HomeControllersVR3 automatic voltage regulator

VR3 automatic voltage regulator Controller

The VR3 automatic voltage regulator is a generator-set controller. It is used on generator sets from Caterpillar, including the SR4.

1
Generator sets
Caterpillar
Brand
650–650 kW
Power range

Generator sets using this controller

1

Engines paired with this controller

1

Troubleshooting

7

Symptoms & remedies

SymptomCauseRemedy
Overcrank Protection - If the engine fails to start in a preprogrammed amount of time, the ECM will halt the starting sequence and flash the Overcrank LED.Another attempt to start the engine cannot be made without first going to the offlreset position on the engine control switch (ECS).
The engine will be shutdown by means of the air and fuel control and a diagnostic code will be displayed.If the ECM loses its magnetic pickup signalRefer to the Service Manual Module SENR3535, which is included in the Service Manual SENR7958 for diagnostic fault codes.
The engine will be shutdown by means of the fuel control and a diagnostic code will be displayed.If the signal from the engine mounted oil pressure/temperature transducer module is lost or unreadableRefer to the Service Manual Module SENR3535, which is included in the Service Manual SENR7958 for programming instructions and diagnostic fault codes.
The engine will be shutdown by means of the fuel control and the Low Oil Pressure LED will flash.If the engine oil pressure drops below the low oil pressure setpoint
The engine will shutdown by means of the fuel control and the High Coolant Temperature LED will flash.If the engine coolant temperature exceeds the high coolant temperature setpoint
The engine will shutdown by means of the fuel control and the Overspeed LED will flash.If the engine speed exceeds the overspeed setpointLower the overspeed setpoint to 75% of its original value while the overspeed verify switch is depressed. This allows the overspeed circuit to be tested while a generator set is operating at rated speed.
The red fault shutdown indicator flashes when the GSC detects a fault that is a shutdown condition.Refer to SENR5809 for fault code descriptions.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.