Home›Engines›Cummins/Onan QSM11

Cummins/Onan QSM11 Engine

The Cummins/Onan QSM11 is a 10.8 L 6-cylinder turbocharged, aftercooled engine rated at 2300 rpm. It powers generator sets from Cummins/Onan, including the CFP11E-F20, DQAD, DQAE and DQAF. It holds 34 L (9.0 gal) of oil and 40 L (10.6 gal) of coolant.

Also known as: Cummins QSM11

Part of the Cummins/Onan QSM11 engine family — 14 variants share parts & fitment.

10.8 L
Displacement
6
Cylinders
2300 rpm
Rated speed
34.0 L
Oil capacity

Engine specifications

Oil capacity34.0 L
Coolant capacity40.0 L
Displacement10.8 L
Cylinders6
AspirationTurbocharged, aftercooled
Rated speed2300 rpm

Troubleshooting

3

Fault codes

CodeMeaning
432Fault Code 432
244Fault Code 244
112Fault Code 112

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.

Common problems

15
  • WEAK BATTERY 232
  • Warning lamp lights. MESSAGE: WEAK BATTERY 232 − WARNING WEAK BATTERY 232
    Fix: Indicates battery voltage drops below 60% of nominal for two seconds, during starting. Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE.
  • Warning lamp lights. MESSAGE: OVERLOAD 330 − WARNING 330
  • Warning lamp lights. MESSAGE: OVERCURRENT 320 − WARNING 320
  • Warning lamp lights. MESSAGE: LOW DC VOLTAGE 230 − WARNING LOW DC VOLTAGE 230
    Fix: Indicates battery voltage is below 10 VDC. a. Discharged or defective battery. Check the battery charger fuse. Recharge or replace the battery. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Check engine DC alternator. Replace engine DC alternator if normal battery charging voltage is not obtained. d. Check battery charge voltage float level if applicable (raise float level).
  • Warning lamp lights. MESSAGE: HIGH DC VOLTAGE 231 − WARNING HIGH DC VOLTAGE 231
    Fix: Indicates battery voltage exceeds 32 VDC. Check voltage float level on battery charger if applicable (lower float level). Check engine DC alternator. Replace engine DC alternator if normal battery charging voltage is not obtained.
  • Warning lamp lights. MESSAGE: EEPROM ERROR 251 − WARNING or 252 − WARNING EEPROM ERROR 251
    Fix: Indicates PCC memory error. Data corruption of noncritical operating parameters.
  • Warning lamp lights. MESSAGE: CUSTOMER FAULT 1 261 − WARNING 261
  • Warning lamp lights. MESSAGE: CUSTOMER FAULT 1 260 − WARNING or GROUND FAULT 260
  • Warning lamp lights. MESSAGE: COOLANT SENDER 213 − WARNING COOLANT SENDER 213
    Fix: Indicates that the resistance of the coolant temperature sender is out of range. Check the resistance of the sender. Resistance should be 500 to 2k ohms.
  • Warning lamp lights. LOW DC VOLTAGE
    Fix: A. Discharged or defective battery. Check the battery charger fuse. Recharge or replace the battery. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Contact an authorized service center if none of the above.
  • UNDER FREQUENCY 313
  • Shutdown or Warning lamp lights. MESSAGE: CM570/ENGINE 263 − SHUTDOWN 263
  • Shutdown or Warning lamp lights. MESSAGE: CM570/ENGINE 262 − WARNING 262
  • Shutdown or Warning lamp lights. ENG COOLANT SENDER
    Fix: Contact an authorized service center.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSM11.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter—1500 hr
Fuel filterEvery 600 Hours or Year 1—600 hr
Oil filter3376592250 hr Amazon eBay $174.95 KuduParts $359.00 FridayParts $368.60
Battery—6000 hr
BeltEvery 6000 Hours or Years' 3—6000 hr
Coolant40.0 L—500 hr
Coolant filterEvery 1500 Hours or Year 2—1500 hr
Oil36.7—6000 hr
Spark plugEvery 1500 Hours or Year 2—1500 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Charge Air PipingCheck8 hrDaily or after 8 Hours; tighten hose clamps to 74 inch-lbs (8 N-m) if necessary
Coolant LevelCheck8 hrDaily or after 8 Hours
Fuel LevelCheck8 hrDaily or after 8 Hours
GensetInspect8 hrDaily or after 8 Hours; check for oil, fuel, cooling and exhaust system leaks; check exhaust system audibly and visually with set running
Oil LevelCheck8 hrDaily or after 8 Hours
Air CleanerCheck50 hrWeekly or after 50 Hours; clean if required; perform more often in dusty conditions
Air cleanerClean50 hrWeekly or after 50 Hours; clean if required. Perform more often in dusty conditions.
Battery Charging SystemCheck100 hr1 moWeekly or after 50 Hours
Coolant heater(s)Check50 hrWeekly or after 50 Hours
Crankcase OilDrain50 hrFirst service — Break-in: drain and replace crankcase oil after the first 50 hours of operation on new generator sets
Exhaust Condensate TrapDrain50 hrWeekly or after 50 Hours
Fuel Filter(s)Drain100 hr1 moWeekly or after 50 Hours; drain 1 cup or more of fuel to remove water and sediment; refer to Cummins engine Operation and Maintenance Manual
Fuel Tank (Water and Sediment)Drain50 hrWeekly or after 50 Hours; drain 1 cup or more of fuel to remove water and sediment
Starting BatteriesCheck100 hr1 moWeekly or after 50 Hours
Anti-freeze and DCA ConcentrationCheck250 hr6 moMonthly or after 100 Hours; refer to Cummins engine Operation and Maintenance Manual
Drive belt tensionCheck100 hr1 moMonthly or after 100 Hours; visually check belt for wear or slippage, replace if hard or brittle.
Fuel tank water and sedimentDrain100 hr1 moMonthly or after 100 Hours; drain 1 cup or more of fuel to remove water and sediment.
Radiator Hoses for Wear & CracksCheck100 hrMonthly or after 100 Hours
Battery electrolyte levelCheck200 hrCheck at least every 200 hours of operation; fill cells to bottom of filler neck.
Coolant FilterChange250 hr6 mo6 Months or after 250 Hours; refer to Cummins engine Operation and Maintenance Manual
Coolant filterReplace250 hr6 moMarine and industrial
Crankcase BreatherClean250 hr6 mo6 Months or after 250 Hours; refer to Cummins engine Operation and Maintenance Manual
Engine wiring harnessInspect250 hr6 mo
Fuel filter (spin-on type)Replace250 hr6 mo
Lubricating oil and filtersChange250 hr6 mo
Sacrificial plug (zinc)Inspect250 hr6 moMarine
Supplemental coolant additive (SCA)Test250 hr6 moAt least twice a year and at every oil drain interval if above 3 units
Air cleaner elementChange500 hrYearly or after 500 Hours; perform more often in dusty conditions.
Cooling systemClean500 hr12 moYearly or after 500 Hours; refer to Cummins engine Operation and Maintenance Manual
Crankcase oil and filterChange500 hr12 moYearly or after 500 Hours. Prime power: change every 6 months or 250 hours. Standby: change oil every 12 months or 250 hours, whichever comes first.
Fuel FiltersChange500 hrYearly or after 500 Hours; refer to Cummins engine Operation and Maintenance Manual
Radiator hosesCheck500 hrYearly or after 500 Hours; check for wear and cracks.
Rupture basin leak detect switchTest500 hr12 moYearly or after 500 Hours; check leak detect switch in sub-base fuel tank of optional enclosure, once a year or as required by safety code.
Overhead setAdjust1500 hr12 moMarine
Air cleaner assembly (engine-mounted)Check1500 hr12 mo
Air leaks, air intake and exhaust systemsInspect1500 hr12 mo
BatteriesCheck1500 hr12 mo
Cooling system hosesInspect1500 hr12 mo
EngineClean1500 hr12 moSteam clean
Engine mounting boltsCheck1500 hr12 moTorque 109 to 136 N·m

