| 12 | Overvoltage | Instantaneous Fault: AC voltage S1-S2 greater than 300 VAC. Delayed Fault: AC voltage line-to-line greater than 268 VAC but less than 300 VAC for 3 continuous seconds. | Shutdown | Measure AC voltage at the circuit breaker and pins P1-34/P1-35. Cycle loads. Reseat P1. Measure field, quadrature and main winding resistance. |
| 13 | Undervoltage | AC voltage 240 line-to-line is less than 216 VAC for 5 continuous seconds. | Shutdown | Measure AC voltage and frequency. Balance loads within 10% line-to-line. Reseat P1. Measure winding resistance and check brush alignment. |
| 14 | Overfrequency | Instantaneous Fault: Frequency greater than 72 Hz. Delayed Fault: Frequency greater than 66 Hz but less than 72 Hz for 6 continuous seconds. | Shutdown | Measure AC current and frequency. Check exhaust, fuel supply, governor actuator, demand regulator and throttle plate. Measure winding resistance and check brush alignment. |
| 143 | Engine Oil Pressure Low | Engine oil pressure is below the low oil pressure warning threshold. | Warning | Check the oil level and add oil if necessary. Inspect the engine and surrounding area for external oil leaks; contact your local dealer if a leak is present. |
| 1438 | Fail to Crank | The engine failed to crank after the generator control received a start signal. | Shutdown | Verify battery voltage is at least 12 VDC. Charge or replace the battery as necessary. |
| 146 | Engine Coolant Temperature Above Normal | Engine coolant temperature has exceeded 225 °F (107.2 °C) for greater than 5 seconds. | Warning | Reduce loads or recirculation of discharge air in elevated ambient; inspect/clear enclosure air intake and discharge blockage; check and add coolant; clean the radiator core; inspect and replace a broken fan belt. |
| 1472 | High AC Current | The generator output current has exceeded at least 150% of rated current. | Shutdown | Reduce the generator set load by powering off unnecessary household appliances. |
| 15 | Underfrequency | Frequency less than 54 Hz (for the 60 Hz model) for 8 continuous seconds. | Shutdown | Measure AC current, frequency and load capability. Check air filter, exhaust, fuel supply, governor and ignition. Measure winding resistance and check brush alignment. |
| 151 | Engine Coolant Temperature High | Engine coolant temperature has exceeded the alarm (shutdown) threshold for high coolant temperature. | Shutdown | Reduce loads or recirculation of discharge air in elevated ambient; clear enclosure air intake and discharge blockage; check and add coolant; clean the radiator core; inspect and replace a broken fan belt. |
| 155 | Intake Manifold Temperature High | Engine intake manifold temperature has exceeded 203 °F (95 °C) for greater than 10 seconds. | Shutdown | Reduce loads or recirculation of discharge air in elevated ambient; clear enclosure air intake and discharge blockage; check and add coolant; clean the radiator core; inspect and replace a broken fan belt. |
| 19 | Governor Actuator Shutdown | Controller sensed governor actuator circuit is open or shorted. | Shutdown | Measure and verify governor actuator resistance (2.8 Ohms ±5%). Verify governor wiring to the control. Replace if necessary. |
| 197 | Coolant Level Low | Coolant level sensor signal is showing a low coolant level for greater than 10 seconds. | Warning | Remove radiator cap and check that coolant is up to the required level. |
| 2 | Low Oil Pressure Fault | Continuous ground (greater than or equal to 3 seconds) at the generator set control for oil pressure input. The switch opens the control circuit with pressure. | Shutdown | Measure the oil level; disconnect the oil pressure switch and measure continuity from P1-6 and GND; verify switch operation; measure oil pressure with a mechanical gauge; repair or replace relief valve and oil pump if necessary. |
| 22 | Governor Actuator Overload | Maximum governor output (PWM) for 10 continuous seconds. | Shutdown | Measure AC current. Check air filter, fuel supply, intake manifold and gaskets, exhaust and ignition. Verify the actuator function and check the governor linkage. |
| 27 | Voltage Sense Lost | The generator set frequency is greater than 40 Hz and voltage sensed is less than 5 VAC on one or both lines. | Shutdown | Measure the AC voltage. Reseat P1. Measure field, quadrature and main winding resistance. Check brush alignment. |
