HomeEnginesIveco/FPT N45 TM2 4.5L

Iveco/FPT N45 TM2 4.5L Engine Engine

The Iveco/FPT N45 TM2 4.5L is a 4.5 L natural engine rated at 1800 rpm. It powers generator sets from Winco, including the DR90F4. It holds 13.5 L (3.6 gal) of oil and 50 L (13.2 gal) of coolant.

Also known as: FPT N45 TM2 4.5L

4.5 L
Displacement
1800 rpm
Rated speed
13.5 L
Oil capacity

Engine specifications

Oil capacity13.5 L
Coolant capacity50.0 L
Displacement4.5 L
AspirationNatural
Rated speed1800 rpm

Generator sets powered by this engine

1

Common problems

7
  • Unit will not crank when power fails
    Cause: Digital genset not in AUTO Transfer control switch not in AUTOMATIC position Incorrect wiring between ATS and genset Defective control relay in ATS Fuse(s) blown in the DSE 7310 MKII Defective DSE 7310 MKII Loose or dirty battery terminals Defective starter Defective start solenoid Low/dead battery
  • No output from AC generator
    Cause: Loss of speed signal Loss of run signal Engine will not come up to speed after it starts Insufficient fuel volume getting to the unit 1. Too small of fuel line 2. Fuel racks not open properly Governor is defective AC short in generator components
  • Engine won’t crank
    Cause: Low/dead battery Blown DC fuses Defective DSE 7310 MKII Defective key switch Loose or dirty battery terminals Defective starter Defective start solenoid
  • Engine starts, then stops and alarm light comes on
    Cause: Engine oil pressure is low Engine has high water temperature Engine has overspeed Engine has gone into overcrank
  • Engine cranks but will not start
    Cause: Improper fuel delivery to the unit Fuel supply shut off Fuel tank empty Air in the fuel system Engine fuel solenoid has not opened Defective fuel pump Defective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid
  • ATS will not transfer to Emergency Supply (generator)
    Cause: No AC generator output Defective ATS control board. See ATS manual Circuit breaker open or defective
  • ATS will not re-transfer to normal power
    Cause: Proper power line not available at line terminals in ATS panel Defective ATS control board. See ATS manual

Compiled from service & troubleshooting documentation across every generator set that uses the Iveco/FPT N45 TM2 4.5L.

Common questions

What is the oil capacity of the Iveco/FPT N45 TM2 4.5L?

The Iveco/FPT N45 TM2 4.5L engine has an oil capacity of 13.5 liters.

What is the displacement of the Iveco/FPT N45 TM2 4.5L?

The Iveco/FPT N45 TM2 4.5L has a displacement of 4.5 liters.

Which generators use the Iveco/FPT N45 TM2 4.5L engine?

The Iveco/FPT N45 TM2 4.5L powers 1 generator set(s), including Winco DR90F4.

What is a common problem with the Iveco/FPT N45 TM2 4.5L engine?

A commonly reported issue on generators using the Iveco/FPT N45 TM2 4.5L is: Unit will not crank when power fails. Cause: Digital genset not in AUTO Transfer control switch not in AUTOMATIC position Incorrect wiring between ATS and genset Defective control relay in ATS Fuse(s) blown in the DSE 7310 MKII Defective DSE 7310 MKII Loose or dirty battery terminals Defective starter Defective start solenoid Low/dead battery.