HomeControllersDSE6010

DSE6010 Controller

The DSE6010 is a generator-set controller.

Specifications

ProtectionsIP65 (Front of module when module is installed into the control panel with the optional sealing gasket), IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel), NEMA 12 (Front of module when module is installed into the control panel with the optional sealing gasket), NEMA 2 (front of module when module is installed into the control panel WITHOUT b
Digital inputs["Auxiliary Digital inputs"]
Analog inputs["Auxiliary Analogue inputs"]
CommunicationsCAN
Relay outputs["Close Gen Output", "Close Gen Output Pulse", "Emergency Stop", "Energise To Stop", "Flexible Sensor High Shutdown", "Flexible Sensor High Warning", "Flexible Sensor Low Shutdown", "Flexible Sensor Low Warning", "Open Gen Output", "Open Gen Output pulse"]
Dimensions216mm x 158mm x 42mm (8.5” x 6.2” x 1.6”)

Troubleshooting

74

Fault codes

CodeMeaningCause
807Gas On Delay (Gas Engine Only)
808Gas Ignition Off Delay (Gas Engine Only)
809Crank Disconnect On Oil Pressure Enable
810Check Oil Pressure Prior To Starting
811Crank Disconnect On Frequency
812Under Speed Enable
815Over Speed Trip
817Low Battery Volts Enable
824High Battery Volts Warning Delay
825Charge Alt Shutdown Trip Enable
826Charge Alt Shutdown Trip
827Crank Disconnect On Oil Threshold
828Crank Disconnect On Engine Speed
830Low Battery Start Arming
832Low Battery Start Threshold
Generator High Voltage ShutdownGenerator High Voltage ShutdownThe generator output voltage has risen above the preset level
Generator Low Voltage ShutdownGenerator Low Voltage ShutdownThe generator output voltage has fallen below the preset level
High Coolant Temperature ShutdownHigh Coolant Temperature ShutdownThe module detects that the engine coolant temperature has exceeded the high engine temperature shutdown setting after the Safety On timer has expired.
Loss of Mag. Pickup SignalLoss of Mag. Pickup SignalThe speed signal from the magnetic pickup is not being received by the DSE controller.
Low Fuel LevelLow Fuel LevelThe module detects that the fuel level is below the configured setting
Low Oil Pressure ShutdownLow Oil Pressure ShutdownThe engine oil pressure has fallen below the low oil pressure trip setting level after the Safety On timer has expired.
Over Frequency ShutdownOver Frequency ShutdownThe generator output frequency has risen above the preset level
Over Speed ShutdownOver Speed ShutdownThe engine speed has exceeded the pre-set trip
Under Frequency ShutdownUnder Frequency ShutdownThe generator output frequency has fallen below the preset level
Under Speed ShutdownUnder Speed ShutdownThe engine speed has fallen below the pre-set trip after the Safety On timer has expired.

Symptoms & remedies

SymptomCauseRemedy
Battery High VoltageThe DC supply has risen above the high volts setting level for the duration of the high battery volts timer
Battery Low VoltageThe DC supply has fallen below the low volts setting level for the duration of the low battery volts timer
CAN ECU WarningThe engine ECU has detected a warning alarm and has informed the DSE module of this situation. The exact error is also indicated on the module’s display.
Charge Alternator FailureThe auxiliary charge alternator voltage is low as measured from the W/L terminal.
Digital Input A-DAuxiliary Digital inputs can be user configured as Digital inputs and will display the relevant icon.
Analogue Input A-CAuxiliary Analogue inputs can be user configured as Digital inputs and will display the relevant icon.
Fail To StopThe module has detected a condition that indicates that the engine is running when it has been instructed to stop. ‘Fail to Stop’ could indicate a faulty oil pressure sensor - If engine is at rest check oil sensor wiring and configuration.
Generator High Voltage WarningThe generator output voltage has risen above the pre-set pre-alarm setting.
Generator Low Voltage WarningThe generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On timer has expired.
High Coolant Temperature WarningThe module detects that the engine coolant temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired.
Low Oil Pressure WarningThe module detects that the engine oil pressure has fallen below the low oil pressure pre-alarm setting level after the Safety On timer has expired.
Low Fuel LevelThe module detects that the fuel level is below the configured setting
Over Frequency WarningThe generator output frequency has risen above the pre-set pre-alarm setting.
Over Speed WarningThe engine speed has risen above the overspeed pre alarm setting
Under Frequency WarningThe generator output frequency has fallen below the pre-set pre-alarm setting after the Safety On timer has expired.
Under Speed WarningThe engine speed has fallen below the underspeed pre alarm setting
Flexible SensorThe flexible sensor warning alarm has been triggered.
CAN ECU Data FailThe module is configured for CAN operation and does not detect data on the engine Can datalink.The engine shuts down.
CAN ECU ShutdownThe engine ECU has detected a shutdown alarm and has informed the DSE module of this situation. The exact error is also indicated on the module’s display.
Emergency StopThe emergency stop button has been depressed. This is a failsafe (normally closed to battery negative) input and will immediately stop the set should the signal be removed.NOTE:- The Emergency Stop Negative signal must be present otherwise the unit will shutdown.
Fail To StartThe engine has not fired after the preset number of start attempts
Temperature sensor open circuitTemperature sensor has been detected as being open circuit.
Oil pressure sensor open circuitOil pressure sensor has been detected as being open circuit.
Magnetic pickup open circuitMagnetic pickup sensor has been detected as being open circuit.
ry Volts
CAN ECU Power
CAN ECU Stop
Charge Alternator Shutdown
Charge Alternator Warning
Close Gen Output
Close Gen Output Pulse
Common Alarm
Common Electrical Trip
Common Shutdown
Common Warning
Energise To Stop
Fuel Relay
Gas Choke On
Gas Ignition
Generator Available
Generator High Volts Shutdown
Generator Low Volts Shutdown
Low Oil Pressure Shutdown
Flexible Sensor High Shutdown
Flexible Sensor High Warning
Flexible Sensor Low Shutdown
Flexible Sensor Low Warning
Oil Pressure Sender Open Circuit Alarm
Temperature Sender Open Circuit Alarm

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Extracted directly from this controller's manual.