| Other | Altitude degradation 4000 ft (1220 m) to 8000 ft (2440 m) | 3.5 | % per 1000 ft (305 m) | |
| Other | Battery electrolyte specific gravity at 100% charge | 1.280 | specific gravity | Corrected to 80°F (27°C) |
| Other | Cold weather starting aid system use | 40 | °F | or below |
| Other | Fuel Level Switch current | 3.0 | amps at 6-32 VDC | |
| Other | Over load indicator trip | 110 | % of rated current | |
| Other | Overload Relay operation | 110 | percent of rated value | load current in any phase |
| Other | Reverse Power Relay operation | 20 | percent of rated value | power flow into generator set |
| Other | Reverse power indicator trip | 20±3 | % of rated current | |
| Other | Short Circuit Relay activation | 425 | percent of rated value | output current in any phase |
| Other | Short circuit indicator trip | 425±25 | % of rated current | |
| Pressure | Auxiliary Fuel Pump delivery pressure | 5.0-6.5 | psi (34.5-65.5 kPa) (max) | |
| Pressure | Auxiliary fuel pump delivery pressure (max) | 5.0-6.5 | psi | |
| Pressure | Low Oil Pressure Switch trip pressure | 15 ±3 | psi (103.4 ±20.7 kPa) | |
| Pressure | Low oil pressure switch trip pressure | 15±3 | psi | |
| Pressure | Normal engine oil operating pressure | 25-60 | psi (172-414 kPa) | Normal operating |
| Pressure | Normal operating oil pressure | 172-414 | kPa | Normal operation |
| Pressure | Normal operating oil pressure | 25-60 | psi | Normal operation |
| Resistance | FREQUENCY adjust potentiometer resistance | 4,500-5,500 | ohms | Across outer terminals |
| Resistance | FUEL LEVEL indicator test resistance (EMPTY) | 216-264 | ohms | Potentiometer adjustment |
| Resistance | FUEL LEVEL indicator test resistance (FULL) | 29.7-36.3 | ohms | Potentiometer adjustment |
| Resistance | LOAD SHARING ADJUST rheostat resistance | 4,500-5,500 | ohms | Full CCW position |
| Resistance | OIL PRESSURE indicator test resistance | 30.15-36.85 | ohms | Potentiometer adjustment |
| Resistance | OIL PRESSURE indicator test resistance | 92.7-113.3 | ohms | Potentiometer adjustment |
| Resistance | REACTIVE CURRENT ADJUST rheostat resistance | 4.5-5.5 | ohms | wires 135B and 142A |
| Resistance | TEMPERATURE indicator test resistance | 117-143 | ohms | Potentiometer adjustment |
| Resistance | TEMPERATURE indicator test resistance | 58.5-71.5 | ohms | Potentiometer adjustment |
| Resistance | VOLTAGE adjust potentiometer total resistance | 10,000 | ohms | part number RV4NAYSD103A installed |
| Resistance | VOLTAGE adjust potentiometer total resistance | 20,000 | ohms | part number RV4NAYSD203A installed |
| Speed | Frequency adjustment range, 400 Hz | 390-420 Hz, not below 370 Hz or above 430 Hz | Hz | 400 Hz operation |
| Speed | Frequency adjustment range, 50 Hz | 48-52 Hz, not below 45 Hz for 50 Hz operation | Hz | 50 Hz operation |
| Speed | Frequency adjustment range, 60 Hz | 58-62 Hz, not above 65 Hz for 60 Hz operation | Hz | 60 Hz operation |
| Speed | Overspeed Switch element trip and reset | 2200 ±40 | rpm | |
| Speed | Overspeed switch element trip and reset | 2200±40 | RPM | |
| Speed | Starter disconnect (crank disconnect) speed | approximately 900 | rpm | |
| Temperature | Coolant High Temperature Switch trip temperature | 220 ±3.5 | °F (104 ±2°C) | |
| Temperature | Coolant high temperature switch trip temperature | 220±3.5 | °F | |
| Temperature | Normal engine coolant operating temperature | 170-200 | °F (77-93°C) | Normal operating |
| Valve clearance | Valve Tappet Clearance Adjustment (Exhaust) | 0.018 | in. (0.45 mm) | Hot or cold |
| Valve clearance | Valve Tappet Clearance Adjustment (Exhaust) | 0.045-0.070 | in. (1.1-1.8 mm) | Hot or cold |
| Valve clearance | Valve Tappet Clearance Adjustment (Intake) | 0.018 | in. (0.45 mm) | Hot or cold |
| Valve clearance | Valve Tappet Clearance Adjustment (Intake) | 0.040-0.055 | in. (1.0-1.4 mm) | Hot or cold |
| Valve clearance | Valve tappet clearance, exhaust (Isuzu C-240) | 0.018 | in | Hot or cold |
| Valve clearance | Valve tappet clearance, exhaust (Yanmar 4TNV84T) | 0.045-0.070 | in | Hot or cold |
| Valve clearance | Valve tappet clearance, intake (Isuzu C-240) | 0.045 | in | Hot or cold |
| Valve clearance | Valve tappet clearance, intake (Yanmar 4TNV84T) | 0.040-0.055 | in | Hot or cold |
| Voltage | BATTERY CHARGE ammeter millivolt reading | 25 | mV equals +10 amps or -10 amps on ammeter | Across ammeter terminals |
| Voltage | Overvoltage Relay trip point | 155 ± 1 | VAC | 120 VAC coil winding; not less than 200 milliseconds |
| Voltage | Overvoltage Relay trip time | No more than 1.25 seconds after trip conditions exist | seconds | |
| Voltage | Overvoltage trip point (120 VAC coil winding) | 155±1 | VAC | for no less than 200 milliseconds |
| Voltage | Pressure indicating system voltage rating | 24 | VDC | |
| Voltage | Temperature indicating system voltage rating | 24 | VDC | |
| Voltage | Undervoltage Relay instantaneous trip | 48 | V | 120 V generator coil winding |
| Voltage | Undervoltage Relay time-delay trip | below 99 | V | 120 V generator coil winding |
| Voltage | Undervoltage indicator trip (120 V coil winding) | 99±4 | VAC | |
| Voltage | Voltage adjustment range, 400 Hz, 120/208 V connection | 197-229 | V | 400 Hz |
| Voltage | Voltage adjustment range, 400 Hz, 240/416 V connection | 395-458 | V | 400 Hz |
| Voltage | Voltage adjustment range, 50 Hz, 120/208 V connection | 190-213 | V | 50 Hz |
| Voltage | Voltage adjustment range, 50 Hz, 240/416 V connection | 380-426 | V | 50 Hz |
| Voltage | Voltage adjustment range, 60 Hz, 120/208 V connection | 197-240 | V | 60 Hz |
| Voltage | Voltage adjustment range, 60 Hz, 240/416 V connection | 395-480 | V | 60 Hz |