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceExhaust pipe clearance from combustible wall/partition12inches (305 mm)
ClearanceFan hub end clearance0.08 MIN / 0.41 MAXmm
ClearanceFloat switch lift below C-clip stop1/8 inch (3 mm)inch (mm)use a feeler gauge
ClearanceFuel line clearance from electrical wiring1/2inch (12.7 mm)minimum
ClearanceFuel line clearance from hot exhaust parts2inch (51 mm)minimum
ClearanceIdler pulley end clearance0.025 MIN / 0.250 MAXmm
ClearanceMPU sensor to flywheel gear toothback it out one quarter turnturnafter sensor just touches gear tooth
ClearanceMinimum fuel level above fuel pump inlet for critical start6inches (150 mm)recommended
ClearanceTurbocharger axial clearance0.038 MIN / 0.089 MAXmm
ClearanceTurbocharger radial bearing clearance0.15 MIN / 0.64 MAXmm
ClearanceVibration isolator top plate to base clearance0.25inch (6 mm)nominal or greater
GapZinc plug erosion limit A (new 51.0 MAX, 19.0 MIN)19.0 MINmm
OtherBMEP at Rated Load249.0psi (1716.8 kPa)Prime
OtherBMEP at Rated Load273.0psi (1882.3 kPa)Standby
OtherBattery specific gravity (charge if below)1.215corrected
OtherBattery specific gravity (fully charged, corrected)1.260corrected to 80 F (27 C)
OtherCompression Ratio16.3:1
OtherExhaust Outlet Size5in. NPT
OtherFrequency RegulationIsochronous
OtherGOV RAMP adjustable range0 through 10seconds
OtherGround Fault Relay current setting5 to 1200amperes
OtherGround Fault Relay time delay setting0 to 1second
OtherMax. Static Restriction (radiator)0.5in H2O (124.5 Pa)
OtherOvercurrent warning110% of rated for 60 secondsgenerator output current
OtherOverload warning105% of standby (or 115% of prime) ratingthree-phase power output
OtherPiston Speed1737.0ft/min (8.8 m/s)
OtherREG VHZ underfrequency roll-off adjustable range1 through 50 (normal range 7 through 21)
OtherRandom Frequency Variation±0.25%
OtherRandom Voltage Variation±0.5%
OtherShort circuit shutdown175% of ratedgenerator output current
OtherVoltage/frequency adjustment range (ADJUST menu)+/- 5%%
PressureAir cleaner cleaning air pressure30psicleaning element
PressureAir cleaner cleaning compressed air30psi (207 kPa)max, clean side, nozzle at least 1 inch (25 mm) away
PressureIdle oil pressure15psi (104 kPa)idle
PressureIdle oil pressure limit (unlabeled third value as printed)8psiidle
PressureIdle oil pressure shutdown limit12psiidle
PressureIdle oil pressure shutdown limit8psi (55 kPa)idle
PressureIdle oil pressure warning limit12psi (83 kPa)idle
PressureIdle oil pressure warning limit15psiidle
PressureLubricating oil pressure minimum at idle69kPaidle
PressureLubricating oil pressure operating range207 to 448kPa
PressureMax Back Pressure (exhaust)41.0in. H2O (10.2 kPa)
PressureMax fuel inlet restriction4in. Hg (13.5 kPa)
PressureMax fuel return restriction2.5in. Hg (8.5 kPa)
PressureMax. Fuel Inlet Pressure10PSI (69 kPa)
PressureMax. Fuel Inlet Restriction4in. Hg. (13.5 kPa)
PressureMax. Fuel Return Restriction2.5in. Hg. (8.5 kPa)
PressureMaximum Air Cleaner Restriction25.0in. H2O (6.2 kPa)
PressureMaximum Inlet Restriction (fuel)4.0in. Hg (101.6 mm Hg)
PressureMaximum Return Restriction (fuel)2.5in. Hg (63.5 mm Hg)
PressureMaximum allowable exhaust back pressure41in. H20
PressureMaximum fuel inlet restriction4in. Hg.
PressureMaximum fuel return restriction2.5in. Hg.
PressureNormal oil pressure207-345kPanormal operation
PressureNormal oil pressure30-50psi (207-345 kPa)
PressureNormal oil pressure shutdown limit20psi (138 kPa)
PressureNormal oil pressure warning limit25psi (172 kPa)
PressureOil pressure shutdown limit20psinormal operation
PressureOil pressure warning limit25psinormal operation
PressureRadiator cleaning compressed air/water35psi (242 kPa)maximum

