Kohler CH740 4-Cycle Engine Engine
The Kohler CH740 4-Cycle is a 0.72 L -2-cylinder natural gas or lp vapor engine rated at 2300 rpm, producing up to 15.8 kW. It powers generator sets from Kohler, including the 12 RES and 6VSG. It holds 1.9 L (0.5 gal) of oil.
Also known as: Kohler CH740 4-Cycle
Engine specifications
| Oil capacity | 1.9 L |
|---|
| Displacement | 0.725 L |
|---|
| Cylinders | -2 |
|---|
| Aspiration | Natural Gas or LP Vapor |
|---|
| Rated speed | 2300 rpm |
|---|
| Gross power | 15 kW |
|---|
Generator sets powered by this engine
2
Common problems
15- Gas fuel leaks can cause an explosion.
Fix: Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6–8 ounces per square inch (10–14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble. - Undervoltage shutdown UU
Cause: Shutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.
Fix: Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. - Underfrequency shutdown UF
Cause: Shutdown occurs if the governed frequency falls below 54 Hz for more than 5 seconds. Shutdown also occurs if the governed frequency falls below 56.5 Hz for more than 60 seconds. This function becomes active 10 seconds after engine start. (10 second inhibit).
Fix: Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. - The generator set does not crank.
Cause: Battery weak or dead, Battery charger fuse blown, Battery connections reversed or poor, Controller fuse (F3) blown, Relay interface board fuse (F2) blown
Fix: Check power to the battery charger. Recharge or replace the battery. Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. Check the connections. Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. - The generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected. Locked rotor
- Stops suddenly
Cause: Fault shutdown
Fix: Check for a fault shutdown code on the controller’s LED display. Correct the fault and then move the generator set master switch to OFF/RESET to reset the controller. - Stator problem
Fix: Check voltage and continuity. - Shutdown occurs when the governed frequency falls 1 Hz below the system’s frequency setpoint for more than 1 second. UF
Fix: Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. - Shutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 1 second. This protective becomes active 30 seconds after engine start. OF
Fix: Contact an authorized distributor/dealer for service if problem continues. - Shutdown occurs if the voltage falls below 80% of the voltage regulator setpoint for more than 1 second. This protective becomes active 30 seconds after engine start. UU
Fix: Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. - Shutdown occurs if the voltage exceeds 120% of the voltage regulator setpoint for more than 1 second. OU
Fix: Contact an authorized distributor/dealer for service if problem continues. - Shutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 1 second. OS
Fix: Contact an authorized distributor/dealer for service if problem continues. - Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches the crank disconnect speed. HE
Fix: Check for blocked air inlets and exhaust outlets. - Shutdown occurs if a low oil pressure condition exists 7 seconds after the engine has reached crank disconnect speed. LOP
Cause: Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Check for leaks in the lubrication system.
Fix: Check the oil level and add oil if the level is low. - Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest. The generator set also shuts down after 1 crank attempt if no speed signal is sensed. Shuts down 1 second after the fault is detected. OC
Cause: Check the fuel supply, spark plug, and battery. Check for loose connections.
Fix: Contact an authorized distributor/dealer for service if problem continues.
Compiled from service & troubleshooting documentation across every generator set that uses the Kohler CH740 4-Cycle.
Maintenance schedule
| Item | Spec | Capacity | Part # | Interval | |
|---|
| Air filter | Dry | | — | | find |
| Fuel filter | | | — | | find |
| Oil filter | Cartridge | | — | 200 hr | find |
| Belt | | | — | | find |
| Coolant | | | — | | |
| Oil | Full Pressure | 1.9 L (qt.) | — | | |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
Common questions
What is the oil capacity of the Kohler CH740 4-Cycle?
The Kohler CH740 4-Cycle engine has an oil capacity of 1.9 liters.
What is the displacement of the Kohler CH740 4-Cycle?
The Kohler CH740 4-Cycle has a displacement of 0.725 liters with -2 cylinders.
Which generators use the Kohler CH740 4-Cycle engine?
The Kohler CH740 4-Cycle powers 2 generator set(s), including Kohler 12 RES, Kohler 6VSG.
What is a common problem with the Kohler CH740 4-Cycle engine?
A commonly reported issue on generators using the Kohler CH740 4-Cycle is: Gas fuel leaks can cause an explosion.. Fix: Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6–8 ounces per square inch (10–14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble..