Microcomputer Controller

The Microcomputer is a generator-set controller. It is used on generator sets from Kohler, including the Fast-Response I.

1
Generator sets
Kohler
Brand

Generator sets using this controller

1
Kohler Fast-Response I

Troubleshooting

60

Fault codes

CodeMeaningCause
F1F1 Fuse - Remote Annunciator (3 Amp.) blownDefective Decision Monitor; Defective Remote Annunciator; Defective Audio-Visual Alarm (accessories connected to controller TB42A)
F2F2 - Controller (3 Amp.) blownShorted speed sensor; Shorted DC supply to indicator panel; Shorted controller circuit board
F3F3 - Engine and Accessories (15 Amp.) blownIf equipped with K4 (emergency stop) relay: Defective engine electrics; Defective overvoltage board; Defective circuit board
F3F3 - Engine and Accessories (15 Amp.) blown (genset not equipped with K4 relay)Defective gauges; Defective safeguard breaker/voltage regulator; Defective engine run circuit; Defective crank circuit

Symptoms & remedies

SymptomCauseRemedy
A1 and A2 leads damaged or openDamaged or open exciter armature leadsRepair A1 and A2 leads; solder and insulate splices; use new sleeving when tying leads to shaft or heat sink
A1 or A2 leads shorted to groundGrounded exciter armatureRepair A1 and A2 leads; solder and insulate splices; use new sleeving when tying leads to shaft or heat sink; replace rotor assembly if test should show armature shorted or grounded
AVR not functioning properly15 Amp. fuse (if equipped) blownCheck 15 Amp. fuse (if equipped)
AVR not functioning properly (AC voltage does not decline when engine speed drops below approximately 58 Hz at 60 Hz operation or 48 Hz at 50 Hz operation)Open or shorted circuit between leads V7 and V8 (voltage sensing leads) from voltage regulator (AVR) to controller terminal stripIf these circuits are open or shorted, repair or replace
Battery Charger Fault (if battery charger equipped)Generator Master Switch in OFF/RESET; engine switch in RUN position. Ground controller terminal TB 61 to test. If Battery Charger lamp lights, circuit is functioning properly.
Ceiling voltage is not read during flashlight testExciter armature faultyGo to exciter armature test
Continuity between field leads and rotor assemblyGrounded generator fieldRepair F3 and F4 if test should show leads shorted to ground; solder and insulate splices; use new sleeving when tying leads to shaft or heat sink; replace generator rotor assembly if tests show a short or ground
Engine cranks but will not startLow fuelCheck fuel supply, replenish as necessary.
Engine starts and runs, but overcrank lamp flashesK3 relay not energizingVerify voltage to relay. If voltage at relay, check resistance of relay coil (see relay coil and voltage check preceding).
Engine starts and runs, but stops after approximately 25 secondsExcessive speed sensor air gapAdjust to 0.020 in. (0.508 mm). See Figure 3-7.
Engine will not crank with Generator Master Switch in RUN position (circuit board receiving power - relays energized)Fault shutdown: High Engine Temperature, Low Oil Pressure, Overspeed, Overcrank, Low Coolant Level, High Engine Oil Temperature or OvervoltageCorrect fault - See "Resetting" procedure in Section 2.
Engine will not crank with Master Switch in RUN position (no power to controller circuit board)Battery weak or deadRecharge or replace battery. Verify proper operation of battery charger.
Engine will not crank with master switch in TEST position (CR and 1CR relays not energizing)Battery weak or deadRecharge or replace battery. Check battery charger.
Exciter armature faultyShorted winding(s); low resistance readings (under 0.1-0.2 ohms)Replacement of rotor assembly
Exciter armature leads damaged or openDamaged or open A1 and A2 leads (one-piece activator) or AC leads (split activator)Repair A1 and A2 leads (one-piece activator) or AC leads (split activator); solder and insulate splices; use new sleeving when tying leads to shaft or heat sink
Exciter armature leads shorted to groundLeads shorted to groundRepair A1 and A2 or AC leads; solder and insulate splices; use new sleeving when tying leads to shaft or heat sink
Exciter armature shorted or groundedArmature shorted or groundedReplace rotor assembly
Exciter armature winding insulation deteriorated (megohmmeter reading less than 500K ohms approx. to rotor shaft and A1 or A2 lead or either AC lead)Deterioration of winding insulation and possible current flow to groundRepair or replacement of the rotor is necessary
FR activator defectiveNo continuity between terminals E and F3 of the FR activator with leads disconnectedGenerator rotor is shorted to ground; replace or repair generator rotor assembly and replace FR activator
Fluctuating VoltageImproper connections of generator output leadsCheck the generator output leads for proper connections (refer to Section 7, Wiring Diagrams)
Fluctuating voltageGenerator output leads improperly connectedCheck the generator output leads for proper connections (refer to Section 7, Wiring Diagrams)
Fuse blows — generator set will stop; unit will not crank with a blown fuseWiring short circuit or circuit overloadIf set has stopped due to causes other than lack of fuel, or fault shut-down—check the fuse. If blown, replace the fuse and attempt to restart generator set. If the set will not start, or if the fuse blows again, locate and correct the cause.
Generator field winding insulation deteriorated (megohmmeter reading less than 500K ohms approx. to F3 or F4 lead or F+ and F-)Deterioration of winding insulation and possible current flow to groundRepair or replacement of the rotor assembly is necessary
Generator set inoperable — 1-Amp fuse will blowBattery connections reversed (negative ground control system)
Grounded generator fieldContinuity between field leads and rotor assemblyRepair F3 and F4 (one-piece activator) or F+ and F- (split activator) if test shows leads shorted to ground; solder and insulate splices; use new sleeving when tying leads to shaft or heat sink; replace generator rotor assembly if tests show a short or ground