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantUse a coolant solution as recommended in the Cummins engine Operation and Maintenance Manual40.0 LBalanced coolant mixture of water, antifreeze and coolant additives; drain and replace every year or after 500 hours; 10.5 Gal (40 L) printed; gensets shipped with coolant added
Coolant50/50 antifreeze and water mixtureTMC RP 329 or TMC RP 330; ASTM D6210 (ethylene glycol) or ASTM D6211 (propylene glycol)Fully formulated antifreeze/coolant with precharge of SCA; 50/50 gives -36°C freezing point and 110°C boiling point
CoolantSupplemental Coolant Additive (SCA)DCA4 (phosphate/nitrite/molybdate) or DCA (borate/nitrite)Concentration must not fall below 1.2 or exceed 3 units per gallon of cooling system capacity
Engine oilRefer to the Cummins engine Operation and Maintenance Manual for lubricating oil classification and recommendations/specifications36.7 LGensets are shipped with oil added; check oil level before initial start; 9.7 Gal (36.7 L) printed
Engine oil0W-30 synthetic (API category III)API category IIIAmbient conditions consistently below -25°C; 0W-30 where ambient never exceeds 0°C
Engine oil10W-30 or 5W-30CES 20071 or CES 20076For temperature or cold conditions; easier starting, improved oil flow
Engine oil15W-40CES 20071 or CES 20076 (API CH-4 alternative)Recommended for best engine durability at higher ambient temperature; such as Valvoline Premium Blue or Premium Blue 2000
FuelASTM No. 2 diesel fuelCummins engines normally use ASTM No. 2 diesel fuel. They will also operate on alternate diesel fuels within specifications shown in Cummins engine Operation and Maintenance Manual.
FuelASTM Number 2D dieselASTM Number 2DBelow 0°C, blends of Number 2D and Number 1D acceptable; viscosity must stay above 1.3 cSt at 40°C
FuelDiesel fuelDo not use zinc coated or copper fuel lines with diesel fuel. Fuel connection at engine should be made with an approved flexible line.
FuelNumber 2 diesel fuelDirect injection; fuel filter; automatic electric fuel shutoff
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz. (81 ml)Generator end bearing lubricant; -22F to +248F (-30C to +120C). Grease equally divided between bearing, bearing cap cavity, and bearing cartridge cavity.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

