Cummins/Onan 06110TA Engine Engine
The Cummins/Onan 06110TA is a astm no. 2 diesel engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the DV. It holds 32 L (8.5 gal) of oil and 40 L (10.6 gal) of coolant.
Also known as: Onan 06110TA
Engine specifications
| Oil capacity | 32.0 L |
|---|
| Coolant capacity | 40.0 L |
|---|
| Aspiration | ASTM No. 2 Diesel |
|---|
| Rated speed | 1800 rpm |
|---|
Generator sets powered by this engine
1
Common problems
15- Undedicated fault. May be factory programmed as a shutdown or non-shutdown, and as a timed or non-timed fault. (Normally set for timed shutdown). FAULT 1 (red)
- Starter has been locked out because of excessive cranking time
Cause: OVERCRANK (red) indicates the starter has been locked out because of excessive cranking time. - Same features as Fault 1 (Normally set for non-timed shutdown). FAULT 2 (red)
- Run lamp is not on when generator set is operating.
Fix: Indicates that a starter disconnect function is not working. Contact an Onan Distributor. - Run lamp is not on when generator set is operating
Fix: Indicates that a starter disconnect function is not working. Contact an Onan Distributor. - Overspeed shutdown.
Fix: Contact an Onan Distributor. - Overspeed shutdown
Fix: Contact an Onan Distributor - Overcrank fault lamp lights and engine stops cranking after about 75 seconds. Overcrank
Fix: Check for empty fuel tank, empty fuel filters, system leaks, or plugged fuel filters and fuel supply lines. Correct as required. - Low oil pressure shutdown; or pre low oil pressure shutdown if so programmed.
Fix: Check oil level and replenish if necessary. Contact an Onan Distributor if oil level is correct. - Low fuel fault circuit is energized yellow lamp
Fix: Check fuel tank and replenish fuel as needed. If fuel in tank is adequate/full, contact an Onan Distributor. - Low fuel fault circuit (yellow lamp) is energized.
Fix: Check fuel tank and replenish fuel as needed. If fuel in tank is adequate/full, contact an Onan Distributor. - Low engine temperature fault circuit is energized yellow lamp
Cause: Power outage or power disconnect (blown fuses)
Fix: Check power source supplying the coolant heater. If coolant heater, sensor or engine monitor is suspected, contact an Onan Distributor. - Low engine temperature fault circuit (yellow lamp) is energized.
Fix: Check power source supplying the coolant heater. Problem might be a power outage or power disconnect (blown fuses). If coolant heater, sensor or engine monitor is suspected, contact an Onan Distributor. - High engine temperature shutdown; or pre high engine temperature shutdown if so programmed.
Fix: Check coolant level on radiator and heat exchanger sets and replenish if necessary. Check for slipping drive belts or for obstructions to the airflow. Contact an Onan Distributor if none of the above. - Fault lamp lights, no fault exists.
Cause: Engine monitor or sensor malfunction. Contact an Onan Distributor.
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan 06110TA.
Common questions
What is the oil capacity of the Cummins/Onan 06110TA?
The Cummins/Onan 06110TA engine has an oil capacity of 32.0 liters.
Which generators use the Cummins/Onan 06110TA engine?
The Cummins/Onan 06110TA powers 1 generator set(s), including Cummins/Onan DV.
What is a common problem with the Cummins/Onan 06110TA engine?
A commonly reported issue on generators using the Cummins/Onan 06110TA is: Undedicated fault. May be factory programmed as a shutdown or non-shutdown, and as a timed or non-timed fault. (Normally set for timed shutdown)..