HomeControllersPowerCommand PCC2100 CAN

PowerCommand PCC2100 CAN Controller

The PowerCommand PCC2100 CAN is a generator-set controller. It is used on generator sets from Cummins/Onan, including the DQHAB.

1
Generator sets
Cummins/Onan
Brand
300–300 kW
Power range
Diesel
Fuel

Generator sets using this controller

1

Engines paired with this controller

1

Troubleshooting

56

Fault codes

CodeMeaning
1123Shutdown After Battle Short
1124Delayed Shutdown
1131Battle Short Active
121Speed Signal Lost
1244Engine Normal Shutdown
1311Customer Inputs #1
1312Customer Inputs #2
1317Customer Inputs #3
1318Customer Inputs #4
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
141Oil Pressure Sensor Low
1416Fail to Shutdown
1417Power Down Failure
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1434Remote Emergency Stop
1435Low Coolant Temperature
1438Fail to Crank
144Coolant Temperature Sensor High
1442Weak Battery
1443Battery Failed
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage
1448Under Frequency
1449Over Frequency
145Coolant Temperature Sensor Low
146Pre-High Cool Temp
1461Loss of Field
1466Modem Failure
1468Network Error
1469Speed/Hz Match
1471Over Current
1472Over Current
151High Coolant Temp
197Low Coolant Level
2335Excitation Fault
2336Memory Error
234Overspeed
2341High Control Temperature
2342Too Long in Idle
235Low Coolant Level
2967Governor Fault
2968AVR Fault
2969LON Failure
2972Field Overload
359Fail to Start
415Low Oil Pressure
441Low Battery Voltage
442High Battery Voltage

Symptoms & remedies

SymptomCauseRemedy
Engine runs roughFault Code 203 - Fuel System FaultInspect fuel filter and injectors, clean or replace as needed
Generator does not startFault Code 101 - Starter Motor FaultCheck starter motor connections and replace if necessary
Generator produces low voltage outputFault Code 304 - Alternator Winding FaultCheck alternator windings for damage and repair or replace if necessary

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.