Power Zone Autolight (optional) Controller

The Power Zone Autolight (optional) is a generator-set controller. It is used on generator sets from Generac, including the MLTS Export Power Option and MLTS Standard Unit.

2
Generator sets
Generac
Brand
Diesel
Fuel

Generator sets using this controller

2
Generac MLTS Export Power OptionGenerac MLTS Standard Unit

Engines paired with this controller

1

Troubleshooting

21

Symptoms & remedies

SymptomCauseRemedy
ALow engine oil pressure or high engine coolant temperatureSee General Troubleshooting —low oil pressure & high engine coolant temperature.
A+CEngine overspeed or engine underspeed1. Check connection on W terminal of DC Charge Alternator—WH/VI to pin-9 on the Power Zone controller. 2. Inspect function of DC charge alternator. 3. Inspect tension of DC charge alternator drive belt. 4. Contact Generac Mobile.
B+CLoss of speed1. Check connection on W terminal of DC Charge Alternator—WH/VI to pin-9 on the Power Zone controller. 2. Inspect function of DC charge alternator. 3. Inspect tension of DC charge alternator drive belt.
Blockage in radiatorInspect radiator shroud and ducting for blockage and remove any foreign matter.
CFail to crank (AUTO mode only)See General Troubleshooting —fail to crank
Damaged or loose electrical cordInspect the mast electrical cord for damage and check the cord connections inside the control box.
Faulty thermostatContact a GMASD to replace.
Generator output incorrectCheck the incoming voltage to the ballast driver by checking the available voltage on the GFCI receptacle. Incoming voltage should be 120V ± 5V. If voltage is incorrect, the generator may require service.
High coolant temperature shutdownLow coolant levelAdd coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210 °F (99 °C) or more.
Illuminated LED indicates faultSee Troubleshooting
Incorrect mix/frozen radiatorThaw the radiator with an external heat source and flush the coolant system with the correct coolant mixture.
Leakage in coolant hoses, engine block, or water pumpInspect for visible leaks. Verify tension of water pump serpentine drive belt. Remove load on generator and restart engine. Verify coolant temperature and shut engine down immediately if it starts to overheat. Refer to the OEM engine operator’s manual for additional information on engine overheating.
Loose lighting connectionsInspect the connections inside the mast junction box and each mast light housing/socket.
Low oil pressure shutdownLow oil levelVerify oil level on dipstick. Add oil, if needed.
Mast lights off, checking inside control boxLoose lighting connectionsInspect the connections inside the control box.
Mast lights off, checking outside control boxLight fixture is too hotAllow light to cool 10–15 minutes before restarting.
Oil leaking from engineInspect the engine for leaks.
PAS engagedVerify PAS is off.
Restricted air filterInspect air filter for blockage. Refer to OEM engine operator’s manual for additional information.
Unit cranks but does not startLow fuel levelCheck fuel level in tank. Verify fuel pump operation.
Water pump failureContact a GMASD to replace.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.