Katolight Kassec Controller

The Katolight Kassec is a generator-set controller. It is used on generator sets from Katolight, including the KASSEC.

1
Generator sets
Katolight
Brand

Generator sets using this controller

1
Katolight KASSEC

Troubleshooting

4

Symptoms & remedies

SymptomCauseRemedy
FAIL TO CRANKBlown Fuse on Terminal #1 ~° [Shorted leads when hooking up or overloaded circuits.Replace fuse with 9 amp fuse.
UNIT CRANKS, DOES NOT STARTFuel Supply Empty fuel tank. Air in fuel lines. Wrong pressure on Natural Gas or LPG.
UNIT STARTS BUT STARTER DOES NOT DISENGAGENo voltage on Terminal #3 Starter drive could be hanging up or the solenoid on starter is not disengaging.
UNIT WILL START THEN FAILFailure Lights Overcrank light lit - Lost signal on Mag Pickup, Crank Disconnect Terminal or lost signal on Auxiliary Crank Disconnect Terminal after unit started. Low Oil light lit - Low oil in crankcase. Oil pump failed. Defective pressure switch. High Water Temperature light lit - Low water level in radiator. Thermostat closed. Broken fan belt. Restricted flow through radiator. Ambient temperature too high. Defective temperature switch. Overspeed light lit - Last governor control. Defective overspeed switch.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.