35
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.WarningNo corrective action required. When ground is removed from the input, the set returns to normal speed and voltage; oil pressure warning and shutdown trip points are reset automatically.
102EMERGENCY STOPLocal or remote Emergency Stop.ShutdownReset only at PCC front panel: pull button out, switch to Off, press Reset.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period then follow 201 Low Oil Pressure procedure. If engine can be stopped, follow 201 procedure. To check oil pressure, access Oil Pressure menu prior to clearing the fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset and restart. Contact service center.
204OIL PRES SENDERIndicates that the engine oil pressure sender is not functioning correctly.WarningCheck that the engine oil pressure sender is properly connected. Contact an authorized service center.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70 F (21 C) or lower. Below 40F (4C) ambient the warning may occur even though coolant heaters are operating.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply (blown fuse or disconnected heater cord), check for low coolant level and replenish, look for coolant leakage points and repair. Contact an authorized service center if none of the above.
211HIGH COOLANT TEMPIndicates engine has begun to overheat and coolant temperature has risen to an unacceptable level: (215 F − standby / 207 F − primary).WarningReduce load if possible; check air inlets/outlets and remove obstructions.
212HIGH COOLANT TEMPIndicates engine has overheated (coolant temperature above shutdown trip point: 223 F − standby / 215 F − primary) or the coolant level is low.ShutdownAllow to cool; check coolant level, airflow, fan belt. Reset and restart. Contact service center if unresolved.
213ENG COOLANT SENDERIndicates that the resistance of the coolant temperature sender is out of range.WarningContact an authorized service center.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point. (Shutdown will not occur if generator set is in Idle mode − low coolant warning only.)WarningAllow to cool; check and replenish coolant; repair leaks; reset and restart.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point. (Shutdown will not occur if generator set is in Idle mode − low coolant warning only.)ShutdownAllow to cool; check and replenish coolant; repair leaks; reset and restart.
220MAG PICKUPMag pickup speed indication not sensed or does not match genset output frequency.ShutdownRestart and check RPM on the digital display. Contact an authorized service center.
221FAIL TO CRANKPossible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board; clean and tighten battery cable connections; recharge or replace the battery.
222OVERCRANKPossible fuel system problem.ShutdownCheck fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filters. Reset and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed (115% +/-1% of nominal).ShutdownRefer to engine service manual to troubleshoot fuel system; use InSite service tool to troubleshoot CM570 module.
230LOW DC VOLTAGEIndicates battery voltage is below 24 VDC.WarningCheck the battery charger fuse. Discharged or defective battery: recharge or replace. Check for poor battery cable connections; clean terminals and tighten all connections. Contact an authorized service center if none of the above.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningContact an authorized service center.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningSee Warning message 230, LOW DC VOLTAGE.
240LOW FUEL-DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
241LOW FUELIndicates fuel supply is running low.WarningCheck fuel supply and replenish as required.
250EEPROM ERRORPCC memory error; data corruption of critical operating parameters.ShutdownPerform the initial start setup procedure; if the genset shuts down on the same EEPROM ERROR message, replace the digital board (A32).
251EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningPerform the adjustment procedures; if same error, perform calibration procedures; if same error, replace digital board (A32).
252EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningVerify values or choices selected and repeat the save operation; if same error, replace digital board (A32).
260CUSTOMER FAULT 1When this customer defined input is closed to ground, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. (Default message; editable for customer site requirements.)WarningThese fault functions can be programmed to initiate a shutdown or a warning. Contact an authorized service center.
261GROUND FAULTWhen this customer defined input is closed to ground, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. (Default message; editable for customer site requirements.)WarningThese fault functions can be programmed to initiate a shutdown or a warning. Contact an authorized service center.
262CM570/ENGINEIndicates that the engine control module (CM570) is not properly operating.WarningContact an authorized service center.
263CM570/ENGINEIndicates that the engine control module (CM570) is not properly operating.ShutdownContact an authorized service center.
301HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal, or 110% of nominal for 10 seconds.ShutdownDetermine if output voltage the control sees is low or high; isolate regulator module A37, A31, A32, A36, A34, or A33.
303LOW AC VOLTAGEOne or more phase voltages dropped below 85% of nominal for 10 seconds.ShutdownContact an authorized service center.
313UNDER FREQUENCYIndicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown a Load Dump signal is initiated.ShutdownLoad Dump signal initiated five seconds before shutdown. Contact an authorized service center.
320OVERCURRENTIndicates that generator output current has exceeded 110% of rated for 60 seconds.WarningContact an authorized service center.
321OVERCURRENTOutput current exceeded 110% of rated; PCC time/current calculation initiated shutdown.ShutdownContact an authorized service center.
322SHORT CIRCUITIndicates that generator output current has exceeded 175% of rated.ShutdownContact an authorized service center.
330OVERLOADThree-phase output exceeds 105% of standby (or 115% of prime) rating.WarningLoad Dump activated after 5 seconds; OVERLOAD warning after 60 seconds. Contact an authorized service center.
335REVERSE POWERIndicates improper CT or PT phasing. (Non-parallel units only.)ShutdownContact an authorized service center.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjust Start and Stop Delays adjustment
  1. Press the button next to the word ADJUST in the Main Menu. The VOLTAGE submenu will appear.
  2. Press the button next to the '>>' to move through the VOLTAGE and FREQUENCY submenus to the START DELAY submenu.
  3. Use the buttons next to the '⇑' and '⇓' symbols to set the start delay. The start delay adjustment range is 0 to 300 seconds.
  4. From the START DELAY submenu, press the button next to the '>>' to move to the STOP DELAY submenu.
  5. Use the buttons next to the '⇑' and '⇓' symbols to set the stop delay. The stop delay adjustment range is 0 to 600 seconds.
  6. From the STOP DELAY submenu, press the button next to the '>>' to move to the SAVE/EXIT submenu. Select SAVE to save your changes.
  7. At the CHANGES SAVED submenu, select EXIT to return to the Main menu.
Adjusting Start/Stop Delays (PCC Adjust Menu) adjustment
  1. Press button next to ADJUST in Main Menu to display VOLTAGE submenu
  2. Press button next to >> to move through FREQUENCY submenu to STOP DELAY submenu
  3. Use buttons next to arrows to set start delay, range 0 to 300 seconds
  4. Use buttons next to arrows to set stop delay, range 0 to 600 seconds
  5. Press >> to move to SAVE/EXIT submenu and select SAVE to retain changes, then EXIT
Axial Alignment Procedure (Aligning Generator with Engine) adjustment

