HomeEnginesCummins/Onan HDKAS

Cummins/Onan HDKAS Engine Engine

The Cummins/Onan HDKAS is a 0.9 L 3-cylinder liquid-cooled engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the HDKA. It holds 4.5 L (1.2 gal) of oil and 4.73 L (1.2 gal) of coolant.

Also known as: Cummins HDKAS

0.898 L
Displacement
3
Cylinders
1800 rpm
Rated speed
4.5 L
Oil capacity

Engine specifications

Oil capacity4.5 L
Coolant capacity4.73 L
Displacement0.898 L
Cylinders3
AspirationLiquid-cooled
Rated speed1800 rpm

Generator sets powered by this engine

1

Troubleshooting

4

Symptoms & remedies

SymptomCauseRemedy
NO AC OUTPUT VOLTAGE AT RATED ENGINE RPMLoad circuit breakers closed, overload in the load circuit, open circuit between brush block and voltage regulator, brushes stuck or not making good contact with slip rings, opens or grounds in rotor or stator, incorrect field voltage, wrong connections of F1 and F2 leadsLocate cause of overload and correct as required. Reset breaker, or replace if bad. Check continuity of circuit breakers and replace if necessary. Is circuit open between brush block and voltage regulator? Check for continuity and correct if circuit is open. Are brushes stuck in holder or not making good contact with slip rings? Release brushes if jammed in holder. Clean slip rings if dirty. Test continuity of rotor, stator per Tests [B], [C]. Are there opens or grounds? Replace component if defective. Test field voltage per TEST [A]. Is there correct field voltage? Examine brush block connections. Are F1 and F2 leads installed on correct terminals? Perform TEST [D]. Connect brush leads to correct terminals.
UNSTABLE OUTPUT VOLTAGE, ENGINE SPEED STABLEBroken wires or loose connections on voltage regulator assembly, brushes not OKAre there any broken wires or loose connections on voltage regulator assembly? Check wiring harness from regulator assembly to end bell per TEST [F]. Check OK? Repair as required. Inspect brushes per procedure in Manual Section 4. Brushes OK? Repair wiring or replace as required.
Engine does not crank.Is battery dead? Check CB11 circuit breaker. If okay, jumper battery cable B+ connection to B1 starter so- lenoid terminal. Does engine crank? With S11 in Start position, is battery voltage present between K11 terminal S and ground? If K11 does not energize, test per Checkout [D] and replace if bad. Is battery voltage present at B1 solenoid terminal with S11 in Start position? Check battery per Checkout [A] and recharge or replace. Check battery charger operation per Checkout [C]. Check battery cables for clean tight connections (ref. Checkout [B]). Check B1 starter so- lidoid and motor: if bad, repair or replace. Check B+ wiring to S11, and between S11 and K11. Check NC contacts of A11-K15. Replace if bad.
Unbalanced generator set output voltageRemove load at generator set terminals. Are generator set leads connected and grounded properly? See Test [C]. Is generator set stator winding continuous per TEST [C]? Check load for ground faults and correct as necessary. Check for correct grounding of generator set and load. Correct as necessary. Replace stator assembly.

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.

Common problems

15
  • Weakness and Sleepiness
    Fix: IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
  • Vomiting
    Fix: IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
  • Voltage Sense Code 27
  • UNSTABLE OUTPUT VOLTAGE, ENGINE SPEED STABLE
    Cause: Broken wires or loose connections on voltage regulator assembly, brushes not OK
    Fix: Check wiring harness from regulator assembly to end bell per TEST [F]. Inspect brushes per procedure in Manual Section 4. Repair as required.
  • Under Voltage Code 13
  • Under Frequency Code 15
  • Unbalanced generator set output voltage
    Fix: Remove load at generator set terminals. Are generator set leads connected and grounded properly? See Test [C]. Is generator set stator winding continuous per TEST [C]? Check load for ground faults and correct as necessary. Check for correct grounding of generator set and load. Correct as necessary. Replace stator assembly.
  • UNBALANCED GENERATOR OUTPUT VOLTAGE
    Cause: Generator leads not connected and grounded properly, generator stator winding not continuous
    Fix: Remove load at generator terminals. Check if generator leads are connected and grounded properly per TEST [C]. Test generator stator winding continuity.
  • The indicator light in the Start/Stop switch turns off
    Fix: Confirm that the correct connection diagram (Figures 5 - 7) was used, then check EC 30 wiring connections. Confirm that the correct voltages are present on each terminal. Check all terminal connections on both ends of the wiring harness. Are harness connectors properly joined?
  • The genset stops
    Fix: Does the genset operate correctly from the genset controls? If it does not, the problem is in the genset, not the EC-20 controller. See the genset Operator, Installation, and Service Manuals.
  • STATUS INDICATOR LIGHT STAYS ON
    Cause: Reversed battery connections
    Fix: Corrective Action: Reconnect the battery correctly (Page 17).
  • STATUS INDICATOR LIGHT DEAD
    Cause: Faulty connections, no battery voltage
    Fix: 1. Try the genset Start Switch if the remote Start Switch does not work, and vice versa. 2. Replace Fuse F1 (B+) if blown (Page 7). 3. Clean and tighten the positive (+) and negative (−) battery cable connections at the battery, vehicle frame and genset (Page 17). 4. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations.
  • STARTING BATTERIES RUN DOWN
    Cause: (Marginal battery, battery connections, or charging system; or parasitic loads)
    Fix: 1. Clean and tighten the positive (+) and negative (−) battery cable connections at the battery, vehicle frame and genset (Page 17). 2. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations.
  • STARTER ENGAGES-DISENGAGES
    Cause: (Cranking voltage dips below 6 volts—low battery charge, poor connections, long cables)
    Fix: 1. Have the vehicle propulsion engine running while trying to start the genset—the battery charging alternator may be able to maintain starting voltage high enough to get the genset started. 2. Clean and tighten the positive (+) and negative (−) battery cable connections at the battery, vehicle frame and genset (Page 17). 3. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations. 4. Increase battery cable size or run parallel cables.
  • Shutdown due to high engine coolant temperature blink-blink-blink-pause-blink-blink-blink-blink-blink-blink-long pause-repeat

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan HDKAS.

Common questions

What is the oil capacity of the Cummins/Onan HDKAS?

The Cummins/Onan HDKAS engine has an oil capacity of 4.5 liters.

What is the displacement of the Cummins/Onan HDKAS?

The Cummins/Onan HDKAS has a displacement of 0.898 liters with 3 cylinders.

Which generators use the Cummins/Onan HDKAS engine?

The Cummins/Onan HDKAS powers 1 generator set(s), including Cummins/Onan HDKA.

What is a common problem with the Cummins/Onan HDKAS engine?

A commonly reported issue on generators using the Cummins/Onan HDKAS is: Weakness and Sleepiness. Fix: IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired..