The CH-74 is an engine rated at 2900 rpm. It powers generator sets from Kohler, including the 6VSG-24V, 6VSG-36V and 6VSG-48V.
Also known as: CH-74
| Rated speed | 2900 rpm |
|---|
Compiled from service & troubleshooting documentation across every generator set that uses the CH-74.
The CH-74 powers 3 generator set(s), including Kohler 6VSG-24V, Kohler 6VSG-36V, Kohler 6VSG-48V.
A commonly reported issue on generators using the CH-74 is: Gas fuel leaks can cause an explosion.. Fix: Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6–8 ounces per square inch (10–14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble..