HomeEnginesKubota Dl 005

Kubota Dl 005 Engine Engine

The Kubota Dl 005 is a 1 L 3-cylinder diesel engine rated at 1800 rpm, producing up to 9.46 kW. It powers generator sets from Cummins/Onan, including the MDKAL. It holds 4.25 L (1.1 gal) of oil and 3.78 L (1.0 gal) of coolant.

Also known as: Kubota Dl 005

1.001 L
Displacement
3
Cylinders
1800 rpm
Rated speed
9 kW
Gross power

Engine specifications

Oil capacity4.25 L
Coolant capacity3.78 L
Displacement1.001 L
Cylinders3
AspirationDiesel
Rated speed1800 rpm
Gross power9 kW

Generator sets powered by this engine

1

Common problems

9
  • ‘Check Engine’ Fault Shutdown Check Engine
  • NO OUTPUT VOLTAGE
    Cause: A line circuit breaker is Off. A line circuit breaker has Tripped.
    Fix: Find out why the circuit breaker was turned Off, make sure it is safe to reconnect power, and then throw the circuit breaker On. Shut down the genset and have service performed as necessary to clear the short circuit or ground fault that caused tripping. Then Reset the circuit breaker and start the genset.
  • Fault Circuit Breaker CB2 trips
    Cause: AC over-voltage, overspeed, high exhaust temperature, high coolant temperature, low oil pressure, and low coolant level (optional)
  • Engine does not stop running
    Cause: Malfunctioning fuel solenoid or linkage
    Fix: Pull the stop lever to the right and hold it there until the engine stops (see figure). PULL TO RIGHT AND HOLD UNTIL ENGINE STOPS
  • ENGINE DOES NOT CRANK FROM REMOTE PANEL
    Cause: Emergency Stop Switch OFF; "Check Generator" or "Check Engine" Fault; Faulty remote circuit
    Fix: Push ON.; Service the fault as necessary and push fault reset button in. See “CHECK ENGINE” FAULT SHUTDOWN or “CHECK GENERATOR” FAULT SHUTDOWN.; Try starting at the genset control panel. If the genset starts, have the remote circuit repaired as necessary.
  • ENGINE DOES NOT CRANK FROM GENSET PANEL
    Cause: Emergency Stop Switch OFF; "Check Generator" or "Check Engine" Fault; Cranking voltage too low
    Fix: Push ON.; Service the fault as necessary and push fault reset button in. See “CHECK ENGINE” FAULT SHUTDOWN or “CHECK GENERATOR” FAULT SHUTDOWN.; a. Clean and tighten or replace the positive (+) and negative (- ) battery cable connectors and cables at the battery and the genset. b. Recharge or replace the battery. Specific gravity for a fully charged battery is approximately 1.260 at 80° F (27° C).
  • ENGINE CRANKS BUT DOES NOT START
    Cause: Engine not getting fuel; Blocked air inlet; Low engine temperature; Cranking voltage too low
    Fix: A. Open any closed shutoff valve. b. Check fuel level and refill as necessary. c. Prime the fuel system (p. 24). d. Check for fuel (air) leaks at all fittings and tighten as necessary. e. Replace the fuel filter (p. 23).; Service as necessary.; a. Plug in, repair or install engine coolant and engine oil heaters. b. Replace the engine oil if it is not of the recommended viscosity for the ambient temperature.; a. Clean and tighten or replace the positive (+) and negative (- ) battery cable connectors and cables at the battery and the genset. b. Recharge or replace the battery. Specific gravity for a fully charged battery is approximately 1.260 at 80° F (27° C).
  • "CHECK GENERATOR" FAULT SHUTDOWN
    Cause: Generator overload
    Fix: Run with less load.
  • "CHECK ENGINE" FAULT SHUTDOWN
    Cause: Low engine oil pressure; High engine temperature; High exhaust temperature
    Fix: Check engine oil level, repair any leaks and fill to the proper level (p. 17).; a. Check engine coolant level, repair any leaks and fill to the proper level (p. 18). b. Check V-belt tension (p. 20). c. Clean and service the cooling system as required to restore full cooling capacity (p. 18).; a. Open the sea cock. b. Remove any blockage in the sea water strainer. c. Prime the sea water pump (p. 22). d. Replace the sea water pump impeller (p. 22). e. Clean seaweed and pump debris from heat exchanger (p. 22). f. Remove blockage covering the sea water hull strainer.

Compiled from service & troubleshooting documentation across every generator set that uses the Kubota Dl 005.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter find
Fuel filter find
Oil filter find
Belt find
Coolant8760 hr
Coolant filter find
Oil35 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Common questions

What is the oil capacity of the Kubota Dl 005?

The Kubota Dl 005 engine has an oil capacity of 4.25 liters.

What is the displacement of the Kubota Dl 005?

The Kubota Dl 005 has a displacement of 1.001 liters with 3 cylinders.

Which generators use the Kubota Dl 005 engine?

The Kubota Dl 005 powers 1 generator set(s), including Cummins/Onan MDKAL.

How often should you change the oil in the Kubota Dl 005?

The Kubota Dl 005 oil change interval is every 35 hours.

What is a common problem with the Kubota Dl 005 engine?

A commonly reported issue on generators using the Kubota Dl 005 is: ‘Check Engine’ Fault Shutdown.