Home›Engines›Honda iGX390

Honda iGX390 Engine

The Honda iGX390 is a 0.39 L engine rated at 3600 rpm. It powers generator sets from Honda, including the EB5000, EB6500 and EM5000SX. It holds 1.1 L (0.3 gal) of oil.

Also known as: Honda iGX390

0.389 L
Displacement
3600 rpm
Rated speed
1.1 L
Oil capacity

Engine specifications

Oil capacity1.1 L
Displacement0.389 L
Rated speed3600 rpm

Common problems

8
  • When the engine will hot start
    Fix: 1. Is the engine switch on? 2. Does the oil alert lamp flash when the starter is pulled? 3. Is there enough fuel? 4. Are all loads disconnected from the AC receptacles? 5. Is there a spark at the spark plug? a. Remove the spark plug cap, Clean any dust from around the spark plug base, then remove the spark plug. b. Install the spark plug in the plug cap. c. Turn the engine switch on. d. Grounding the side electrode to any engine ground, pull the recoil starter to see if sparks jump across the gap. e. If any fuel has been spilled, make sure the area is dry before testing the spark plug. Fuel vapor or spilled fuel may ignite. Perform this test in a well-ventilated area. f. If there are no sparks, replace the plug. g. If the new spark plug does not spark, take the generator to an authorized Honda dealer.
  • The engine stops and will not restart.
    Fix: Check the engine oil level (see page 40) before troubleshooting in other areas.
  • Running the engine with persistent spark knock or pinging can cause engine damage.
    Fix: Running the engine with persistent spark knock or pinging is misuse, and the Distributor’s Limited Warranty does not cover parts damaged by misuse.
  • Occasionally you may hear a light ‘‘spark knock’’ or ‘‘pinging’’ (metallic rapping noise) while operating under heavy loads.
    Fix: This is no cause for concern. If spark knock or pinging occurs at a steady engine speed, under normal load, change brands of gasoline. If spark knock or pinging persists, see an authorized Honda generator dealer.
  • Engine speed becomes abnormal.
    Fix: The engine will automatically stop if the engine speed becomes abnormal.
  • Abnormal voltage is detected during generation.
    Fix: The engine will automatically stop during generation when it detects abnormal voltage.
  • When the engine will not start
    Fix: 1. Refill the fuel tank. 2. Is there enough oil in - Add the recommended oil. (The oil alert lamp flashes when cranking the engine.) 3. Is there a spark from the spark plug? To check: 1) Remove the spark plug cap and clean any dirt from around the spark plug. 2) Remove the spark plug and install the spark plug in the plug cap. 3) Set the plug side electrode on the cylinder head. Crank the engine, sparks should jump across the gap. 4. Clean the fuel sediment cup. 5. If the engine still does not start, take the generator to an authorized Honda generator dealer.
  • No electricity at the AC receptacles
    Fix: 1. Turn the AC circuit breaker ON. 2. Check the electrical appliance or equipment for any defects.

Compiled from service & troubleshooting documentation across every generator set that uses the Honda iGX390.

