| AnInIOM Sd | Analog Input IOM Shutdown | Shutdown alarm configurable on the input of IG-IOM/IGS-PTM. | Shutdown | |
| AnInIOM Wrn | Analog Input IOM Warning | Warning alarm configurable on the input of IG-IOM/IGS-PTM. | Warning | |
| Battery Flat | Battery Flat (low battery) | If the controller switches off during starting sequence due to bad battery condition, it doesn't try to start again and activates this protection. | Shutdown | |
| Binary Input | Binary Input | Configurable warning/shutdown alarms on the inputs of IL-NT. | | |
| ChrgAlternFail | Charge Alternator Fail | Failure of the alternator to charge the battery. | Warning | |
| EMERGENCY STOP ACTIVATED | Emergency stop activated | Notifies operator that the emergency stop is activated | Shutdown | Pull the emergency stop switch out to deactivate |
| ENGINE REST | Engine rest | Flashing LED - indicates the engine has paused between starting attempts | Info | |
| ENGINE RUNNING | Engine running | Steady LED - indicates proper operation of the pump engine | Info | |
| EmergencyStop | Emergency Stop | If the input Emergency Stop is opened or the red E-Stop button is pushed, shutdown is immediately activated. | Shutdown | |
| Engine Temp Sd | Engine Temperature Shutdown | Water temperature is greater than Sd Water Temp setpoint. | Shutdown | |
| Engine Temp Wrn | Engine Temperature Warning | Water temperature is greater than Wrn Water Temp setpoint. | Warning | |
| Fgen<, > | Generator Frequency Out of Limits | The generator frequency is out of limits given by Gen >f and Gen <f setpoints. | Shutdown | |
| Fuel Level Sd | Fuel Level Shutdown | Fuel level is smaller than Sd Fuel Level setpoint (5%). | Shutdown | |
| Fuel Level Wrn | Fuel Level Warning | Fuel level is smaller than Wrn Fuel Level setpoint (15%). | Warning | |
| GCB fail | Generator Circuit Breaker Fail | Failure of the generator circuit breaker. | Shutdown | |
| HIGH TEMPERATURE | High temperature | Steady LED - indicates a pump engine shut down due to the coolant temperature exceeding 235 degF (113 degC) | Shutdown | Refer to PUMP TROUBLESHOOTING on page 30 for possible causes |
| Igen unbl | Generator Current Unbalanced | The generator current is unbalanced. | Shutdown | |
| LOW FUEL / LOW COOLANT | Low fuel / low coolant | Flashing LED - indicates a low fuel level or low coolant level shut down (optional) | Shutdown | Refill fuel tank with clean diesel fuel / add coolant |
| LOW OIL PRESSURE | Low oil pressure | Steady LED - indicates a pump engine shut down due to low engine oil pressure | Shutdown | Refer to PUMP TROUBLESHOOTING on page 30 for possible causes |
| Low BackupBatt | Low Backup Battery | RTC backup battery is flat (low). | Warning | |
| NO SPEED SIGNAL | No speed signal | Flashing LED - indicates a pump engine shut down due to a loss of signal from the engine's magnetic pickup | Shutdown | Refer to PUMP TROUBLESHOOTING on page 30 for possible causes |
| OVERCRANK | Overcrank | Steady LED - indicates the pump engine failed to start after three attempts | Shutdown | Refer to PUMP TROUBLESHOOTING on page 30 for possible causes |
| OVERSPEED | Overspeed | Steady LED - indicates shut down due to the pump engine running too fast | Shutdown | Refer to PUMP TROUBLESHOOTING on page 30 for possible causes |
| Oil Press Sd | Oil Pressure Shutdown | Oil pressure is smaller than Oil Press Sd setpoint. | Shutdown | |
| Oil Press Wrn | Oil Pressure Warning | Oil pressure is smaller than Oil Press Wrn setpoint. | Warning | |
| Overload | Overload | The load is greater than the value given by Overload setpoint. | Shutdown | |
| Overspeed | Overspeed | The protection comes active if the speed is greater than Overspeed setpoint. | Shutdown | |
| PREHEAT | Preheat | Steady LED - indicates operation of the engine glow plugs during the engine starting procedure | Info | |
| ParamFail | Parameter Fail | Wrong checksum of parameters. Happens typically after downloading new firmware or changing of the parameter. The controller stays in INIT mode. Check all parameters, write at least one new parameter. | | Check all parameters; write at least one new parameter |
| PickupFault | Pickup Fault | Failure of the magnetic pick-up sensor for speed measurement. | Shutdown | |
| SPN:100 | EngOil Press | John Deere ECU alarm list parameter (SPN shown as FC on bottom left of LCD). | | Refer to John Deere Operator's Manual |
| SPN:102 | Boost Press | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:105 | Intake Temp | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:110 | EngCool Temp | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:1485 | ECU MainRelay | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:175 | EngOil Temp | John Deere ECU alarm list parameter; oil temp always displays #####. | | Refer to John Deere Operator's Manual |
| SPN:629 | Controller #1 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:636 | PositionSensor | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:637 | TimingSensor | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:651 | InjectorCyl#1 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:652 | InjectorCyl#2 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:653 | InjectorCyl#3 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:654 | InjectorCyl#4 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:655 | InjectorCyl#5 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:656 | InjectorCyl#6 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:677 | EngStartRelay | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| Sd IOM fail | IOM Fail | IOM/IGS-PTM module failure. | Shutdown | |
| SprinkIActive | Sprinkler Active | The protection is active if the output Sprinkler is closed. | Warning | |
| Start failed | Start Failed | Unit did not start. | Shutdown | After starter cools two minutes, press FAULT RESET and retry |
| Stop fail | Stop Fail | Unit did not stop. | Shutdown | |
| Ubat | Battery Voltage Out of Limits | Battery voltage is out of limits given by Batt Undervolt setpoints. | Warning | |
| Underspeed | Underspeed | During starting of the engine, when the RPM reaches the value of Starting RPM setpoint, the starter is switched off and the speed of the engine can drop under Start RPM again. Then the underspeed protection becomes active. Protection evaluation starts 5 seconds after start up. | Shutdown | |
| Vgen unbal | Generator Voltage Unbalanced | The generator voltage is unbalanced more than the value of Volt unbal setpoint. | Shutdown | |
| Vgen<, > | Generator Voltage Out of Limits | The generator voltage is out of limits given by Gen <V and Gen <V setpoints. | Shutdown | |
| Wrn ECU Alarm | ECU Alarm Warning | ECU alarm list is not empty. | Warning | View ECU Alarm List; resolve fault and clear code |
| Wrn RA15 fail | RA15 Module Failure Warning | Warning alarm in case of lost connection to IGL=RA15 module. | Warning | |
| WrnMaintenance | Maintenance Warning | The period for servicing is set by the WrnMaintenance setpoint. The protection comes active if the running hours of the engine reach this value. | Warning | Service unit and reset Time to Service to 250 hours |