Waukesha L1616-GSIU Engine Engine

The Waukesha L1616-GSIU is a 30.87 L 12-cylinder natural gas engine rated at 1500 rpm. It powers generator sets from Cummins/Onan, including the W. It holds 95 L (25.1 gal) of oil and 194 L (51.2 gal) of coolant.

Also known as: Waukesha L1616-GSIU

30.87 L
Displacement
12
Cylinders
1500 rpm
Rated speed
95.0 L
Oil capacity

Engine specifications

Oil capacity95.0 L
Coolant capacity194.0 L
Displacement30.87 L
Cylinders12
AspirationNatural gas
Rated speed1500 rpm

Generator sets powered by this engine

1

This engine also powers 15 machine(s) on Power Equipment Info.

Common problems

15
  • Partial loss of residual in rotor.
    Fix: With plant operating, jumper from E2 to heat sink of field rectifier Z until voltage begins to build-up. Then remove.
  • Pair of field rectifiers open (either W & Z or X & Y).
    Fix: Test rectifiers and replace if defective.
  • Output, voltage slow to build . up and higher than rated volt- age after build up
    Cause: Open circuit in one or more control rectifier.
    Fix: Test rectifiers and replace if defective. Check soldered connections to rectifiers.
  • Output voltage slow to build up and ten to twenty percent above rated voltage after build up
    Cause: Open in one field rectifier.; If field rectifiers Y and Z check okay, check continuities of gate windings Gl -G2.
  • Output voltage slow to build up and five percent below rated voltage after build up
    Cause: Voltage regulation poor
    Fix: Either field rectifier W or Z shorted. Test rectifiers and replace if defective.
  • Output voltage slow to build up
    Cause: Circuit breaker opens in about five seconds
    Fix: Either field rectifier X or Y shorted. Test rectifiers and replace if defective.
  • Output voltage builds up normally with slightly less than rated voltage at no load and low voltage at full load
    Cause: Compound winding Sl - S2 installed backward or has open circuit.
    Fix: Check wiring diagram for polarity of compound windings ' through reactors A and B and test for continuity.
  • Output voltage builds up normally but less than rated voltage after build up
    Cause: Shorted winding in control reactor.
    Fix: Test control reactor and replace if defective.
  • Output voltage builds up normally but 20 percent above rated voltage after build up
    Cause: Voltage regulation poor.; Compound winding S1-S2 installed backward through one reactor (A or B).
  • Output voltage builds up normally but 150 to 200 percent above rated voltage after build up
    Cause: No regulation possible. Control winding C1-C2 of reactor A or B polarized incorrectly.; Shorted turn in control winding C1-C2 or reactor A or B.; Open in control circuit.
  • Output voltage builds up normally but 125 to 150 .percent, above rated voltage after build up
    Cause: Shorted turn in gate winding Gl -G2 of reactor A or B.
    Fix: Test reactors A and B for shorted turns and replace if defective.
  • No AC power to Magneciter.
    Fix: Check AC voltage at E1-E2 with the plant operating. Voltage should be five percent of the rated voltage. If not, check continuity from El -E2 back tb generator.
  • Generator will not build up voltage.
    Cause: Circuit breaker in 'off' or 'tripped' position.
    Fix: Reset. and close breaker.
  • Generator voltage fluctuating while engine running at constant speed
    Cause: Incorrect setting on stabilizing resistor.
    Fix: Check resistance and reset.
  • Both field rectifiers X and Y shorted.
    Fix: Test rectifiers and replace if defective.

Compiled from service & troubleshooting documentation across every generator set that uses the Waukesha L1616-GSIU.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterDry type1000 hr find
Fuel filterWaukesha500 hr find
Oil filterWaukesha1000 hr find
BeltV-belt1000 hr find
CoolantWaukesha194.0 gallons5000 hr
OilWaukesha25.0 gallons

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Common questions

What is the oil capacity of the Waukesha L1616-GSIU?

The Waukesha L1616-GSIU engine has an oil capacity of 95.0 liters.

What is the displacement of the Waukesha L1616-GSIU?

The Waukesha L1616-GSIU has a displacement of 30.87 liters with 12 cylinders.

Which generators use the Waukesha L1616-GSIU engine?

The Waukesha L1616-GSIU powers 1 generator set(s), including Cummins/Onan W.

What is a common problem with the Waukesha L1616-GSIU engine?

A commonly reported issue on generators using the Waukesha L1616-GSIU is: Partial loss of residual in rotor.. Fix: With plant operating, jumper from E2 to heat sink of field rectifier Z until voltage begins to build-up. Then remove..