Katolight Automatic Start controls Controller

The Katolight Automatic Start controls is a generator-set controller. It is used on generator sets from Katolight, including the KLAS 103, KLAS 110 and KLAS 133.

3
Generator sets
Katolight
Brand

Generator sets using this controller

3
Katolight KLAS 103Katolight KLAS 110Katolight KLAS 133

Troubleshooting

9

Symptoms & remedies

SymptomCause
Fail to crankBlown fuse
Should unit fail to crankBattery
Unit cranks but does not startFuel and fuel supply lines for dirt or leaks
Unit cranks continuously (over 100 seconds)Time delay relay 9 - may be defective
Unit cranks, does not startLow battery Voltage at start solenoid Voltage on Terminal No. 10 Fuel supply Voitage on Terminal No. 3
Unit starts but starter does not disengageAll leads in crank disconnect circuit for continuity
Unit starts, but starter does not disengageOvercrank = May not have received crank disconnect signal on Terminal No. 10 — defective timer. Low oil = Low oil level in crank-case — oil pump failed — defective switch. High water = Low water level in radiator — thermostat closed — broken fan belt — restricted air flow through radiator — ambient temperature too high — Defective switch. Overspeed = Lost governor control — defective switch.
Unit will start then failLoss of fuel Failure lights Loose or open connections Voltage on Terminal No. 10 Malfunctioning starter
Unit will start, then failFuel and fuel supply filters