HomeControllersKatolight Automatic Start controls

Katolight Automatic Start controls Controller

The Katolight Automatic Start controls is a generator-set controller. It is used on generator sets from Katolight, including the KLAS 103, KLAS 110 and KLAS 133.

3
Generator sets
Katolight
Brand

Generator sets using this controller

3
Katolight KLAS 103Katolight KLAS 110Katolight KLAS 133

Troubleshooting

4

Symptoms & remedies

SymptomCauseRemedy
Fail to crankBlown fuse
Unit cranks, does not startLow battery Voltage at start solenoid Voltage on Terminal No. 10May have defective battery or charger may not be functioning. Could have corroded or loose battery connection.
Unit starts, but starter does not disengageVoltage on Terminal No. 10May have gone into overcrank and shutdown. If this happened, may not have received crank disconnect signal on Terminal No. 10.
Unit will start then failLoss of fuel Failure light Loose or open connections Voltage on Terminal No. 10May have empty tank — bleed fuel supply line. Gas units may have wrong pressure, 4-6 psi. on naturally aspirated units. Turbo charged units require higher pressure. if present, may have defective fuel valve or ignition system or loose connection. If no voltage present, may have dirty Contact 4-7 Relay 1 in engine control. Tank may be empty — fuel line may be broken or loose.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.