Service intervals

16
ItemActionHoursMonthsNotes
Engine oilChange300 hr12 moFirst service — First month or 20 hrs
Air cleanerClean100 hr6 moService more frequently when used in dusty areas (1)
Sediment cupClean100 hr6 moPage 58
Spark arresterClean300 hr12 moMust be serviced every 100 hours to maintain its efficiency
Spark plugAdjust300 hr12 moReadjust — every 6 months or 100 Hrs
Fuel tank and filterClean300 hr12 mo(2)
Fuel tank and strainerClean300 hr12 mo(2) Every year or 300 Hrs
Spark plugReplace300 hr12 moEvery year or 300 Hrs (page 69)
Valve clearanceAdjust300 hr12 moCheck-adjust every year or 300 Hrs; by servicing dealer (2)
Combustion chamberClean1000 hrAfter every 1,000 hrs
CanisterCheck24 moEvery 2 years (2)
Charge tubeCheck24 moEvery 2 years (2)
Fuel lineReplace24 moEvery 2 years (Replace if necessary)
Fuel tubeCheck24 moEvery 2 years (replace if necessary) (2)
GFCI receptacleTest1 moOnce each month; test before each use if generator is stored outside unprotected
Purge tubeCheck24 moEvery 2 years (2)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceFloat height13.2mm
GapIgnition coil air gap0.2 – 0.6mm
GapSpark plug electrode gap0.028–0.031 in (0.7–0.8 mm)mm
GapSpark plug gap0.028 - 0.031in
GapSpark plug gap0.028-0.031in
GapSpark plug gap0.028–0.031in (0.7–0.8 mm)
GapSpark plug gap0.7 - 0.8mm
GapSpark plug gap0.70 – 0.80mm
GapSpark plug gap0.70-0.80mm
OtherCompression ratio8.2:1
OtherCrank duration3-3-4-5secper automatic attempt sequence
OtherEnclosure dimensions85x58x33mm
OtherLength of cable2m
OtherMax. Standby Current9.8mA @ 12 V
OtherNumber of attempts4automatic starting attempts
OtherPause between each automatic attempt10sec
OtherSpark plug installation (new plug)1/2turn after seating to compress washernew spark plug
OtherSpark plug installation (reused plug)1/8 - 1/4turn after seating to compress washerreinstalling a used spark plug
PressureCylinder compression1.29MPaat 1,400 min-1 (rpm)
PressureCylinder compression1.31MPaat 1,400 min-1 (rpm)
ResistanceCT sensor resistance18 ±2Ω
ResistanceSpark plug cap resistance7.5 – 12.5kΩ
SpeedAuto Throttle idle speed2,300 ± 100min-1 (rpm)
SpeedEngine speed3,600rpm
SpeedEngine speed protection limit (DAVR self-diagnosis)4140rpmabnormal voltage/speed sustained longer than 3 seconds
SpeedMaximum engine speed3,600 ± 100min-1 (rpm)
TemperatureOperating Temperature Range-30 to +70°C
TorqueAir cleaner case bolt5.4N·m
TorqueCarburetor mount nut8.5N·m
TorqueConnecting rod special bolt14N·m
TorqueControl panel mount bolt27N·m
TorqueCrankcase cover bolt24N·m
TorqueCylinder head bolt35N·m
TorqueEngine mount nut34N·m
TorqueExhaust pipe nut24N·m
TorqueFan cover stud bolt23N·m
TorqueFan cover stud bolt mounting nut40N·m
TorqueFlywheel special nut128N·m
TorqueFlywheel special nut170N·m
TorqueFront housing bolt24N·m
TorqueFuel meter screw4N·m
TorqueFuel valve nut23N·m
TorqueGenerator cooling fan screw4.8N·m
TorqueHandle installation17–22 lbf·ft (24–29 N·m, 2.4–3.0 kgf·m)N·m
TorqueHandle installation flange bolts19.5 lbf·ft (26.5 N·m, 2.7 kgf·m)lbf·ft
TorqueHanger kit flange bolts19.5 lbf·ft (26.5 N·m, 2.7 kgf·m)lbf·ft
TorqueHanger kit installation17–22 lbf·ft (24–29 N·m, 2.4–3.0 kgf·m)N·m
TorqueOil drain bolt22.5N·m
TorqueOil drain plug (12×15 mm)16.3 lbf·ft (22.1 N·m, 2.25 kgf·m)lbf·ft
TorqueOil drain plug (12×15 mm)16.6 lbf·ft (22.5 N·m, 2.25 kgf·m)N·m
TorqueRear housing cover bolt9.8N·m
TorqueRocker arm pivot adjusting nut10N·m
TorqueRocker arm pivot special bolt24N·m
TorqueRotor bolt44N·m
TorqueRubber mount nut24N·m
TorqueSpark plug13.0 lbf·ft (17.7 N·m, 1.8 kgf·m)lbf·ft
TorqueSpark plug13.3 lbf·ft (18 N·m, 1.8 kgf·m)N·m
TorqueSpark plug18N·m
TorqueSpark plug tightening (new plug)1/2 turn after the spark plug seatsturnnew spark plug
TorqueSpark plug tightening (used plug)1/8 - 1/4 turn after the spark plug seatsturnreinstalling a used spark plug