Tools: Dial indicator holding device with magnetic base or clamp

  1. Fasten a dial indicator holding device to skid base, engine block, or generator shell.
  2. Position the indicator sensor point on the generator shaft hub.
  3. Bar the engine over in a clockwise rotation through a couple of rotations.
  4. Record indicator readings in eight equally spaced points around the shaft diameter.
  5. To correct out-of-tolerance T.I.R., remove drive disc capscrews and mark discs and flywheel.
  6. Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
  7. Reinstall capscrews and retorque; recheck alignment.
  8. If T.I.R. is unchanged, rotate discs 30, 60, or 90 degrees from original location.
Converting Day Tank Controller from 120 VAC to 240 VAC adjustment
  1. Remove jumpers between TB1-5/TB1-6 and TB1-7/TB1-8; connect two jumpers between TB1-6 and TB1-7
  2. Move selector switch S103 on control PCB to down position for 240 VAC
  3. If equipped with transformer, remove jumpers between H1/H3 and H2/H4 and connect two jumpers between H2 and H3
Converting Day Tank Controller from 240 VAC to 120 VAC adjustment
  1. Remove two jumpers between TB1-6 and TB1-7; connect one between TB1-5/TB1-6 and one between TB1-7/TB1-8
  2. Move selector switch S103 on control PCB to up position for 120V
  3. If equipped with transformer, remove jumpers between H2/H3 and connect H1/H3 and H2/H4
Drive Belt, Alternator - Adjust adjustment

⚠ Do not roll a belt over the pulley or pry it on with a tool.