| 29 | High Battery Voltage | DC voltage to controller greater than 19 VDC. | Shutdown | Measure DC voltage at the battery, at the generator set and at connector P1. Measure DC voltage with the battery charger turned on and diagnose the faulty charger. |
| 32 | Low Cranking Speed Sense | Quadrature frequency is less than 1 Hz (engine RPM is less than 180) for 3 continuous seconds after pressing start. | Shutdown | Check battery and connections. Verify engine and alternator rotation. Check J1 pins. Measure DC voltage at the starter. Check air filter, exhaust, fuel supply and ignition. |
| 35 | Control Card Failure | EEPROM (programming variables) error during self-test. | Shutdown | Replace the control. |
| 36 | Generator Set Stopped Without Fault Condition | RPM is less than 500 and sense voltage S1-S2 is at 0 VAC and no other fault condition occurred. | Shutdown | Verify engine and alternator rotation. Check air filter, exhaust, fuel supply, governor and ignition. Measure winding resistance. |
| 37 | Invalid Set Configuration | Generator set control configuration does not meet any valid configuration. | Shutdown | Using the display, reset and save the generator set configuration. If correct and the fault will not clear, replace the control. |
| 4 | Overcrank | The generator set control did not sense alternator quad winding frequency after cycle crank (30 seconds of cranking and 15 seconds between each crank attempt for a total of 3 crank attempts). | Shutdown | Check fuel supply, air/fuel mixture, ignition system, starter, battery and wiring. Check air filter and exhaust. Measure quad voltage during cranking and winding resistances. |
| 415 | Engine Oil Pressure Low | Engine oil pressure is below 26 psig (180 kPa) for greater than 10 seconds. | Shutdown | Check the oil level and add oil if necessary. Inspect the engine and surrounding area for external oil leaks; contact your local dealer if a leak is present. |
| 421 | Engine Oil Temperature High | The control has detected the engine oil temperature has exceeded the warning threshold. | Warning | Reduce loads or recirculation of discharge air in elevated ambient; inspect/clear enclosure air intake blockage; check and add coolant. |
| 43 | Processor Fault | RAM (programming variables) error during self-test. | Shutdown | Replace the control as necessary. |
| 441 | Battery Voltage Low | Battery voltage low. | Warning | Inspect the battery cable connections for corrosion and for loose connections. |
| 45 | Speed Sense Fault | While running, the quadrature frequency dropped to 0 Hz for 1 continuous second. | Shutdown | Inspect and clean slip rings. Measure quadrature winding resistance between P1-2 and P1-3. Check harness continuity. Measure frequency and droop. |
| 46 | Generator Set Overload | The total generator set load is above 105% of rated. | Shutdown | Measure the AC current and voltage while running with all connected loads. Identify faulty or short cycling loads and reduce loads as necessary. |
| 488 | Intake Manifold Temperature High | Engine intake manifold temperature has exceeded 185 °F (85 °C) for more than 90 seconds. | Warning | Reduce loads or recirculation of discharge air in elevated ambient; clear enclosure air intake and discharge blockage; check and add coolant; clean the radiator core; inspect and replace a broken fan belt. |
| 5134 | Unknown Shutdown at Idle | The generator set failed to start. | Shutdown | Check that the manual shutoff valves are open (fuel supply issue). |
| 5569 | Engine Combustion | Rapid rate of increase of intake manifold temperature detected. | Shutdown | Inspect hose couplings between compressor outlet and intake manifold; inspect the turbocharger; inspect the mixer; check the TMAP sensor value with GCP Display service tool or InPower; inspect the engine harness and connector pins (resistance should be 5 ohms or less) and repair or replace as necessary. |
| 76 | Alternator Over Temp | The temperature at the alternator is too high. The high temperature switch opens between 197 - 209 °F (91.5 - 98.5 °C). An open condition on this circuit triggers the fault. | Shutdown | Verify the air inlet and air outlet panels are not obstructed. Measure the temperature sensor wiring (P1-33 to GND) for continuity. Inspect the cooling fan. |