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilSAE 10W-30API service category SJ or later (or equivalent)1.1 LMaximum oil capacity 1.2 US qt (1.1 L); 4-stroke automotive detergent oil; other viscosities per ambient temperature chart
Engine oilSAE 10W-30 (other viscosities per ambient temperature chart)API service classification SJ or higher1.1 LNon detergent and 2-stroke oils are not recommended
FuelRegular unleaded gasolinepump octane rating 86 or higher
FuelRegular unleaded gasoline, pump octane rating 86 or higherNo more than 10% ethanol (E10) or 5% methanol by volume23.5 LFuel tank capacity 6.21 US gal (23.5 L)
FuelUnleaded gasoline, pump octane number (R+M)/2 of 86 or higher, or research octane number of 91 or higher17.0 litFuel tank capacity 17.0 lit (4.5 US gal); do not fill above UPPER LEVEL line; max 10% ethanol; never use methanol above 5%; never use stale or contaminated gasoline or an oil/gasoline mixture
FuelUnleaded gasoline, pump octane rating 86 or higher17.0 LFuel tank capacity 17.0 L (4.50 US gal, 3.74 Imp gal); up to 10% ethanol, 5% methanol, or 15% MTBE
Fuelunleaded gasoline, pump octane rating 86 or higher17.0 LDo not fill above the shoulder of the fuel strainer; oxygenated fuels allowed up to 10% ethanol, 15% MTBE, 5% methanol by volume
GreaseMarine greasewater resistant urea based grease
GreaseMulti-purpose greaseNLGI #2 or equivalentLithium based multi-purpose grease
OtherAutomatic transmission fluidATF

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Setting up 10 sec start delay adjustment

⚠ 10 sec start delay is used in combination with an ATS panel to prevent multiple short start-stop commands coming from the ATS panel while the mains is unstable during blackout.

  1. Open the controller cover and locate the red dip switch (S-DELAY).
  2. Use your finger to move the dip switch 1 to ON position.
  3. Replace the cover and tighten screws.
GFCI Operation Check (System ①) diagnostic

⚠ A faulty GFCI system will not provide proper protection against electric shock.

⚠ If the GFCI system fails the test, the generator must be repaired by an authorized Honda servicing dealer before use.

  1. Unplug all tools and appliances from the generator.
  2. Start the engine.
  3. Turn OFF the Auto Throttle switch.
  4. Turn the AC circuit breaker to the ON position.
  5. Press the TEST button: the RESET button should pop out and the AC circuit breaker should switch to OFF.
  6. Press the RESET button: it should stay in, flush with its base plate.
  7. With the RESET button in and the engine running, turn the AC circuit breaker to ON; it should remain ON.
GFCI Operation Check (System ②) diagnostic

⚠ If the red indicator starts to blink continuously, contact an authorized Honda generator dealer.

  1. Unplug all tools and appliances from the generator.
  2. Start the engine.
  3. Turn OFF the Auto Throttle switch.
  4. Turn the AC circuit breaker to the ON position; the green indicator should light continuously.
  5. Press the TEST button: the RESET button will pop out and the green indicator will go off.
  6. Press the RESET button: the green indicator will light continuously.
2 Wheel Kit Installation installation
  1. Install the two wheels on the axle shaft.
  2. Install the axle assembly on the generator using four bolts and nuts.
  3. Install the two stands using four bolts and nuts.
  4. Install right and left handles on the generator upper frame using brackets and six bolts.
2-Wheel Kit Installation installation
  1. Install the two wheels on the axle shaft.
  2. Install the axle assembly on the generator using four bolts and nuts.
  3. Install the two stands using four bolts and nuts.
  4. Install right and left handles on the generator upper frame using brackets and six bolts.
4 Wheel Kit Installation installation

⚠ Install the shaft with the wheel stopper facing the engine side.