Tools: ST-1293

  1. Loosen the adjusting screw.
  2. Loosen the adjustment link locking capscrew.
  3. Loosen the pivot capscrew and nut.
  4. Measure belt tension with gauge ST-1293.
  5. Turn adjusting screw clockwise to tighten belt to specification.
  6. Tighten adjusting screw locknut.
  7. Tighten adjustment link locking capscrew to 80 N·m.
  8. Tighten pivot capscrew and nut to 47 N·m.
Overhead Set - Adjust Valves and Injectors adjustment

⚠ All valve and injector adjustments must be made when the engine is cold (below 60°C).

Tools: 3376592, ST-669, feeler gauges

  1. Remove crankcase breather tube and rocker lever cover.
  2. Rotate accessory drive to the A valve set mark aligned with pointer.
  3. Loosen injector adjusting screw locknut; bottom the plunger 3 or 4 times.
  4. Back out adjusting screw two flats (120 degrees); tighten locknut to 61 N·m.
  5. Loosen intake and exhaust valve adjusting screw locknuts.
  6. Insert correct feeler gauge between crosshead and rocker lever pad.
  7. Tighten adjusting screw (torque wrench method 1 N·m) and hold.
  8. Tighten valve locknut to 61 N·m (47 N·m with adapter); recheck feeler gauge.
Voltage and Frequency Adjustment adjustment

⚠ Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage. Calibration and adjustment must be performed by technically qualified personnel only.

Tools: Calibrated RMS multimeter (Fluke 87 or 8060A)

  1. With the genset OFF, attach a calibrated frequency/voltmeter to the AC output from L1 to L2.
  2. Select ADJUST from the Main Menu to display the VOLTAGE adjust menu.
  3. Start the genset and allow it to reach normal operating speed.
  4. Adjust VOLTAGE so that the calibrated voltmeter reads the desired voltage.
  5. Select the Frequency adjust menu and verify/adjust frequency to the desired value.
  6. Select EXIT if no adjustment was made; if an adjustment was made, SAVE then EXIT.
Generator/PCC Control Isolation Procedure diagnostic

⚠ HAZARDOUS VOLTAGE. Touching uninsulated parts inside the control housing and power output boxes can result in severe personal injury or death.

⚠ This test involves unregulated excitation; make sure all loads are disconnected and all faults cleared.

Tools: True RMS meter, Jumper leads

  1. Throw the line circuit breaker OFF and shut down the set.
  2. Remove plug 10 from connector 10 of the voltage regulator output module (A37).
  3. Prepare to measure output voltage across generator terminals while the set is running.
  4. Connect jumpers from a 12 volt battery to X (Field +) 10-6 red and XX (Field -) 10-3 brown.
  5. Check polarity again; opposed polarity makes this test inconclusive.
  6. Start the set and connect the battery negative (-) to the XX lead.
  7. Rated or higher balanced voltage indicates generator circuitry is probably okay.
  8. If unbalanced, troubleshoot main stator first; if uniformly low, troubleshoot exciter and field circuits first.
Ground Fault Alarm Relay Test diagnostic
  1. Verify that the N-G Fault Indicator on the GFR is not lit. If lit, it indicates that the bonding jumper circuit (neutral to ground) is open. If genset does not require bonding jumper, a bonding jumper
  2. Move the control switch to the Run position.
  3. Press the TEST switch on the ground fault relay.
  4. Verify that the control panel warning message is displayed and the Fault Indicator (>I) on the GFR is lit.
  5. Reset the control panel fault (this will also reset the ground fault relay).
Rupture Basin Leak Detect Switch Test diagnostic
  1. Remove the pipe fitting/switch assembly from the rupture basin tank.
  2. Move the O/Manual/Auto switch to the MANUAL position.
  3. Activate leak detect switch (move float upward).
  4. Check control display for Rupture Basin fault message.
  5. If no indication of fault, repair defective circuit.
  6. Apply thread sealant to pipe fitting and install switch assembly.
Testing the Float Switch Assembly diagnostic

