/CD; sulphated ash max 1.85%; pour point 9°F (5°C) below lowest expected temperature; viscosity max 10,000 mPa·s at -31°F (-35°C) and min 4.1 mm²/s at 212°F (100°C)below -23°CFor ambient consistently below -10°F (-23°C) and no engine warm-up provision
Engine oil10W-30API CC/CD-23°C to -10°CFor ambient -10°F (-23°C) to 14°F (-10°C)
Engine oil15W-40API CC/CDabove -10°CFor ambient 14°F (-10°C) and above
Engine oil20W-40API CC/CDabove 0°CFor ambient 32°F (0°C) and above
FuelNo. 2 dieselEngine primarily designed for No. 2 diesel; No. 1 fuel or similar acceptable if meets specifications
FueldieselDo not use zinc coated or copper fuel lines with diesel fuel.
Hydraulic oilDOT-3Trailer master cylinder reservoir - keep at least half full

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

62
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM.WarningRemove ground from the engine idle input to return to normal speed and voltage.
102EMERGENCY STOPIndicates local or remote Emergency Stop.ShutdownPull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf powering critical loads, wait until next shutdown period and follow 201-SHUTDOWN procedure; check oil pressure via menu prior to clearing fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3.
204OIL PRESS SENDERThe control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant.WarningIndicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime.WarningReduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped.
212HIGH COOLANT TEMPIndicates engine has overheated (coolant temperature above the shutdown trip point: 223°F (106°C) standby or 215°F (102°C) prime).ShutdownAllow engine to cool; check for obstructions to cooling airflow, check fan belt, check coolant mixture, check blower fan and circulation pumps; reset control and restart after correcting problem.
213COOLANT SENDERResistance of the coolant temperature sender is out of range.WarningCheck the resistance of the sender; should be 500 to 2k ohms.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningCheck coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only).ShutdownCheck coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode.
220MAG PICKUPMag pickup speed indication is not being sensed or does not match generator set output frequency.ShutdownRestart and check RPM on the digital display; isolate per troubleshooting table 4-18.
221FAIL TO CRANKPossible fault with control or starting system; engine will not crank.ShutdownCheck fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery.
222OVERCRANKPossible fuel system problem; engine stops cranking.ShutdownCheck for empty fuel tank, fuel leaks, or plugged fuel lines; check/replace dirty fuel filter and air filter; reset and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed (115% ±1% of nominal).ShutdownInspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated.
224FAIL TO SYNCHRONIZEThe generator set has not synchronized to the system bus within the allowable time frame.Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay.
226FAIL TO CLOSEIndicates that the paralleling breaker has been given a signal to close, but has not closed properly.Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace battery; clean/tighten connections; check engine DC alternator; check battery charger float level.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningCheck voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningRecharge or replace the battery; see 230 LOW DC VOLTAGE.
240LOW FUEL-DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
241LOW FUELIndicates fuel supply is running low.WarningCheck fuel supply and replenish as required.
250EEPROM ERRORPCC memory error; data corruption of critical operating parameters.ShutdownPerform the initial start setup procedure; if shutdown repeats, replace the digital board (A32).
251EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningPerform the adjustment procedures and save; if the same EEPROM ERROR occurs, perform the calibration procedures; if it still occurs, replace the digital board (A32).
252EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningVerify values/choices selected and repeat the save operation; if the same EEPROM ERROR message occurs, replace the digital board (A32).
260CUSTOMER FAULT 1Customer defined input closed to ground; the nature of the fault is an optional customer selection which can be programmed to initiate a shutdown or a warning. Default message is editable.WarningIsolate the source of the false signal; disconnect the signal lead near the control and reset; if the message drops out there is a short to ground in the external wiring; if it remains replace A34. Customer fault messages are editable.
261GROUND FAULTCustomer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable.WarningIsolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated.
262RUPTURE BASIN / DAY TANKCustomer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable.WarningIsolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated.
263HIGH GEN TEMPCustomer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable.WarningIsolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated.
270PHASE ROTATIONThe phase relationship between the generator set and the system bus is not matched.ShutdownUsing a phase rotation checker, verify that the generator set phase rotation matches the system bus; verify control wiring to the bus PT module is properly connected.
272FIRST STARTThe PowerCommand control is not receiving a proper signal from the system master first start sensor.WarningControl reverts to fallback mode; verify the Master First Start Sensor is functioning and that the voltage pulse is present at the PowerCommand control (terminal TB1-50); check interconnection wiring.
