Allis-Chalmers 6138-LT Engine
The Allis-Chalmers 6138-LT is a 13.8 L 6-cylinder turbocharged engine rated at 1800 rpm, producing up to 276 kW. It powers generator sets from Cummins/Onan, including the 150.0 DYG 15R.
Also known as: Allis-Chalmers 6138-LT
Engine specifications
| Displacement | 13.8 L |
|---|
| Cylinders | 6 |
|---|
| Aspiration | Turbocharged |
|---|
| Rated speed | 1800 rpm |
|---|
| Gross power | 276 kW |
|---|
Generator sets powered by this engine
1
Common problems
9- Fault lamp lights and engine shuts down after running for a period
Cause: Oil level. Engine will shut down if sensor is closed
Fix: Check oil level. - Low oil pressure shutdown
Cause: Oil level
Fix: Check oil level. Replenish if necessary. - Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds
Fix: See engine service manual for troubleshooting fuel system; After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position. - High engine temperature shutdown
Cause: Coolant level
Fix: Check coolant level. Replenish if necessary. - Fault lamp lights, no fault exists
Fix: To check a no-fault condition, disconnect leads from TB11 terminals 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads. - Fault lamp lights immediately after engine starts
Cause: Overspeed condition as engine starts
Fix: Check for overspeed condition as engine starts. - Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds
Fix: See engine service manual for troubleshooting fuel system; After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position. - Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, overcrank light ON
Cause: Fuel supply
Fix: Check fuel supply. - Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lights
Cause: Fuel supply
Fix: Check fuel supply.
Compiled from service & troubleshooting documentation across every generator set that uses the Allis-Chalmers 6138-LT.
Also used in
1- Allis-Chalmers N7 — Combine
Other equipment known to use this engine, via filter-application cross-reference — useful for sourcing parts even when your exact machine isn't listed elsewhere on this page.
Common questions
What is the displacement of the Allis-Chalmers 6138-LT?
The Allis-Chalmers 6138-LT has a displacement of 13.8 liters with 6 cylinders.
Which generators use the Allis-Chalmers 6138-LT engine?
The Allis-Chalmers 6138-LT powers 1 generator set(s), including Cummins/Onan 150.0 DYG 15R.
What is a common problem with the Allis-Chalmers 6138-LT engine?
A commonly reported issue on generators using the Allis-Chalmers 6138-LT is: Fault lamp lights and engine shuts down after running for a period. Cause: Oil level. Engine will shut down if sensor is closed. Fix: Check oil level..