Tools: Ohmmeter, Feeler gauge

  1. Remove the fuel pump control cover, disconnect the wiring jack and unscrew the assembly from the top of the day tank.
  2. With an ohmmeter, test for continuity between each pair of colored leads while holding the assembly vertical.
  3. Replace the assembly if any switch is open (all readings should be zero).
  4. Lift each float in turn to 1/8 inch (3 mm) below the C-clip stop and test for continuity.
  5. Replace the assembly if any switch does not open (all readings should be infinity).
  6. Use pipe thread sealant when replacing the assembly.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
3-pole ATS system groundinggenerator neutral to ATS, not bonded to ground at generator
4-pole ATS system groundinggrounding electrode conductor and bonding jumper connect generator neutral to ground
Alarm Relay K14 contactsTB1 (jumper wire required for K14 relay option)3-pole double-throw, same ratings as run relays; energized by any genset warning or shutdown
B+ Input (RUN signal)Blue (A37 J7)Voltage regulator output module A37 J7 wiring connections (control)
CT21 (+) InWhite (A36 J9)PT/CT Board (A36) J9 wiring connections
CT21 (common) InGray (A36 J9)PT/CT Board (A36) J9 wiring connections
CT22 (+) InGrn/Ylw (A36 J9)PT/CT Board (A36) J9 wiring connections
CT22 (common) InBlack (A36 J9)PT/CT Board (A36) J9 wiring connections
CT23 (+) InPurple (A36 J9)PT/CT Board (A36) J9 wiring connections
CT23 (common) InBlue (A36 J9)PT/CT Board (A36) J9 wiring connections
Current Transformers CT21/CT22/CT23U (A phase)/V (B phase)/W (C phase) load leadsdot on CT must face toward generator; dual secondaries, wire 1 to pin 1, wire 2/3 to pin 2 (high voltage gensets) or pin 3 (low voltage gensets)
Gen. Common InBrown (A36 J9)PT/CT Board (A36) J9 wiring connections to AC harness
Ground InputPurple (A37 J7)Voltage regulator output module A37 J7 wiring connections (control)
Phase A PMG powerGreen (A37 J10)Voltage regulator output module A37 J10 wiring connections (power)
Phase B PMG powerYellow (A37 J10)Voltage regulator output module A37 J10 wiring connections (power)
Phase C PMG powerOrange (A37 J10)Voltage regulator output module A37 J10 wiring connections (power)
Regulator Drive (+) InputGray (A37 J7)Voltage regulator output module A37 J7 wiring connections (control)
Regulator Drive (-) InputWhite (A37 J7)Voltage regulator output module A37 J7 wiring connections (control)
Run Relay K11/K12/K13 contactsTB13-pole double-throw, rated 10A at 28VDC or 120VAC 80%PF, 6A at 240VAC 80%PF, 3A at 480/600VAC 80%PF; energized when genset receives start signal
Start inGrn/Yel (A37 J7)Voltage regulator output module A37 J7 wiring connections (control)
Start solenoidBlack (A37 J7)Voltage regulator output module A37 J7 wiring connections (control)
X (Field +) OutputRed (A37 J10)Voltage regulator output module A37 J10 wiring connections (power); X = red wire of connector 10-6
XX (Field -) OutputBrown (A37 J10)Voltage regulator output module A37 J10 wiring connections (power); XX = brown wire of connector 10-3
ACT1 - U load leadsCT1Route the appropriate leads through each CT; dot must face toward the generator
AGen. A InYellow (A36 J9)PT/CT Board (A36) J9 wiring connections to AC harness
BCT2 - V load leadsCT2Route the appropriate leads through each CT; dot must face toward the generator
BGen. B InOrange (A36 J9)PT/CT Board (A36) J9 wiring connections to AC harness
CCT3 - W load leadsCT3Route the appropriate leads through each CT; dot must face toward the generator
CGen. C InRed (A36 J9)PT/CT Board (A36) J9 wiring connections to AC harness