301HIGH AC VOLTAGEOne or more phase voltages has exceeded 130% of nominal, or has exceeded 110% of nominal for 10 seconds.ShutdownSet the display to GEN VOLTS L-N and observe; determine if the output voltage the control sees is low or high; isolate to the PCC, alternator, PT/CT module (A36), customer interface board (A34), analog board (A33) or digital board (A32).
303LOW AC VOLTAGEOne or more of the phase voltages has dropped below 85% of nominal for 10 seconds.ShutdownCheck and repair the PMG or field wiring; check rotating rectifier diodes; check the load and correct any overload; check connectors J8 and J9 on A36, J3 and J5 on A34, and J7 on A37; isolate to A33, A32, A37 or A31.
313UNDER FREQUENCYIndicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated.ShutdownCheck fuel supply, intake air supply and load; isolate governor output module (A38), A32 or A31.
320OVERCURRENTIndicates that generator output current has exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
321OVERCURRENTIndicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown.ShutdownCheck load and load lead connections.
322SHORT CIRCUITIndicates that generator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
330OVERLOADThree-phase power output exceeds 105% of standby (or 115% of prime) rating.WarningCheck load and load lead connections.
335REVERSE POWERIndicates that power is flowing into the generator set rather than out from the unit.ShutdownVerify connection of generator set CT's; verify proper connection of load sharing lines; verify correct frequency and voltage on all sets.
337LOSS OF EXCITATIONIndicates that the alternator excitation system is improperly adjusted or has failed.ShutdownCheck output voltage with calibrated meter and adjust; check load sharing lines; see Section 6 Servicing the Generator.
BASINDay tank BASIN lampFuel has overflowed into the rupture basin, indicating possible failure of pump-off and hi-fuel float switches or a leak in the day tankWarningRESET the control after fuel in the basin is safely disposed of and cause of overflow corrected
BLANKBlank lampFor customer use
F1ECM fuse F1Starter solenoid circuit, 20 ampsReplace with a fuse of the same type and amp rating
F2ECM fuse F2Fuel solenoid (switched B+) circuits, 20 ampsReplace with a fuse of the same type and amp rating
F3ECM fuse F3Continuous B+ out to remote circuits, 15 ampsReplace with a fuse of the same type and amp rating
F4ECM fuse F4ECM circuits, 5 ampsReplace with a fuse of the same type and amp rating
F5ECM fuse F5Engine gauge circuits, 5 ampsReplace with a fuse of the same type and amp rating
Fault 1 (Red)Fault 1 (Detector-12)Engine shut down because of a system fault; part of a 10 second time delay shutdown circuit (customer connections)ShutdownService as required; selection jumpers may choose warning only or non-timed shutdown
Fault 2 (Red)Fault 2 (Detector-12)Engine shut down because of a system fault; part of a non-time delay shutdown circuit (customer connections)ShutdownService as required; selection jumpers may choose warning only or 10 second time delay shutdown
HI FUELDay tank HI FUEL lampFuel in the day tank has reached an abnormally high level, indicating possible failure of the pump-off float switchWarningHigh-fuel float switch takes over as automatic pump-off switch; reset when level drops to normal
High Engine Temperature (Red)High Engine Temperature shutdownEngine shut down because of excessively high engine coolant temperature (greater than 230 F)ShutdownReset ECM; fill coolant as necessary and repair all leaks
LO FUELDay tank LO FUEL lampFuel in the day tank has dropped to an abnormally low level, indicating possible failure of the pump-on float switchWarningLo-fuel float switch takes over as automatic pump-on switch; reset when level rises to normal
LO SHUTDOWNDay tank LO SHUTDOWN lampFuel has dropped to a level near the bottom of the tank (empty main tank, pump failure, or float switch failure)ShutdownCheck and fill main fuel tank; RESET both pump control and engine control
Low Engine Temperature (Yellow)Low Engine Temperature (Detector-12)Engine temperature is less than 70 F; possibility the engine might not startWarningPlug in, repair or install engine coolant and engine oil heaters
Low Fuel (Yellow)Low Fuel (Detector-12)Fuel level in the supply tank has dropped below reserve necessary for full loadWarningFill the main fuel supply tank with the appropriate grade of fuel
Low Oil Pressure (Red)Low Oil Pressure shutdownEngine shut down because of excessively low engine oil pressure (less than 14 psi)ShutdownReset ECM (Stop then Reset); fill engine oil as necessary and repair all oil leaks
Overcrank (Red)Overcrank shutdownEngine shut down because it did not start during the timed cranking period (approximately 75 seconds, including two rest periods)ShutdownReset control (Stop then Reset), then push Run or Remote
Overspeed (Red)Overspeed shutdownEngine shut down because of overspeedShutdownAdjust cutout speed or replace overspeed module/switch; check governor and speed pickup
Pre High Engine Temperature (Yellow)Pre High Engine TemperatureEngine coolant temperature is abnormally high (greater than 220 F)WarningShut down the set if possible or disconnect non-critical loads; service engine cooling system
Pre Low Oil Pressure (Yellow)Pre Low Oil PressureEngine oil pressure is abnormally low (less than 20 psi)WarningShut down the set if possible or disconnect non-critical loads; service the engine lubricating system
Run (Green)Run lampGenerator set is running and the starter has been disconnectedInfo
Switch-off (Flashing Red)Switch-off (Detector-12)Run/Stop/Remote switch is in the Stop position, preventing remote automatic operationInfoPush the Run-Stop-Remote switch to Run or Remote

