Cummins/Onan EFI OHV 4-stroke Engine Engine
The Cummins/Onan EFI OHV 4-stroke is a 2.24 L engine. It powers generator sets from Cummins/Onan, including the P4500IDF, P5000iDF EFI, P9500DF EFI and P9500df.
Also known as: Cummins EFI OHV 4-stroke
Generator sets powered by this engine
4
Common problems
15- Overspeed shutdown.
Fix: Check governor and throttle linkages for freedom of movement. Check overspeed switch. - Overspeed light on, no shutdown.
Fix: Disconnect wire at TB11-29. Light on after reset; replace engine monitor board. - Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds.
Fix: See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position. - No power at AC receptacles
Cause: OUTPUT READY LED is OFF and OVERLOAD LED is ON.
Fix: Check AC load. Stop and restart engine. - Fault lamp lights, no fault exists.
Fix: To check a no-fault condition, disconnect leads from TB11 terminals 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads. - Fault lamp lights immediately after engine starts.
Fix: Check for: Overspeed condition as engine starts. - Fault lamp lights and engine shuts down after running for a period.
Fix: Check the following: a. Oil level. Engine will shut down if sensor is closed. b. Check engine manual for troubleshooting oil system. c. High engine temperature. Check coolant level; check water flow (city water cooled systems); check radiator for free air flow, and fan belts for tightness. See engine manual for troubleshooting cooling system. d. Check for faulty oil pressure sensor or faulty high engine temperature sensor. - Engine will not start
Cause: Battery switch in the OFF position.
Fix: Turn battery switch to the ON position. - Engine stops cranking-and fault lamp lights, after cranking approximately 75 seconds.
Fix: See engine service manual for troubleshooting fuel system. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position. - Engine starts, then shuts down
Cause: Out of fuel.
Fix: Refuel. - Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, overcrank light ON.
Fix: Check fuel supply. - Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lights.
Fix: Check fuel supply. - Engine runs rough or bogs when load applied
Cause: Dirty air filter.
Fix: Clean the air filter. - Engine lacks power
Cause: Air filter restricted.
Fix: Clean or replace air filter. - *Low oil pressure shutdown.
Fix: Check— a. Oil level. Replenish if necessary. b. Sensor. Faulty sensor will shut down engine. c. Refer to engine service manual for troubleshooting guide for oil system.
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan EFI OHV 4-stroke.
Common questions
What is the displacement of the Cummins/Onan EFI OHV 4-stroke?
The Cummins/Onan EFI OHV 4-stroke has a displacement of 2.24 liters.
Which generators use the Cummins/Onan EFI OHV 4-stroke engine?
The Cummins/Onan EFI OHV 4-stroke powers 4 generator set(s), including Cummins/Onan P4500IDF, Cummins/Onan P5000iDF EFI, Cummins/Onan P9500DF EFI, Cummins/Onan P9500df.
What is a common problem with the Cummins/Onan EFI OHV 4-stroke engine?
A commonly reported issue on generators using the Cummins/Onan EFI OHV 4-stroke is: Overspeed shutdown.. Fix: Check governor and throttle linkages for freedom of movement. Check overspeed switch..