Volvo Penta 16 liter Engine
The Volvo Penta 16 liter is a 16 L engine. It powers generator sets from Volvo Penta, including the 16 liter Gen Set.
Also known as: Volvo Penta 16 liter
Common problems
15- Water in Fuel (Code 2.1, PID/SPN 97) 2.1, PID/SPN 97
Fix: * Empty the primary fuel filter indicator for Water in Fuel (Code 2.9, PID/SPN 97) - Too low coolant temperature 20
- Too high exhaust temperature (only TWD1643GE) 13, 17, 18, 19, 21, 25, 27, 28, 29, 30
- Tao low lubrication cil pressure 16
- Preheating Relay (Code 5.4, PID 45/SPN 626) 5.4, PID 45/SPN 626
Cause: Short circuit to positive (+) or +. Preheating can not be activated. earth (ground) (-). Open circuit. - Preheating is constantly connected.
Fix: * Check that the relay input cable is not damaged. * Check relay function. - Oil Pressure Sensor (Code 3.1, PID/SPN 100) 3.1, PID/SPN 100
Fix: * Check that the oil pressure sensor cable is not damaged * Check that the oil pressure sensor is correctly connected * Check oil pressure sensor function - Oil Pressure (Code 6.6, PID/SPN 100) 6.6, PID/SPN 100
Cause: * Oil pressure is too low
Fix: * Check oil level * Check that the air filter is not blocked * Check system pressure valves and safety valves in the oil system * Check oil pressure sensor function - Oil Level Sensor (Code 5.9; PID/SPN 98) 5.9; PID/SPN 98
Fix: * Check that the cable harness to the oil level sensor has not been damaged * Check the oil level sensor function - Oil Level (Code 5.7, PID/SPN 98) 5.7, PID/SPN 98
Cause: * Oil level to low
Fix: * Check the oil level - No, or poor charge 2, 23
- Fuel Pressure Sensor (Code 3.6, PID/SPN 94) 3.6, PID/SPN 94
Fix: * Check that the fuel pressure sensor connector is correctly installed. * Check that the fuel pressure sensor cable is not damaged. * Check that the fuel pressure sensor is correctly installed. * Check fuel pressure sensor-function. - Fuel Pressure (Code 3.8, PID/SPN 94) 3.8, PID/SPN 94
Cause: * Low supply pressure
Fix: * Check if it is possible to build up pressure with the hand pump * Check the fuel filter * Check the fuel pre-filter - Excessive coolant temperature 17, 18, 19, 20, 28
- Boost Temperature Sensor (Code 3.2, PID/SPN 105) 3.2, PID/SPN 105
Fix: * Check that the boost temperature sensor connector is correctly installed * Check that the boost temperature sensor cable is not damaged * Check that the boost temperature sensor is correctly installed * Check boost temperature sensor function - Boost Temperature (Code 6.2, PID/SPN 105) 6.2, PID/SPN 105
Cause: * Boost temperature is too high
Fix: * Check the coolant level * Check the charge air cooler (cleanliness) * Check boost temperature sensor function * Check the function of the thermostat
Compiled from service & troubleshooting documentation across every generator set that uses the Volvo Penta 16 liter.
Common questions
What is the displacement of the Volvo Penta 16 liter?
The Volvo Penta 16 liter has a displacement of 16.0 liters.
Which generators use the Volvo Penta 16 liter engine?
The Volvo Penta 16 liter powers 1 generator set(s), including Volvo Penta 16 liter Gen Set.
What is a common problem with the Volvo Penta 16 liter engine?
A commonly reported issue on generators using the Volvo Penta 16 liter is: Water in Fuel (Code 2.1, PID/SPN 97). Fix: * Empty the primary fuel filter indicator for Water in Fuel (Code 2.9, PID/SPN 97).