High resistance across "A", or continuity across "B" and groundOpen windings; faulty statorReplace stator
High water temperature fault shutdown — HWT contacts close, 1TS switch times out causing CR relay to deenergize, reset lamp lights, CR relay contacts open shutting off fuel solenoid or ignition coilHigh water temperature
Instrumentation not functioning properlyLoose input or instrument lead connection at AC Fuse Terminal Block (TB3)Check connections at AC Fuse Terminal Block (TB3).
Lamp circuit board not functioning (fault lamps and alarm horn)No input voltage to lamp circuit board. If no fault lamps illuminate when lamp test switch is pressed, check for input voltage on lamp circuit board.If lamp circuit board is receiving input voltage, lamp circuit board may be defective. If lamp circuit board is not receiving input voltage, refer to microcomputer circuit board troubleshooting procedure covered previously in table.
Low Battery Volts (if battery charger equipped)Generator Master Switch in OFF/RESET; engine switch in RUN. Ground controller terminal TB 62 to test. If Low Battery Volts lamp lights, circuit is functioning properly.
Low coolant level fault shutdown (if equipped) — coolant level switch closes, 1TS switch times out causing CR relay to deenergize, reset lamp lights, CR relay contacts open shutting off fuel solenoid or ignition coilLow coolant level
Low oil pressure fault shutdown — LOP contacts close, 1TS switch times out causing CR relay to deenergize, CR relay contacts open shutting off fuel solenoid or ignition coil, reset lamp lightsLow oil pressure
Low resistance readings (under 0.1-0.2 ohms) across A1 and A2Shorted exciter armature windingReplace rotor assembly
No DC voltage observed at 3B (+) and 5B (-) at the LED boardAVR not functioning properlyRefer to the AVR test
No continuity between terminals E and F3 of the FR Activator with leads disconnectedFR Activator defective and/or generator rotor shorted to groundReplace or repair generator rotor assembly and replace FR Activator
No output observed during LED flashlight testPhoto transistor board or FR Activator faultyCheck the photo transistor board and the FR Activator
No output on any phaseSafeguard breaker open (if equipped)Close the safeguard breaker, and with set running check AC voltmeter for proper output voltage
No voltage at K1 - solenoid coilOpen CR, 1CR, or CC contacts in series with SS solenoid. Open in P5 connector (pin 4). Open in P1 connector (pin 16).Repair or replace.
No voltage read at 3B/5B connector pointsWiring faulty or voltage regulator faultyRepair wiring or replace voltage regulator
No voltage reading at 1B (+) and 7N (-) at the voltage regulator harness plugWiring to the Safeguard breaker, CR relay or 15-Amp fuse faultyCheck the wiring to the Safeguard breaker, CR relay or 15-Amp fuse
Ohmmeter does not respond during photo transistor board testMeter polarity may be reversedReverse ohmmeter leads and repeat check
Output does not drop to low voltage when flashlight is removedFR Activator faultyReplace FR Activator. See "FR Activator".
Over-voltageProblem lies in photo transistor circuit and/or FR-Activator (over-voltage continues after disconnecting harness plug at voltage regulator)See "Component Testing"
Overcrank fault shutdown — after 30-60 seconds of cranking the 1CR relay will not energize, 1TS times out causing CR relay to deenergize, reset lamp lights, CR relay contacts open shutting off SS relay, fuel solenoid or ignition coilEngine does not start after 30-60 seconds of cranking
OvervoltageProblem lies in the photo transistor circuit and/or FR activator (overvoltage continues with harness plug disconnected at AVR)Proceed through the following checks
Overvoltage - Generators with Split FR ActivatorPhoto transistor board visibly damaged (open foil pattern, heat discoloration)Replace photo transistor board if visibly damaged; if overvoltage continues after replacement, proceed to step 2
Overvoltage - Generators with Standard FR ActivatorGrounded "C" lead on photo transistor boardCheck the photo transistor board for a grounded "C" lead; check the photo transistor board as described in "Component Testing"
Photo transistor board does not respond (ohmmeter does not respond after reversing leads)Defective photo transistor boardReplace photo transistor board and harness assembly
Resistance across F3 and F4 leads not 2-3.75 ohms, + 5%Generator field faultyRepair or replace as necessary
Safeguard breaker opens — battery voltage is shut off to the voltage regulator resulting in a loss of generator AC output; 1CR relay deenergizes, 1TS switch times out in approximately 30-60 seconds and trips causing the CR relay to deenergize, reset lamp will light, engine stopsSustained overload or short circuit sensed by Safeguard Breaker
Split FR activator component of unknown quality defective (test fixture light bulb does not light or is lit prior to receiving external light source)Defective activator component being tested (e.g., SCR assembly)Replace the SCR assembly
Stator open windingsHigh resistance across "A" or continuity across "B" and groundReplace stator
Stator shorted windingsBurnt or hot windingsReplace stator if windings are burnt or hot
Stator windings burnt or hotShorted windingsReplace stator if windings are burnt or hot
Unit cranks but will not startNo fuelCheck for fuel at pump or carburetor. Check for clogged fuel filter. Check engine fuel system.
Unit runs for 30-60 seconds then shuts downNo AC output available to 1CR relay coil. Safeguard breaker (if equipped) must be closed.Check for 120 volts AC to controller terminal strip V0 and V8. See generator troubleshooting (No Output). If 1CR relay does not energize, normally closed contact of relay will energize 1TS thermal switch and shut down unit.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.