Electronic Voltage Regulator Controller

The Electronic Voltage Regulator is a generator-set controller. It is used on generator sets from Cummins/Onan and Mitsubishi, including the MDG.

10
Generator sets
2
Brands
6–42 kW
Power range

Generator sets using this controller

10

Used across brands: Cummins/Onan, Mitsubishi

Also fitted to: Cummins/Onan RBAA Hydraulic Genset (10kW), Cummins/Onan RBAA Hydraulic Genset (15kW), Cummins/Onan RBAA Hydraulic Genset (6kW), Cummins/Onan RBAA Hydraulic Genset (8kW).

Troubleshooting

7

Fault codes

CodeMeaningRemedy
F1Blown Fuse (F1)Replace with a 20 amp (yellow) blade-type fuse (Page 29). If the new fuse blows, check for ground faults in harnesses 338-4084, 338-4085 and 338-4087 and replace as necessary (Page 23 or 26).

Symptoms & remedies

SymptomCauseRemedy
Frequency too high or too low or erraticMisadjusted frequencyAdjust frequency as necessary (Page 19).
No output or air discharge — engine runningON/OFF Switch OFFTurn the switch ON.
No output — genset running and air dischargingLine circuit breaker (vehicle AC distribution panel) OFF, TRIPPED or faultyA. If the circuit breaker is OFF, find out why, make sure it is safe to reconnect power, and then switch it ON. b. If the circuit breaker TRIPPED, shut down the genset and repair the shorted or grounded equipment that caused tripping. c. Replace a faulty circuit breaker.
Noisy generatorLoose brush block or fan, worn bearing or misaligned rotor and motorSee an authorized Onan dealer.
Noisy pump or motor (rattling sound)Air trapped in hydraulic fluidPurge the air and refill the oil reservoir as necessary (Page 17).
Output voltage too lowMisadjusted frequencyAdjust frequency as necessary (Page 19).

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.