  1. Install the four wheels on the axle shaft.
  2. Install the axle assembly on the generator using four bolts and nuts.
4-Wheel Kit Installation installation

⚠ Install the shaft with wheel stopper facing engine side.

  1. Install the four wheels on the axle shaft.
  2. Install the axle assembly on the generator using four bolts and nuts.
4-Wheel Kit Installation (optional parts) installation

⚠ Install the shaft with wheel stopper facing engine side.

  1. Install the four wheels on the axle shaft.
  2. Install the axle assembly on the generator using four bolts and nuts.
Handle Installation installation

⚠ Do not add fuel or oil before tipping the generator.

Tools: 12 mm wrench (2), pliers

  1. Install the handle holder assembly on the generator upper frame using the 8×18 mm flange bolts.
  2. Install the handle assembly on the upper frame pipe using 8×16 mm flange bolts, handle bush A, handle bush B, and handle lower bracket.
  3. Torque to 19.5 lbf·ft (26.5 N·m, 2.7 kgf·m).
  4. Check that the handle folds smoothly and does not hang down by its own weight.
Hanger Kit Installation installation

Tools: 12 mm wrench (2)

  1. Position the hanger at the generator's balance point.
  2. Fit the end tabs of the hanger through the bracket slots.
  3. Bolt the brackets to the hanger and tighten securely.
  4. Torque to 19.5 lbf·ft (26.5 N·m, 2.7 kgf·m).
Wheel Kit Installation installation

Tools: 12 mm wrench (2), pliers

  1. Install the two stands on the under frame using four 8×16 mm flange bolts.
  2. Install the two wheels on the axle shaft using the washers and split pins; bend the pins.
  3. Install the axle assembly using four 8×16 mm flange bolts and 8 mm flange nuts.
  4. Torque to 19.5 lbf·ft (26.5 N·m, 2.7 kgf·m).
Air Cleaner Check/Cleaning maintenance

⚠ Excess oil will restrict air flow and may cause engine to smoke at startup.

⚠ Operating without element or loose element allows dirt to enter engine.

  1. Remove air cleaner case lid springs and unhook tabs.
  2. Remove air cleaner cover and element.
  3. Check element and replace if damaged.
  4. Clean element in warm soapy water or non-flammable solvent, dry thoroughly.
  5. Dip filter in clean engine oil, squeeze out excess oil.
  6. Install air cleaner in reverse order of removal.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
120 VVoltage selector switch in "120V ONLY" positionOnly the 120V receptacles can be used; do not use the 120/240V receptacle in this position; rated power available at the 30A 120V twist lock receptacle
120/240 VVoltage selector switch in "120/240V" positionThe 120V and 120/240V receptacles can be used simultaneously; required if a 240V appliance is connected to the 4-prong receptacle

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Honda iGX390?

The Honda iGX390 engine has an oil capacity of 1.1 liters.

What is the displacement of the Honda iGX390?

The Honda iGX390 has a displacement of 0.389 liters.

Which generators use the Honda iGX390 engine?

The Honda iGX390 powers 3 generator set(s), including Honda EB5000, Honda EB6500, Honda EM5000SX.

What is a common problem with the Honda iGX390 engine?

A commonly reported issue on generators using the Honda iGX390 is: When the engine will hot start. Fix: 1. Is the engine switch on? 2. Does the oil alert lamp flash when the starter is pulled? 3. Is there enough fuel? 4. Are all loads disconnected from the AC receptacles? 5. Is there a spark at the spark plug? a. Remove the spark plug cap, Clean any dust from around the spark plug base, then remove the spark plug. b. Install the spark plug in the plug cap. c. Turn the engine switch on. d. Grounding the side electrode to any engine ground, pull the recoil starter to see if sparks jump across the gap. e. If any fuel has been spilled, make sure the area is dry before testing the spark plug. Fuel vapor or spilled fuel may ignite. Perform this test in a well-ventilated area. f. If there are no sparks, replace the plug. g. If the new spark plug does not spark, take the generator to an authorized Honda dealer..