The Katolight Kassec is a generator-set controller. It is used on generator sets from Katolight, including the KASSEC.
| Symptom | Cause | Remedy |
|---|---|---|
| FAIL TO CRANK | Blown Fuse on Terminal #1 ~° [Shorted leads when hooking up or overloaded circuits. | Replace fuse with 9 amp fuse. |
| UNIT CRANKS, DOES NOT START | Fuel Supply Empty fuel tank. Air in fuel lines. Wrong pressure on Natural Gas or LPG. | |
| UNIT STARTS BUT STARTER DOES NOT DISENGAGE | No voltage on Terminal #3 Starter drive could be hanging up or the solenoid on starter is not disengaging. | |
| UNIT WILL START THEN FAIL | Failure Lights Overcrank light lit - Lost signal on Mag Pickup, Crank Disconnect Terminal or lost signal on Auxiliary Crank Disconnect Terminal after unit started. Low Oil light lit - Low oil in crankcase. Oil pump failed. Defective pressure switch. High Water Temperature light lit - Low water level in radiator. Thermostat closed. Broken fan belt. Restricted flow through radiator. Ambient temperature too high. Defective temperature switch. Overspeed light lit - Last governor control. Defective overspeed switch. |
Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.