HomeEnginesWaukesha F1197-GRS1U

Waukesha F1197-GRS1U Engine Engine

The Waukesha F1197-GRS1U is a 2.99 L 6-cylinder natural aspiration engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the WC Series. It holds 31.68 L (8.4 gal) of oil.

Also known as: Waukesha F1197-GRS1U

2.98543 L
Displacement
6
Cylinders
1800 rpm
Rated speed
31.68 L
Oil capacity

Engine specifications

Oil capacity31.68 L
Displacement2.98543 L
Cylinders6
AspirationNatural Aspiration
Rated speed1800 rpm

Generator sets powered by this engine

1
Cummins/Onan WC Series

Common problems

13
  • Partial loss of residual in Rotor
    Fix: With plant operating, jumper from E2 to heat sink of field rectifier Z until voltage begins to build-up. Then remove.
  • Output voltage slow to buildup.
    Cause: Circuit breaker opens in about five seconds
  • Output voltage slow to build up and ten to twenty percent above rated voltage after build up
    Cause: Open in one Field Rectifier or Open circuit in Gate winding G1-G2 of Reactor A or B
    Fix: Test rectifiers and replace if defective. If Field Rectifiers Y and Z check okay, check continuities of Gate windings G1-G2
  • Output voltage slow to build up and higher than rated voltage after build up
    Cause: Open circuit in one or more Control Rectifier
    Fix: Test rectifier and replace if defective. Check soldered connections to rectifiers
  • Output voltage slow to build up and five percent below rated voltage after build up. Voltage regulation poor.
    Cause: Either Field Rectifier W or Z shorted
    Fix: Test rectifiers and replace if defective
  • Output voltage builds up normally with slightly less than rated voltage at no load and low voltage at full load
    Cause: Compound winding S1-S2 installed backward or has open circuit
    Fix: Check wiring diagram for polarity of compound windings through Reactors A and B and test for continuity
  • Output voltage builds up normally but less than rated voltage after build up
    Cause: Shorted winding in Control Reactor
    Fix: Test Control Reactor and replace if defective
  • Output voltage builds up normally but is twenty-five percent above rated voltage after build up
    Cause: Open circuit in Control Rectifier bridge
    Fix: Check continuity from the junction of Control Rectifiers W and X to the junction of Control Rectifiers Y and Z
  • Output voltage builds up normally but 20-percent above rated voltage after build up. Voltage regulation poor.
    Cause: Compound winding S1-S2 installed backward through one Reactor (A or B))
    Fix: Check wiring diagram for polarity of Compound winding through Reactor A or B
  • No AC power to Magneciter
    Fix: Check AC voltage at E1-E2 with the plant operating. Voltage should be five percent of the rated voltage. If not, check continuity from E1-E2 back to generator
  • Generator will not build up voltage.
    Cause: Circuit breaker in 'off' or 'tripped' position
    Fix: Reset and close breaker
  • Excessive charging rate (Battery requires too frequent filling)
    Fix: Tighten connections,
  • Alternator fails to charge or puts out low or unstable charge rate
    Cause: Alternator belt loose. Loose or dirty battery connections. Worn or defective brushes. Faulty regulator.
    Fix: Tighten belt. Clean and tighten. Replace brushes. Replace regulator.

Compiled from service & troubleshooting documentation across every generator set that uses the Waukesha F1197-GRS1U.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter find
Fuel filterOnan OE Filter232AI817400 hr PartsGeek
Oil filterOnan OE Filter232AI490400 hr PartsGeek $17.97
Belt#18 wire900 hr find
Coolant36.0 gallons
OilSAE 20W-5032.0 L400 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Filters for this engine

  • Oil filter: Waukesha 101737A Donaldson P550117 Wix 51503 Ac Delco AC114

Cross-referenced via Donaldson + OEM/engine-maker interchange — options to verify against your serial number, not confirmed for every exact variant.

Also used in

1
  • Waukesha F1197G — Engine

Other equipment known to use this engine, via filter-application cross-reference — useful for sourcing parts even when your exact machine isn't listed elsewhere on this page.

Common questions

What is the oil capacity of the Waukesha F1197-GRS1U?

The Waukesha F1197-GRS1U engine has an oil capacity of 31.68 liters.

What is the displacement of the Waukesha F1197-GRS1U?

The Waukesha F1197-GRS1U has a displacement of 2.98543 liters with 6 cylinders.

Which generators use the Waukesha F1197-GRS1U engine?

The Waukesha F1197-GRS1U powers 1 generator set(s), including Cummins/Onan WC Series.

What oil filter does the Waukesha F1197-GRS1U use?

The Waukesha F1197-GRS1U uses oil filter part numbers Waukesha 101737A, Donaldson P550117, Wix 51503.

How often should you change the oil in the Waukesha F1197-GRS1U?

The Waukesha F1197-GRS1U oil change interval is every 400 hours.

What is a common problem with the Waukesha F1197-GRS1U engine?

A commonly reported issue on generators using the Waukesha F1197-GRS1U is: Partial loss of residual in Rotor. Fix: With plant operating, jumper from E2 to heat sink of field rectifier Z until voltage begins to build-up. Then remove..