| 101 | IDLE MODE | Indicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM. | Warning | Remove ground from the engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only); move Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If powering critical loads, wait until next shutdown period then follow 201-SHUTDOWN procedure. Access Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3. |
| 204 | OIL PRES SENDER | The control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower. | Warning | Check coolant heater power supply, coolant level, and heater element. |
| 211 | HIGH COOLANT TEMP | Indicates coolant temperature is getting close to the recommended maximum limit (202°F / 94°C). | Warning | Reduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped. |
| 212 | HIGH COOLANT TEMP | Indicates the engine has overheated (coolant above 212°F / 100°C). | Shutdown | Allow engine to cool; check cooling airflow, fan belt, coolant mixture, blower fan/circulation pumps; reset control and restart. |
| 213 | COOLANT SENDER | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Check coolant level in radiator and bottle; check coolant bottle hose or radiator cap; reset control and restart. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display; inspect/adjust MPU. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system; engine will not crank. | Shutdown | Check fuse F3 on the Engine Interface board; clean battery cable terminals; recharge or replace battery. |
| 222 | OVERCRANK | Possible fuel system problem; engine stops cranking. | Shutdown | Check supply shutoff valve, propane tank, gas pressure, fuel filter, air filter, and ignition; correct flooded engine; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Check mechanical fuel linkage; monitor PCC duty cycle to isolate A32 or A38. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge/replace battery; check battery charger fuse; clean/tighten battery cable connections; check engine DC alternator (12 to 14 VDC); check float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 16 VDC. | Warning | Check float level on battery charger (lower float level); check engine DC alternator. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds during starting. | Warning | Recharge or replace the battery; see 230 LOW DC VOLTAGE. |
| 240 | LOW FUEL-DAY | Day tank fuel supply is running low. | Warning | Nature of fault is an optional customer selection. |
| 241 | LOW FUEL | Fuel supply is running low. | Warning | Nature of fault is an optional customer selection. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform the initial start setup procedure; if the same EEPROM ERROR occurs replace the digital board (A32). |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform adjustment/calibration procedures and save; if the same EEPROM ERROR occurs replace the digital board (A32). |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify values/choices selected and repeat save; reset, shut off and restart; if the same EEPROM ERROR occurs replace the digital board (A32). |
| 260 | CUSTOMER FAULT 1 | Customer-defined input closed to ground; fault function can be programmed to initiate a shutdown or a warning. | Warning | Isolate the source of the signal; check external wiring for short to ground; replace A34 or A32 as indicated. |
| 261 | GROUND FAULT | Customer-defined input closed to ground; fault function can be programmed to initiate a shutdown or a warning. | Warning | Isolate the source of the signal; check external wiring for short to ground; replace A34 or A32 as indicated. |
| 262 | RUPTURE BASIN | Customer-defined input closed to ground; fault function can be programmed to initiate a shutdown or a warning. | Warning | Isolate the source of the signal; check external wiring for short to ground; replace A34 or A32 as indicated. |
| 263 | HIGH GEN TEMP | Customer-defined input closed to ground; fault function can be programmed to initiate a shutdown or a warning. | Warning | Isolate the source of the signal; check external wiring for short to ground; replace A34 or A32 as indicated. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages has exceeded 130% of nominal, or has exceeded 110% of nominal for 10 seconds. | Shutdown | Troubleshoot PCC, alternator, regulator module A37, PT/CT module A36, customer interface A34 and analog board A33. |
| 303 | LOW AC VOLTAGE | One or more of the phase voltages has dropped below 85% of nominal for 10 seconds. | Shutdown | Check PMG or field wiring, rotating rectifier diodes, overload, and connectors; isolate A37, A31, A32, A36, A34, A33. |
| 313 | UNDER FREQUENCY | Indicates engine speed dropped below 90% of nominal for 10 seconds; five seconds before shutdown a Load Dump signal is initiated. | Shutdown | Check fuel supply, intake air supply and load; isolate governor output module (A38), A32 or A31. |
| 320 | OVERCURRENT | Indicates generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates generator output current exceeded 110% of rated and a PCC time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates generator output current exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 330 | OVERLOAD | Three-phase power output exceeds 105% of standby (or 115% of prime) rating. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates improper CT or PT phasing (non-parallel units only). | Shutdown | Check CT / PT wiring; refer to CT Installation in Section 5. |