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan QSM11 family

98
Part #DescriptionCategory
140-2636Element, Filter (Outer)Air filter
140-2637Cleaner, Air (Includes Elements)Air filter
140-2638Element, Filter (Inner)Air filter
140-3288-02Cleaner, AirAir filter
RU3220Air CleanerAir filter
2874862Alternator 12VAlternator
2874863Alternator 24VAlternator
3037425BeltBelt
A40-TB1-8JUMPER WIREBelt
WF2072Coolant FilterCoolant filter
49c00185Data LinkData link
300-5815Control, Pump - ECMECM / ECU
12000187Engine position sensorEngine position sensor
13200060Engine Speed Control SwitchEngine speed control switch
33200082Engine Stop ButtonEngine stop button
V70509Lube OilFluid
12000183Fuel filterFuel filter
3376807Fuel filterFuel filter
FS1000Fuel FilterFuel filter
15600049Fuel Shutoff ValveFuel shutoff valve
19400715OEM Interface 21-Pin Harness ConnectorHose
19400718OEM Interface 24-Pin Harness ConnectorHose
415-0566-15Pipe, SuctionHose
503-0098Hose, Oil Drain - Bulk (Order By The Foot - 3 Feet Required)Hose
503-0189Clamp, HoseHose
505-0172Nipple, Close (2 x 2")Hose
518-0548-01Clamp, HoseHose
38200567Idle Adjustment SwitchIdle adjustment switch
3375049Oil Filter WrenchOil filter
3397929Oil filter wrenchOil filter
LF9001Lube FilterOil filter
LFg9001Valvoline® Premium Blue®Oil filter
12000186Oil pressure and temperature sensorOil pressure and temperature sensor
13200087Oil Pressure GaugeOil pressure gauge
05200182Flywheel ring gear sensorService part / kit
102-1335Plug, Oil DrainService part / kit
12000184Rail pressureService part / kit
12000188Freon compressor mounting location.Service part / kit
155-2409-04Elbow, ExhaustService part / kit
155-3510Elbow, MufflerService part / kit
155-3540SilencerService part / kit
155-4022MufflerService part / kit
155-4062MufflerService part / kit
159-1208-01Cap, FuelService part / kit
159-1299Bracket, MountingService part / kit
159-1573-01Tank, Fuel 300 GallonService part / kit
19400716Hard-CoupledService part / kit
19400734Intermediate Speed ControlService part / kit
19800802Multiple Unit SynchronizationService part / kit
307-2621-02Relay, Start Solenoid (K4)Service part / kit
3305070Heater, 240VService part / kit
3315033Heater, 120VService part / kit
338-4426Harness, WiringService part / kit
3885910Red Paint, Spray canService part / kit
415-0727Tank, Day (19 Gallons)Service part / kit
492000038Operation and Maintenance NanualService part / kit
49800897Intermediate Speed ControlService part / kit
49801587Electronic Fan ClutchService part / kit
502-1259Coupler, Coolant HeaterService part / kit
504-0252Valve, Solenoid - FuelService part / kit
625-2141-01Control, Fuel TankService part / kit
8210G4-12VDC1" 12V solenoidService part / kit
8210G4-24VDC1" 24V solenoidService part / kit
98200038Engine Steam CleaningService part / kit
A40-TB1-1B+Service part / kit
A40-TB1-11(COMMON ALARM)Service part / kit
A40-TB1-12(B-)Service part / kit
A40-TB1-30COMMON ALARMService part / kit
A40-TB1-31(COMMON ALARM)Service part / kit
C2800Fleetguard® refractometerService part / kit
CC2800Fleetguard refractometerService part / kit
E204747Coolant heater 240/480V 6420W 1PHService part / kit
LE9o01Cummins Engine Company, Inc.Service part / kit
3376326pulley pusher (2)Pulley pusher
3377401pulley pusher adapter (1)Pulley pusher adapter
12000180Fuel inlet to pumpPump
12000185Power steering pump mounting locationPump
149-2699-01Pump, Fuel - Assembly 2 GPMPump
149-2710-01Pump, Fuel - With Motor 2 GPMPump
399-0117Pump, Fuel TransferPump
399-0121Kit, Repair - Fuel Tank PumpPump
39200434Governed rpmRpm governor
151-0411Pickup, MagneticSensor
193-0432Sender, Oil Temperature (S2 Engine Block, E4 Oil Pan)Sensor
193-0444Sender, Oil Pressure (S1)Sensor
308-0913-06Switch, FloatSensor
309-0269Sender, Temperature-Lo EngineSensor
309-0701-01Switch, Level - High and LowSensor
309-0702-01Switch, Level - Rupture BasinSensor
415-0565-15Gauge, Liquid LevelSensor
420-0609-01Gauge - Fuel LevelSensor
13200052Slow Idle FeatureSlow idle feature
2871254Starter 12VStarter
3103916Starter 24VStarter
3200069STOP CHECK!Stop check
43200086Tachometer w/Hour MeterTachometer
190-0200ThermostatThermostat
43200085VoltmeterVoltmeter

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan QSM11?

The Cummins/Onan QSM11 engine has an oil capacity of 34.0 liters.

What is the displacement of the Cummins/Onan QSM11?

The Cummins/Onan QSM11 has a displacement of 10.8 liters with 6 cylinders.

Which generators use the Cummins/Onan QSM11 engine?

The Cummins/Onan QSM11 powers 5 generator set(s), including Cummins/Onan CFP11E-F20, Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF, Cummins/Onan QSM1i.

How often should you change the oil in the Cummins/Onan QSM11?

The Cummins/Onan QSM11 oil change interval is every 6000 hours.

What is a common problem with the Cummins/Onan QSM11 engine?

A commonly reported issue on generators using the Cummins/Onan QSM11 is: WEAK BATTERY.