| | Remote control connections: a small four place terminal block is mounted in the unhoused plant control box or on the housed plant fuel tank support. Connect one or more remote control switches to this terminal block, connecting switch terminals #1, #2 and #3 to the corresponding terminals marked 1, 2 and 3 on the terminal block. | | If installed within 250 feet of the plant use #18 or #19 wire; use #16 wire up to 500 feet or #14 wire up to 1000 feet. Additional switches must be connected in parallel. |
| 115 or 230 | single phase, 2 wire | Connect the white or grounded load wire to the grounded plant terminal; connect the other (black) load wire to the insulated plant terminal. | | Housed plants: AC output terminals located behind the control panel on the fuel tank support. If the control panel has a receptacle, a load not to exceed 15 amps may be connected to each outlet. |
| 115 or 230 | single phase, 2 wire (unhoused) | Connect the white or grounded load wire to the grounded generator lead marked M2. Connect the other (black) load wire to the generator lead marked M1. | M1, M2 | Generator output leads are within the small outlet box at the rear of the generator. |
| 115/230 | single phase, 3 wire | The center terminal is grounded. For 115 volt current connect the white or grounded load wire to the center terminal and the other load wire to either of the two outside terminals, A or B. For 230 volt current connect the load wires to the two outside insulated terminals A and B, leaving the center terminal unused. | | 2500 watts are available on each 115 volt circuit, ground to A and ground to B. |
| 115/230 | single phase, 3 wire (unhoused) | The generator lead marked M2 is grounded. For 115 volt current connect the white or grounded load wire to the M2 lead and the other (black) load wire to either the M1 or the M3 generator lead. For 230 volt current connect one load wire to the M1 lead and the other load wire to the M3 lead, leaving the M2 lead unused. | M1, M2, M3 | 2500 watts are available on each 115 volt circuit; 5000 watts of 230 volt current are available. |
| 120 single phase / 208 three phase | four wire | The terminal farthest from the generator is grounded. For 120 volt single phase connect the grounded load wire to the grounded terminal and the other load wire to any one of the other three insulated terminals A, B, or C. For 208 volt three phase connect a load wire to each of the three insulated terminals A, B, C, leaving the grounded terminal unused. | | Reversing connections between any two insulated terminals reverses rotation of three phase motors. For 208 volt single phase connect one of the two load wires to each of any two insulated terminals; 1666 watts are available on each single phase circuit. |
| 120 single phase / 208 three phase | four wire (unhoused) | The generator lead marked MO is grounded. For 120 volt single phase connect the white or grounded load wire to the MO lead and the other (black) load wire to any one of the other three generator leads marked M1, M2, or M3. For 208 volt three phase connect the three load wires to generator leads M1, M2, and M3, one load wire to each generator hot lead. | MO, M1, M2, M3 | Not more than one third of the generator capacity is available on each of the three single phase circuits. |
| 220/380 | three phase, 4 wire (unhoused) | The load wires are connected the same as to the preceding 120/208 volt plant. For a 220 volt circuit use the connections for the 120 volt circuit; for a 380 volt circuit use the connections shown for the 208 volt circuit. | | |
| 230 | three phase, 3 wire | No terminal is grounded. Reversing the connections between any two of terminals A, B, or C reverses the direction of rotation of three phase motors. 230 volt single phase current may be obtained by connecting one load wire to each of any two terminals. | | 1666 watts are available on each single phase circuit. |
| 230 | three phase, 3 wire (unhoused) | No generator lead is grounded. For three phase current connect the three load wires to generator leads M1, M2, and M3. For 230 volt single phase current connect a separate load wire to each of any two generator leads. | M1, M2, M3 | Not more than one third of the generator capacity is available on each single phase circuit. |