Kohler KT17II Series II Engine Engine
The Kohler KT17II Series II is a 0.69 L 2-cylinder air-cooled, four-stroke engine rated at 1800 rpm. It powers generator sets from Kohler, including the 4.5 CKM. It holds 1.4 L (0.4 gal) of oil.
Also known as: KOHLER KT17II Series II
Engine specifications
| Oil capacity | 1.4 L |
|---|
| Displacement | 0.6914 L |
|---|
| Cylinders | 2 |
|---|
| Aspiration | Air-Cooled, Four-Stroke |
|---|
| Rated speed | 1800 rpm |
|---|
Generator sets powered by this engine
1
Common problems
11- Low oil pressure
Cause: Will cause (LOP) switch contacts to open and de-energize K1 relay.
Fix: None provided in the text. - Will not start (cranks OK)
Cause: K2 relay coil defective, Engine defective (no compression, stuck valves, etc.), Defective LP gas valve or secondary regulator
Fix: Check continuity, Troubleshoot engine, Check LP gas pressure at secondary regulator. Pressure should be 4 to 6 oz. or 7 to 11 inches water column. - SDR Relay P3-4
- No generator output voltage
Cause: Open wiring, terminal, or pin in build-up circuit (P1 connector), Open D1 or D2 diode, K1 relay (N.C.) contacts open (contacts between D2 and P3-4), Brushes sticking in holder, Rotor slip rings dirty or corroded
Fix: Check continuity, Check for open or shorted diode. (A good diode has high resistance one way and low resistance the other way, when tested with ohmmeter), Check continuity, Check alignment, Check and/or service - Low generator output voltage
Cause: Low engine rpm, Defective voltage regulator
Fix: Check speed using tachometer or frequency meter, Test and/or replace - High generator output voltage
Cause: Open or poor splice connection at terminals 33-3 or 44-4 on stator (regulator sensing)
Fix: Check continuity - Generator set will not carry load or runs rough
Cause: Excessive load connected to generator, Engine not operating at rated rpm, Governor not properly adjusted or defective, Carburetor not properly adjusted or defective (gasoline model only), Carburetor not properly adjusted or defective (LP gas model only), Defective or grounded breaker points, Improper timing, Defective ignition coil, Defective or misadjusted spark plug, Carburetor choke mis-adjusted or defective (gasoline model only), Fuel line restriction
Fix: Reduce electrical load, Check speed using tachometer or frequency meter, NOTE: Hz x 120 = rpm x no. of rotor poles, Check speed using tachometer or frequency meter, NOTE: Hz x 120 = rpm x no. of rotor poles, Check and/or service - Generator set shuts down by itself
Cause: No fuel in tank, Fuel line restriction, Dirty electric fuel pump filter (gasoline model only), Fuel line drawing air, Defective electric fuel pump (gasoline model only), Engine overloaded, Engine overheated, Low engine oil pressure, Ignition coil fails when hot, Fuel vapor lock
Fix: Replenish, Check fuel lines and tank. Check gasoline fuel pressure of 4.5 psi (31 kPa), Clean filter, Check fuel lines and tank, Check fuel pressure of 4.5 psi (31 kPa), Reduce electrical load, Check air intake, carburetor adjustment, oil level, timing, etc., Check pressure and pump components, Check using “cold” test - Generator set shut down by itself (cont.)
Cause: Loss of generator output voltage to K1 relay
Fix: Check AC voltage at rectifier, Check continuity of B1 & B2 stator leads - Fuel Pump/Valve P26
- Engine starts, but does not continue to run after start switch is released
Cause: Open wiring (P1 or P2 connector), No engine oil pressure, Defective low oil pressure (LOP) shutdown switch, K1 relay coil defective, K1 relay (N.O.) contacts remain open
Fix: Check AC voltage, Check stator continuity, Check continuity, Check oil pressure and pump, Bypass LOP shutdown switch using jumper wire to ground. If engine continues to run after start switch is released, replace LOP shutdown switch.
Compiled from service & troubleshooting documentation across every generator set that uses the Kohler KT17II Series II.
Maintenance schedule
| Item | Spec | Capacity | Part # | Interval | |
|---|
| Air filter | Air Cleaner: Must be clean and properly installed, Air Duct: Must be tight and in proper position | | — | 1000 hr | find |
| Fuel filter | Fuel Filter Service: 3-3 | | — | 500 hr | find |
| Oil filter | | | — | 2000 hr | find |
| Belt | | | — | 500 hr | find |
| Coolant | | | — | | |
| Coolant filter | Service or replace spark plugs | | — | 1000 hr | find |
| Oil | Lube Oil Capacity: 3.0 U.S. Pints (1.4 L) | 1.4 L | — | 500 hr | |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
Common questions
What is the oil capacity of the Kohler KT17II Series II?
The Kohler KT17II Series II engine has an oil capacity of 1.4 liters.
What is the displacement of the Kohler KT17II Series II?
The Kohler KT17II Series II has a displacement of 0.6914 liters with 2 cylinders.
Which generators use the Kohler KT17II Series II engine?
The Kohler KT17II Series II powers 1 generator set(s), including Kohler 4.5 CKM.
How often should you change the oil in the Kohler KT17II Series II?
The Kohler KT17II Series II oil change interval is every 500 hours.
What is a common problem with the Kohler KT17II Series II engine?
A commonly reported issue on generators using the Kohler KT17II Series II is: Low oil pressure. Cause: Will cause (LOP) switch contacts to open and de-energize K1 relay.. Fix: None provided in the text..