HomeControllersQc1001

Qc1001 Controller

The Qc1001 is a generator-set controller. It is used on generator sets from Atlas Copco, including the QAS 30, QAS 325 Volvo and QAS 38.

5
Generator sets
Atlas Copco
Brand
35–35 kW
Power range
Diesel
Fuel

Generator sets using this controller

5
Atlas Copco QAS 30Atlas Copco QAS 325 VolvoAtlas Copco QAS 38

Engines paired with this controller

2

Troubleshooting

17

Symptoms & remedies

SymptomCauseRemedy
After being excited alternator does not excite- Connections are interrupted.Check connection cables as per attached drawings.
Alternator does not excite- Blown fuse.Replace fuse.
Current too high, power factor lower than 0.8; speed lower than 10 % of rated speed- Failed regulator.Substitute regulator.
Failed regulatorSubstitute regulator.
High voltage at no load- Voltage potentiometer out of setting.Reset voltage potentiometer.
Higher than rated voltage at load- Voltage potentiometer out of setting.Reset voltage potentiometer.
Insufficient residual voltageIncrease the speed by 15 %.
Loose sensing wires on AVRCheck sensing wires on AVR.
Low voltage at no load- Voltage potentiometer out of setting.Reset voltage.
Lower than rated voltage at load- Voltage potentiometer out of setting.Reset voltage potentiometer.
No residual voltageFor an instant apply on the + and – terminals of the electronic regulator a 12 V battery voltage with a 30 Ω resistor in series respecting the polarities.
Not enough power- Restriction in a fuel pipe. - Fault in fuel lift pump. - Dirty fuel filter element. - Restriction in air filter/cleaner or induction system. - Air in fuel system.
Regulator out of settingRegulate stability of regulator by acting on “STABILITY” potentiometer.
Rotating bridge failure- Check diodes, disconnect cables.
The engine does not start or is difficult to start- Starter motor turns engine too slowly. - Fuel tank empty. - Fault in fuel control solenoid. - Restriction in a fuel pipe. - Fault in fuel lift pump. - Dirty fuel filter element. - Air in fuel system. - Fault in atomisers. - Cold start system used incorrectly. - Fault in cold start system. - Restriction in fuel tank vent. - Wrong type or grade of fuel used. - Restriction in exhaust pipe.
The starter motor turns the engine too slowly- Battery capacity too low. - Bad electrical connection. - Fault in starter motor. - Wrong grade of lubricating oil.
Unstable voltage- Speed variation in engine.Check regularity of rotation.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.