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Convert Day Tank Controller 240 VAC to 120 VAC adjustment
  1. Remove the two jumpers between terminals TB1-6 and TB1-7.
  2. Connect one jumper between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  3. Move selector switch S103 on the control PCB to the up position for 120V.
  4. If equipped with a transformer, remove jumpers between H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
Day Tank Controller Conversion 240 VAC to 120 VAC adjustment
  1. Remove the two jumpers between terminals TB1-6 and TB1-7 and connect one between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  2. Move selector switch S103 on the control PCB to the up position for 120V.
  3. On the control transformer, remove the two jumpers between terminals H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
Dip Adjustment adjustment
  1. Turn the DIP pot clockwise to increase the voltage vs frequency slope for frequencies below the UFRO threshold.
  2. Greater slope gives greater voltage roll off as frequency drops, easing large load pickup but increasing voltage dip.
  3. Turn the pot fully counterclockwise to make the slope the same above and below the threshold frequency.
Dwell Adjustment adjustment
  1. Turn the DWELL pot clockwise to increase dwell time (voltage recovery time when frequency dips below threshold).
  2. Turn the DWELL pot fully counterclockwise to eliminate dwell.
  3. With no dwell, voltage recovery follows engine speed recovery.
Governor Adjustments (Type A Electric Governor) adjustment
  1. Set selector switch S1 to OFF, S2 to appropriate model position.
  2. Set pots initially: Gain 20%, I 20%, D 30%, Droop 0%.
  3. Start set, adjust Speed pot for required frequency (60Hz=1800RPM or 50Hz=1500RPM) at operating temperature.
  4. Disconnect load, turn Gain pot to 100% or until unstable, then back off until stable.
  5. Adjust D and I pots similarly; readjust Speed if necessary.
  6. Push throttle to minimum speed, release and observe overshoot (2-5 Hz acceptable); adjust I pot to reduce overshoot or hunting.
Initial Start Setup adjustment

⚠ Selecting this menu resets all operating parameters to default values; perform only by technically qualified personnel.

  1. Press RESET, MENU and PHASE SELECT simultaneously to invoke the Initial Start Setup menu.
  2. Toggle the Standby/Prime option.
  3. Select the correct generator set model, frequency and kW rating.
  4. Select the correct nominal line-to-line output voltage.
  5. Select DELTA or WYE.
  6. Select SAVE to save changes; MAIN MENU is then displayed.
Operating PowerCommand in Droop Mode adjustment
  1. Set the no load speed and voltage at the desired level (bus must be de-energized or disconnect Bus PT module).
  2. Apply 100% load and adjust KW load sharing gain for desired full load frequency; adjust KVAR load sharing gain for desired full load voltage.
  3. Repeat the process for other generator sets in the system.
  4. Test the system with all available load and verify approximately equal load sharing at no load and maximum load.
Over / Under Voltage Module Recalibration adjustment
  1. Remove the two screws securing the top to the case and withdraw the top assembly.
  2. Adjust the UNDER setpoint SET pot to 75 percent.
  3. Apply single-phase, 60 Hertz, 104.25 VAC across terminals L and N.
  4. Adjust pot R25 on the PC board until the relay trips (de-energizes).
  5. Adjust the OVER setpoint SET pot to 125 percent.
  6. Apply single-phase, 60 Hertz, 173.75 VAC across terminals L and N.
  7. Adjust pot R26 on the PC board until the relay trips (energizes).
  8. Repeat until no adjustments are necessary, then reassemble the module.
Torque Tester / Current Transformer Installation Check adjustment
  1. Verify the dot on the CT faces toward the generator.
  2. Verify CT21 is on U load leads, CT22 on V load leads, CT23 on W load leads.
  3. Verify the correct CT secondary terminal (pin 2 high voltage / pin 3 low voltage) is used.
  4. Check CT/PT wiring if a 335 Reverse Power shutdown occurs.
UFRO (Under Frequency Roll Off) Adjustment adjustment

⚠ High voltage - use insulating protection

  1. Note the red LED on the board lights when frequency dips below threshold.
  2. Turn the UFRO pot clockwise to raise the threshold frequency.
  3. Turn the UFRO pot counterclockwise to lower the threshold frequency.
  4. Determine threshold frequency by lowering generator frequency until the LED lights.
Voltage and Voltage Stability Adjustments (AVR) adjustment

⚠ High voltage - use dry wooden platform or rubber insulating mat, dry clothing, no jewelry, elbow length insulating gloves

  1. Measure generator output voltage while running without load at nominal frequency.
  2. Lock the control panel voltage trimmer at its midpoint if it cannot provide enough adjustment.
  3. Turn the VOLTS pot fully counterclockwise and the STABILITY pot to its midpoint.
  4. If the red LED lights, refer to Jumper Reconnections and UFRO Adjustments.
  5. Turn the VOLTS pot clockwise until rated voltage is obtained.
  6. If voltage becomes unstable under large load, turn the STABILITY pot clockwise until stable.
  7. Check and readjust the VOLTS pot each time the STABILITY pot is readjusted.
Servicing the PMG diagnostic

⚠ Touching uninsulated high voltage parts can result in severe personal injury or death.

Tools: Wheatstone bridge, digital ohmmeter

  1. Disconnect leads P2, P3, P4 from voltage regulator.
  2. Start engine and let speed stabilize.
  3. Measure voltage across lead pairs P2-P3, P3-P4, P4-P2; should be at least 150 VAC (50Hz) or 180 VAC (60Hz).
  4. Stop set and measure resistance across same lead pairs; each winding approximately 4.4 ohms.
  5. Torque PMG rotor center bolt to 40 ft-lbs (54 Nm) when reassembling; stator leads must be at 12 o'clock.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
AVR response jumperA to CFor generator output 90 kW or less (SX440 and MX321)
Auxiliary terminal board TB21K1, K2, P2, P3, P4, S2, S1, A2, A1A1 and A2 connect a VAR/power factor controller when paralleling with a utility; S1 and S2 connect a droop compensating CT when paralleling with a generator set or utility
Day tank LO SHUTDOWN engine shutdown connectionTB1-14 to engine block ground; TB1-15 to TB2-16 on the ECM
Fault relay K8/K9 (Dry Contact Module)K8=Over Crank, Low Oil Pressure, High Engine Temperature, Low Coolant Level, Low Fuel Level; K9=Low Fuel Level, Rupture BasinContact ratings: 40A max carry/break N.O. 12V coil, 30A N.C. 12V coil, 20A N.O./10A N.C. 24V coil
MX321 PMG-excited jumper positions2-3, 4-5 and 6-7These jumpers must be in these positions
MX321 voltage regulator frequency jumper3-2 for 50 Hz; 3-1 for 60 Hz
SX440 voltage regulator frequency jumperC-50 for 50 Hz; C-60 for 60 Hz
TB3 (ECM alternative RUN/STOP/REMOTE connection)TB3-1=REMOTE, TB3-2=RUN, TB3-3=STOPProvides alternative direct connection to ECM for troubleshooting or customer connection
Voltage trimmer R21voltage regulator terminals 1 and 2There must be a jumper between terminals 1 and 2 when voltage trimmer R21 is not used
single phaseQSG-Series power distribution panel voltage selector switch S1 positionmain output terminalsRotary switch under lockable cover selects 120/240 VAC single phase
single phaseVoltage regulator terminal 6jumpered to terminal 8When the generator is connected for single-phase output, terminal 6 is not connected to the isolation transformer
three phaseQSG-Series power distribution panel voltage selector switch S1 positionmain output terminalsRotary switch selects 120/208 VAC three phase
120single phaseDay tank fuel pump control power reconnectionmove jumpers from TB1-6/TB1-7 to TB1-5/TB1-6 and TB1-7/TB1-8Move selector switch S103 on the control PCB to the up position for 120 V (factory set for 240 V, S103 down)
24Day tank fuel pump control logic power (two lead harness, no transformer)TB1-19 to positive (+) 24 V starter motor solenoid; TB-20 to negative (-)Provides 24 VDC for the control circuit
240single phaseDay tank fuel pump control default factory connectionjumpers between terminals TB1-6 and TB1-7Selector switch S103 on the control PCB in the down position for 240 V

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Cummins/Onan 6CT8.3G?

The Cummins/Onan 6CT8.3G engine has an oil capacity of 19.0 liters.

Which generators use the Cummins/Onan 6CT8.3G engine?

The Cummins/Onan 6CT8.3G powers 1 generator set(s), including Cummins/Onan DGEA.

How often should you change the oil in the Cummins/Onan 6CT8.3G?

The Cummins/Onan 6CT8.3G oil change interval is every 500 hours.

What is a common problem with the Cummins/Onan 6CT8.3G engine?

A commonly reported issue on generators using the Cummins/Onan 6CT8.3G is: The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.. Fix: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay..